Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Stuart-Hobson Middle School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200117134 01 9/4/01 (STUART-HOBSON) 1. ASBESTOS ASSESSMENT REQUIRED. 2ND FLOOR/NEAR BOYS BATHROOM: WATER FOUNTAIN CONSTANTLY RUNNING, MAKING A LOT OF NOISE. ASBESTOS CODE A -CLEAR FOR REPAIRS ON 08/13/01. SYLVIA GRIMES - SAFETY (202)576-5583 | |||
| FM-200120437 01 10/19/01 (STUART-HOBSON) MARBLE STONE ON FRONT STEPS IS VERY LOOSE. THIS IS CONSIDERED A SAFETY HAZARD AND IT NEEDS ATTENTION IMMEDIATELY. | |||
| FM-200203260 02 2/22/02 (Stuart-Hobson) ***Urgent*** First Floor Room 105 The wall outlet needs to be replaced because it trips the breaker to the "off" position. Fire has also come out of the outlet [safety hazard]. | |||
| FM-200125684 /01 3/12/02 (STUART-HOBSON) ASBESTOS ASSESSMENT REQUIRED THIRD FLOOR GIRLS BATHROOM FLUSH VALVE ON COMMODE IS LEAKING IN GIRLS BATHROOM (TRIED TO CUT IT OFF, BUT IT IS AN OLD ONE). NEED IMMEDIATE ATTENTION DUE TO IT LEAKING DOWN INTO THE 2ND FLOOR GIRLS BATHROOM CEILING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/27/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) | |||
| FM-200201093 02 8/20/02 (STUART-HOBSON) ASBESTOS ASSESSMENT REQUIRED REPAIR FAUCET ON THREE-COMPARTMENT SINK (WATER IS LEAKING). ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/28/02 RICHARD GIBSON - SAFETY (202)576-5584 (RG)-01/28/02 | |||
| FM-200213892 02 11/25/02 (Stuart Hobson) Fire code violation; 1. Asbestos assessment required. Boys Gym: Broken door hardware. Asbestos Code A - Clear for repairs on 08/13/02 . Leroy Minton / Safety Office 202-576-8962. | |||
| FM-200213893 02 11/25/02 (Stuart Hobson) Fire code violation; Page 3 of 3 Basement Storeroom: Water leaking near light. Asbestos Code A - Clear for repairs on 08/13/02 . Leroy Minton / Safety Office 202-576-8962. | |||
| FM-200224375 03 1/24/03 Stuart-Hobson Third floor - room 305 Top of window fell down and can not get it back up. Cold air is coming in room. Consider a safety hazard and it need immediate attention. | |||
| FM-200224372 03 1/24/03 Stuart-Hobson First floor - room 102 Bottom window is off track and when you pull window up it comes out. Consider a safety hazard. | |||
| FM-200224374 03 1/24/03 Stuart-Hobson First floor - room 104 Window fell down and spring fell out on side. Curtodian get window back up, but it needs attention. Consider a safety hazard. | |||
| FM-200224376 03 1/24/03 Stuart-Hobson Basement - girls gym Window from top keeps falling down, due to the springs are weak and and falling down. Consider a safety hazard and it need immediate attention. | |||
| FM-200226682 03 3/13/03 Stuart-Hobsob First floor main office lavatory Hot waterside of sink will not cut off. No cut off valve operational. Safety hazard | |||
| FM-200225325 03 3/24/03 Stuart-Hobson First floor annex hall Exit door has one working hinge holding door up. Door almost fell on an student. This is considered an fire code violation and safety. | |||
| FM-200224186 03 3/26/03 Stuart-Hobson Boiler Room Replace low water cut out on Boiler #1 URGENT!!!!! | |||
| FM-200222481 /02 3/26/03 Stuart-Hobsos Boiler room URGENT Asbestos assessment may be required. Replace 4" stop valve ont the domestic hot water storage tank line, so contractor can replace new temerture regulator valve. Asbestos Code A - Clear For Repairs On 12/13/02. Horne Engineering - Roger Kager (RG 12/13/02) | |||
| FM-200228828 03 4/17/03 Stuart-Hobsob First floor -room 106 Window has come out the frame and could not get it back in. This a considered an safety hazard. | |||
| FM-200228827 03 4/17/03 Stuart-Hobsob Basement - VMJ Center Window fell down from the top and when custodian try to put the window back up it fell back down an the pane broke up in it. This is considered an safety hazard and needs immediate attention. | |||
| FM-200228829 03 4/22/03 Stuart-Hobson Basement cafeteria Door going out to playground, needs door plate at the bottom, bolted down, because one screw is holding it in place. This is an safety code for students and staff. | |||
