Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Webb Elementary School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200113808 01 9/19/01 WEBB FIRST FLOOR EXIT DOOR 1) REPLACE BROKEN DOOR CLOSURE NEAR GIRLS RESTROOM ASBESTOS CODE A-CLEAR FOR REPAIRS ON 06/22/01. RONALD EDWARDS - SAFETY (202)576-6693 | |||
| FM-200119131 01 9/25/01 (WEBB) 1ST FLOOR / LEARNING CENTER #1 !!!!!!!!!!! EMERGENCY !!!!!!!! LIGHTS ARE POPPING AND SPARKING. (SAFETY HAZARD) | |||
| FM-200122233 /01 12/1/01 (WEBB) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ TEACHERS LOUNGE REPAIR OR REPLACE LOCK ON DOOR. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/14/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) | |||
| FM-200115843 01 12/5/01 WEBB 1ST FLOOR - TEACHER LOUNGE ASBESTOS ASSESSMENT REQUIRED REPAIR OR REPLACE LOCK ON DOOR. LOCK BROKEN. ASBESTOS CODE A-CLEAR FOR REPAIR ON 9/20/01 BY DCPS SAFETY CHARLES E. BUCHANAN (202-567-5582) | |||
| FM-200115006 01 12/5/01 WEBB LIBRARY 1) REPLACE CEILING TILE DUE TO A/C LEAK MATERIAL FALLING ON PCS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 07/10/01. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200124221 /01 1/17/02 (WEBB) ASBESTOS ASSESSMENT REQUIRED ENCLOSED COURT REMOVE BROKEN DRAIN PIPE BY EXIT DOOR. ASBESTOS CODE A-CLEAR FOR REPAIR 12/05/01 BY DCPS SAFETY RONALD EDWARD 202 439 8094 | |||
| FM-200125647 /01 1/22/02 (WEBB) GROUNDS/FRONT & REAR OF BUILDING REPAIR FENCE IN FRONT & REAR OF BUILDING (SAFETY HAZARD) | |||
| FM-200202849 02 2/26/02 (WEBB) ***URGENT*** 2ND FLOOR LEARNING CENTER II REPAIR PIPE CONNECTED TO URINAL WHICH IS LEAKING FROM THE WALL (HEALTH & SAFETY HAZARDS). | |||
| FM-200204092 02 3/11/02 (Webb) ****Urgent**** 1st Level Playground Side of Building Weld window guards back, which were pried away from the window overnight [may have been either valdalism or an attempted breakin]. | |||
| FM-200204942 02 4/1/02 (Webb) ***Very Urgent*** 1st floor/room #140: Window guard torn away from the window by vandals; window guard needs to be welded. | |||
| FM-200202850 02 4/9/02 (WEBB) 1ST FLOOR LEARNING CENTER I REPAIR & UNSTOP TWO SINKS WHICH ARE BACKING UP (HEALTH & SAFETY HAZARD) | |||
| FM-200204944 02 5/2/02 (Webb) ***Very Urgent*** 1st Floor/Main entrance: Repair or replace door closer. Asbestos Code A - Clear For Repairs On 03/27/02. Horne Engineering - Philp Connolly (RG 03/27/02) | |||
| FM-200210786 02 7/15/02 Webb ****Urgent**** Building Exterior [Ruptured Pipe]/Holbrooke St. Side A ruptured pipe is causing water to run down the street---neighbors are complaining and worrying about mosquito breeding. | |||
| FM-200217953 02 10/31/02 (Webb) AS SOON AS POSSIBLE 1st Floor/Room #120: Classroom door has fallen off hinges. (Instructed to remove door for safety) Asbesstos Code A-clear for repair by DCPS Charles E. Buchanan on 9/20/02 | |||
| FM-200221955 02 12/3/02 Webb Back of building - room 143 Window guards need to be re-welded before break in. Urgent | |||
| FM-200223766 03 1/16/03 (Webb) !!!VERY URGENT!!! 1st Floor hallway: Electrical panel box has fallen from the wall, electrical wires are exposed. | |||
| FM-200218901 02 1/24/03 (Webb) !!!VERY URGENT!!! 1st and 2nd floor: Electrical power lost throughout the 1st and 2nd floor; there are no lights in the classrooms. (10/04/02, approx. 4:39 p.m., personnel discovered it was a PEPCO PROBLEM) | |||
| FM-200105338 01 3/13/03 WEBB PARKING LOT AREA GROUNDS NEED TO BE LEVEL DUE TO DAMAGE BY DELIVERY TRUCK. IT IS A SAFETY HAZARD. | |||
| FM-200208034 02 7/29/03 Webb 1. Asbestos Assessment Reqd. 1st Floor Classrooms 147 [Head Start] 2. Install electrical outlets in rooms 147 [Head Start] to support window a/c units. Code A-clear for repair by DCPS Safety ( Leroy Minton ) on 5/21/02 | |||