| FM-200330010 03 5/15/03 (Stuart-Hobson) !!!VERY URGENT!!! 1st Floor/Boys restroom: Students pulled sink off wall; pipes broken, and water flooded the floors. Engineers have water under control. The water has been shut off. | |||
| FM-200217668 02 7/29/03 Stuart-Hobson ****Urgent**** Basement VMJ Center 1. The wall light switch has a short in it. The computer room needs a well-lit area; and 2. Floor oujtlet needs to be replaced because fire came out of the plug when a teacher tried to use it---also tripped the breaker to the "off" position. | |||
| FM-200208747 02 7/29/03 Stuart-Hobson Third (3rd) Floor - Classroom #212 Wall outlets are not working on one side of the room. When teacher put plug in outlet fire came out! This considered on Emergency situations. Safety Hazard. \\ Asbestos Code A - Clear for repairs on 05/05/03. Horne Engineering - Philp Connolly (RG 05/07/03) | |||
| FM-200341512 /03 12/29/03 Stuart-Hobson Main office Knob lock an door has been jammed so that principal can not get out the door. This is consider a safety hazard and fire code violation. This need immediate attention. | |||
| FM-200114490 01 3/17/04 STUART-HOBSON (1) SURVEY ELECTRICAL CAPACITY TO DETERMINE WHETHER THE ROOMS WILL HANDLE THE LOAD. (2) INSTALL NEW WINDOW A/C UNITS IN THE FOLLOWING LOCATIONS.: AUDITORIUM - (4) 28,000 BTU ROOM 201 - (1) 28,000 BTU ROOM 200 - (1) 25,000 BTU ROOM 204 - (1) 25,000 BTU ROOM 205 - (1) 25,000 BTU ROOM 207 - (1) 25,000 BTU TEACHERS LOUNGE (1) 25,000 BTU AUDITORIUM - (6) 28,000 BTU Code A Clear for repair by Leroy Minton, Jr. DCPS Safety 07-31-02 DCPS Safety-Sheila R. Howard 07-31-02 | |||
| FM-200338409 03 3/17/04 Stuart-Hobson First floor Room 105, 106 and 207 Window fell down from top, the window back up it will not stay up. This is consider a safety hazard for the students, also cold coming into room. | |||
| FM-200227460 03 3/17/04 Stuart-Hobson First floor room 102 Hinge that holds door together has been off also door is very hard to close. This is consider an fire code violation. and safety hazard. Asbestos Code A-clear for repair by DCPS on 04/07/03 Charles Buchanan | |||
| FM-200222311 /02 3/17/04 Stuart-Hobson Third floor - room 305 Doors is pulled from the hinges and locked is hard to lock. Considered an safety and fire code violation. Asbestos Code A - Clear for repairs on 12/12/02. Horne Engineering - Bipin Nanavaty (RG 12/13/02) | |||
| FM-200222310 /02 3/17/04 Stuart-Hobson First floor - exit door Screws and brackets off in the door hinges, top of door hinges are hanging down. Considered an safety and fire code violation. Asbestos Code A - Clear for repairs on 12/12/02. Horne Engineering - Bipin Nanavaty (RG 12/13/02) | |||
| FM-200222308 /02 3/17/04 Stuart-Hobson Second floor - room 201 Door is pulled from hinges and hard to close to lock the door. Considered an safety and fire code violation. Asbestos Code A - Clear for repairs on 12/12/02. Horne Engineering - Bipin Nanavaty (RG 12/13/02) | |||
| FM-200218492 02 3/17/04 (Stuart-Hobson) ***Urgent*** Basement Custodian's Office Restroom Replace faulty flush valve. When flushed, the water will not go down and the custodian's need to be able to use this restroom. | |||
| FM-200206493 02 3/17/04 (Stuart-Hobson) 1. Asbestos assessment required. Basement/court yard cafeteria: Drain stopped up and backing up. When it rains court yard floods; as of this date, court yard is still flooded. Asbestos Code A - Clear for repairs on 04/24/02. DCPS Safety - Richard Gibson (04/24/02) | |||
| FM-200203264 02 3/17/04 (Stuart-Hobson) ***Urgent*** First Floor Main Office Repair or replace bad ballast which is causing the light not to function. This light is over the top of the secretarys desk making it hard for her to see. | |||
| FM-200445964 04 3/29/04 Stuart-Hobson Boiler Room URGENT URGENT URGENT!!!!!!!!!! Boiler #1 Replace safety valve, Valve keep popping. School will be without heat if repairs are not made today 3/29/04. boilers 2 and 3 are down | |||
| FM-200443187 04 4/21/04 (Stuart-Hobson) !!!URGENT!!! 3rd Floor/Boys Bathroom: Repair cut-off valves are broken under the sink. Students are unable to wash their hands; please respond as soon as possible. | |||
| FM-200445489 04 7/4/04 Stuart-Hobson URGENT Basement kitchen Compact sink has an crack on side of sink. Water leaks down on the floor a lot. Cafeteria worker almost slipped up due to water being all over the floor. This needs immediate attention. | |||
| FM-200458776 /04 12/7/04 Stuart- Hobson Boiler Room Boiler #2 need safety valve . | |||
| FM-200459378 04 1/3/05 Stuart-Hopson Outside steps leading to boiler room Repair or replace metal railing on the steps leading to the boiler room. Asbestos Code A - Clear for repairs on 12/09/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200456939 /04 8/1/05 Stuart-Hobson Exterior Grounds 1) Change safety rails and extend surface 8 feet by fireman pole. Poc - Oscar Mebane - 202-345-0688 | |||
| FM-200457125 /04 8/1/05 (Stuart Hobson) !!!URGENT!!! 2nd Floor: Broken door hinge. Asbestos Code A - Clear for repairs on 10/21/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200457124 /04 8/10/05 (Stuart Hobson) !!!URGENT!!! Basement/Kitchen: Hot water handle broken on sink in the kitchen. Asbestos Code A - Clear for repairs on 10/21/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200509688 05 8/11/05 (Stuart-Hobson) "Urgent" Exterior main entrance. Repair or Replace panic bar. Note: Existing panic bar is not catching. | |||
| FM-200122021 /01 10/21/05 (STUART-HOBSON) THRU-OUT BUILDING LOCKERS ARE COMING AWAY FROM WALLS ON THE 1ST AND 2ND FLOOR, AND ALSO COMING APART. (SAFETY HAZARD) | |||
| FM-200218498 02 10/21/05 (Stuart-Hobson) 1st, 2nd & 3rd Floors/Boys' Restrooms 1. The panel on the wall behind the commode is coming off the wall [safety hazard] in the 1st floor boys restroom; and 2. Repair/replace push button knobs on the sinks in the boys' restrooms (all three floors) that are missing. The school does not have the parts on hand to make repairs. | |||
| FM-200445237 04 10/21/05 (Stuart-Hobson !!!VERY URGENT!!! Basement Level: Repair or replace aluminum sink that has a crack in the seam on the left side. This problem causes water to leak on the floor. | |||
| FM-200453471 04 12/1/05 Stuart-Hobson Fire Code Violation Room 216 Hardware on the door broken. Asbestos Code A - Clear for repairs on 08/30/04. DCPS Safety - Richard Gibson (RG 08/31/04) | |||
| FM-200453479 04 12/1/05 Stuart-Hobson Fire Code Violation First floor Panic hardware broken. Asbestos Code A - Clear for repairs on 08/30/04. DCPS Safety - Richard Gibson (RG 08/31/04) | |||
| FM-200453465 04 12/1/05 Stuart-Hobson Fire Code Violation Third floor Pentrating opening in the wall. Asbestos Code A - Clear for repairs on 08/30/04. DCPS Safety - Richard Gibson (RG 08/31/04) | |||
| FM-200514147 /05 1/20/06 (Stuart-Hobson) "Urgent" Ground floor, Kitchen Cafeteria. Plaster & Paint walls and ceiling in storage room located in the kitchen area. Note: Plaster and paint are falling into food. Lead & Asbestos Code A - Clear for repairs on 10/27/05. Tidewater - Rodney Distance (RG 10/28/05) | |||
| FM-200617401 06 1/30/06 Basement-VMJ Library Very Urgent Investigate, repair or replace electrical floor outlets in this area; there is no power in any of the floor outlets making usage of computers impossible. | |||
| FM-200457950 04 1/30/06 Stuart-Hopson Boile room Replace safety valves on boilers # 2 & 3 | |||
| FM-200510272 05 1/30/06 Stuart-Hobsen Urgent!! Second Floor-Room 201/Computer Lab. Change the lock. Note: Need to get into the room, then change the locks (the teacher left and lost the keys) | |||
| FM-200222306 /02 1/30/06 Stuart-Hobsob Basement - Cafeteria bathroom Ceiling fell out in two areas, due to the girls bathroom on first floor flooded. This is considered an health and safety hazard. Asbestos Code A - Clear for repairs on 12/12/02. Horne Engineering - Bipin Nanavaty (RG 12/13/02) | |||
| FM-200450265 04 1/30/06 (Stuart-Hobson) !!!URGENT!!! Basement/Hallway: Lights are out needs attention immediately. | |||
| FM-200217643 02 1/30/06 Stuart-Hobson ****Urgent**** 1st Floor Main Hallway 1. The hallway light has a short in it; and 2. The 5th Street side exit lights are completely out. | |||