| FM-200125648 /01 9/9/03 (WEBB) ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR BOYS RESTROOM REPAIR URINAL WHICH NEEDS A WAX RING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/22/01. RICHARD GIBSON - SAFETY (202)576-5584 (RG) | |||
| FM-200225259 03 9/9/03 (Webb) 2nd Floor - girls restroom: Repair one (1) toilet need to be unclog and four (4) sinks need to be unclog. Temperture on sinks need to be turn down. (Hot water side) URGENT | |||
| FM-200213822 02 9/10/03 Webb ****Urgent**** Westside of Building Restore water to the westside of the building---half of the building has no water. | |||
| FM-200225257 03 9/30/03 (Webb) First floor/Boys restroom: Repair two (2) flush valves, not working and repair four (4) toilets flush valves. Repair four (4) sinks, that need to be unclog, also a faucet need repairing. URGENT | |||
| FM-200228031 03 9/30/03 Webb First floor custodial closet Replace or repair fascet hot water turn off valve not working water runs constantly. URGENT | |||
| FM-200205917 02 10/8/03 Webb 2nd Floor Boys & Girls RestroomsUnclog hand sinks. P-traps were removed, but found to be clear. There is no hand-augur on site to snake out debris. Code A - Clear for repairs on 04-25-02. One foot of ACM insulation removed from a 3/4" pipeline to clear the way for necessary repairs on 04-25-02. (LMJ) Safety Office 202--576-8962. | |||
| FM-200228033 03 10/8/03 Webb Second floor learning center II Replace or repair two bradley basins. Not working. Health hazard URGENT | |||
| FM-200228770 03 10/8/03 (Webb) !!!VERY URGENT!!! 2nd Floor/Learning center-Teachers toilet: Water seeping around bottom of toilet, appears to be problem with wax ring. | |||
| FM-200339032 /03 10/20/03 (Webb) !!!URGENT!!! 1st Floor/Health Suite: Replace or replace lock on main door; lock is inoperable. | |||
| FM-200338853 /03 10/27/03 (Webb) !!!URGENT!!! 1st Floor/Mens Bathroom: Sink hanging off wall, please re-attached. Asbestos Code A - Clear for repairs on 10/23/03. Horne Engineering - Edward Rodriguez (RG 10/27/03) | |||
| FM-200447115 04 4/26/04 Webb Urgent !!! First Floor - 141 1) Slop sink pipe busted, no cut off valve. | |||
| FM-200444233 04 5/5/04 Webb Urgent !!! Outside Holbrook Street 1) Steps leading to building are deteriorating. Need to be repaired. Safety hazard !! | |||
| FM-200442972 04 5/28/04 Webb EMERGENCY First floor room 141A A cabinet need to be repair it is hanging down, before a child get hurt. Asbestos Code A - Clear for repairs on 01/20/04. Horne Engineering - Tony Marcolin (RG 01/21/04) | |||
| FM-200448836 04 6/3/04 (Webb) !!!VERY URGENT!!! 1st Floor/Boys Bathroom: Ruptured pipe on urinal, water running flooding the floors, unable to shut the water off. | |||
| FM-200449053 04 6/8/04 (Webb) !!!VERY URGENT!!! !!!VANDALISM!!! 1st Floor/Near Playground: Window guards removed due to attempted break-in. | |||
| FM-200115879 01 7/9/04 WEBB 1ST FLOOR - TEACHER LOUNGE ASBESTOS ASSESSMENT REQUIRED INSTALL 1 A/C 28000 (BTU). CONSTRUCT & INSTALL HOLDING CAGE OR PLATFORM. A/C ON SITE. ASBESTOS CODE A-CLEAR FOR REPAIR ON 9/20/01 BY DCPS SAFETY CHARLES E. BUCHANAN (202-567-5582) | |||
| FM-200201530 02 9/15/04 (WEBB) ASBESTOS ASSESSMENT REQUIRED 2ND FLOOR/LEARNING CENTER #2 ELECTRICAL PANEL BOX IS HOT & IS AFFECTING THE LIGHTS WHERE THE TEACHERS ARE INSTRUCTING STUDENTS--(LIGHTS ARE FLICKERING, CUTTING ON & OFF, ETC.) ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/24/02 RICHARD GIBSON - SAFETY (202)576-5584 (RG)-01/24/02 | |||
| FM-200340328 /03 9/27/04 (Webb) 1st Floor/Stairways: Replace light fixtures in stairways; need to be upgraded. (Very dark area) Safety Hazard | |||