| FM-200514136 /05 1/30/06 (Stuart-Hobson) "Urgent" Ground floor,Kitchen Repair or Replace garbage disposal. | |||
| FM-200514138 /05 1/30/06 (Stuart-Hobson) "Urgent" Ground floor,Kitchen Replace themocouple on deep fryer | |||
| FM-200206947 02 1/30/06 1st floor/Auditorium: 1. Asbestos assessment required. Door knob on door has broken off, needs to be replaced. Asbestos Code A - Clear for repairs on 05/02/02. DCPS Safety - Ronald Edwards (RG 05/03/02) | |||
| FM-200341516 /03 1/30/06 Stuart-Hobson First floor boys bathroom Plummers had ro cut hole on side of urinal to fix lines that so backed up. Replace urinal that was damaged while repairing fixtures lines. Safety hazard asbestos assessment. Asbestos Code A - Clear for repairs on 12/15/03. Horne Engineering - Troy Wilcome (RG 12/17/03) | |||
| FM-200124694 /01 2/3/06 STUART-HOBSON BOILER ROOM STEPS 1. ASBESTOS ASSESSMENT REQUIRED. REPLACE HANDRAILING ONSTEPS LEADING TO BOILER ROOM AND REPAIR OR REPLACE METAL LANDING. (SAFETY HAZARD). Requester Phone: 698-1750 Requestor Phone: 698-1750 Asbestos Code A - Cleared for repairs on 04-21-03 by Leroy Minton Jr. (LM/04-08-03) the Safety Office 202-576-8962. | |||
| FM-200340763 /03 2/7/06 stuart-Hobson Boys Gym Repair or replace 3/4" leaking steam line at entrance to boy gym. Code A - clear for exploratory if ACM is impact stop work and send back to the safety office 12/4/03 Sylvia Grimes. | |||
| FM-200447064 04 2/7/06 Stuart-Hobson Third floor room 305 Bottom of door get stuck when you try to close to lock it. ?This is considerate a fire code violation. Code A- clear for repairs as of 4/28/04 Sylvia Grimes safety . | |||
| FM-200515904 /05 2/7/06 Repair ceiling and falling plaster over top of the food service line in the cafeteria on the ground floor. Asbestos Code A - Clear for repairs on 11/30/05. DCPS Safety - Richard Gibson (RG) | |||
| FM-200512542 05 2/7/06 Stuart-Hobson Ground 4th St. side of bldg. Fence has been pulled away from support post, and is creating a safety hazard for the students. | |||
| FM-200517363 06 4/3/06 Very Urgent: Investigate and make necessary repairs to the steam line behind the lockers across from the #3 stairwell on the first floor. | |||
| FM-200217576 02 4/14/06 Stuart-Hobson ****Urgent*** 1st Floor Auditorium Water is coming in through the interior wall whenever it rains, damaging the inside window ledge. The exterior masonry wall needs pointing up and sealed to prevent the water coming through the interior wall. It has already been determined there is no drain problem [per Mr. Vernon]. POC: Mr. Vernon (202)576-8046 | |||
| FM-200222588 /02 8/25/06 REPAIR/REPLACE VALVE (STOP/SAFETY) | |||
| FM-200632268 /06 2/20/07 Repair boiler #3 off on flame failure. No heat in building. Urgent !!!!!! | |||
| FM-200514144 /05 3/5/07 (Stuart-Hobson) "Urgent" Ground floor, Cafeteria & Cafeteria Dressing room. Repair or Replace loose ceiling tiles and replace missing ceiling tiles in cafeteria over serving table tables. Note: Tiles are falling and recently feel during lunch period. HA 037 Ceiling tile white 1' X 1' with holes in straight lines No Asbestos HA 042 Plaster old school N0 Asbestos HA 742 Brown coat with HA 042 No Asbestos Code A-clear for repair by DCPS Charles Buchanan on 11/03/05 | |||
| FM-200218410 02 3/5/07 Stuart-Hobson ****Urgent**** Asbestos Assessment Reqd. Girls' Restroom Throughout Furnish and install handicapped railings in the first stall of all girls' lavatories on all floors. Bars may need to be placed behind the commodes. There is a handicapped student in the school who has classes on all floors [safety concerns]. Asbestos Code A-clear for repair by Horne Engineer Roger Kager DCPS Charles Buchanan on 09/27/02 | |||
| FM-200621460 06 3/5/07 Second Floor Teacher's Lounge - Asbestos Assessment Required - Has cracked and broken floor tiles. Asbestos Code D - on 04/19/06. Tidewater - Shamika Parker (RG 04/26/06) Asbestos Code A - Abated and repaire on 11/01/06 by Motir Services (LM-11/15/06) Safety Office 202-576-8962. |