| FM-200458146 /04 11/12/04 Webb First and Second floor hallway Replace light ballasts throughout hallway. URGENT hallway is dark in some areas (safety hazard). Asbestos Code A - Clear for repairs on 11/10/04. DCPS Safety - Leroy Minton Jr. (RG 11/10/04) | |||
| FM-200458612 /04 11/23/04 Webb Playgroung The sliding board has been vadalize, it need to be repaired before a kid get hurt, and the hole need to be covered. | |||
| FM-200457629 /04 12/1/04 (Webb) !!!VERY URGENT!!! Through-Out the Building: Replace filters in water fountains, low water pressure; students are covering the bubbler with their mouth in order to consume the amount of water needed. Health Hazard) | |||
| FM-200456231 04 12/6/04 Webb Fire Code Violation First floor Door self closing hardware broken across from room # 141B. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456228 04 12/6/04 Webb Fire Code Violation First floor Door closer hardware broken across from room # 137. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456247 04 12/6/04 Webb Fire Code Violation First floor Learning center # 1Breachs in the ceiling. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456226 04 12/6/04 Webb Fire Code Violation First floor Self closing door hardware broken across from room # 137. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456225 04 12/6/04 Webb Fire Code Violation First floor Ceiling breached in front of room # 139. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200459356 04 12/14/04 Webb Front door Need new hinges in order for the door to close. Asbestos Code A - Clear for repairs on 12/09/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200456538 04 1/4/05 (Webb) !!!VERY URGENT!!! Learning Center #1: Ballast burning, and smoking in the pre-k area. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Richard Gibson (RG) | |||
| FM-200459237 04 3/8/05 WEBB EXIT DOORS REPLACE DOOR CLOSERS Asbestos Code A - Clear for repairs on 12/08/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200502265 05 3/10/05 Webb EMERGENCY Under the stairwell the middle Need hole cover with plywood, befoe a child get hurt. | |||
| FM-200500314 05 3/21/05 Webb Second floor learning center 2 girls restroom The partition is preventing entrance to the restroom. Asbestos Code A - Clear for repairs on 01/11/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200450118 04 3/25/05 Webb Coirridor Replace 5 broken door closer's on exit doors. Asbestos Code A - Clear for repairs on 08/27/04. DCPS Safety - Richard Gibson (RG 08/28/04) | |||
| FM-200504821 05 4/28/05 (Webb) "Urgent" First floor, Learning Center/Second floor Replace flush valve on commode in (learning center). Unclog toilet in (second floor, boys' restroom). | |||
| FM-200456243 04 6/20/05 Webb Fire Code Violation First floor Auditorium the ceiling is breached. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456985 /04 8/1/05 Webb Middle stairway Repair breach in wall, this is a safety hazard. Asbestos Code A - Clear for repairs on 10/22/04. DCPS Safety - Leroy Minton Jr. (RG 10/22/04) | |||
| FM-200456986 /04 8/1/05 Webb Parking lot Repair or replace gate. Bulk trash is dump dailey, this matter has to stop. This is a safety and Health hazard. | |||
| FM-200507635 05 8/5/05 (Webb) !!!!VERY URGENT!!!! Outside Storage Outside storage door has been broken off the henges, and needs to be replaced. Code A-clear for repair by DCPS Charles Buchanan on 7/15/05 | |||
| FM-200509601 05 8/10/05 (Webb) "Urgent" 1st floor, Teachers' lounge. Install door knob lock. Note: Carpenters just installed door and there is no way to secure room. | |||
| FM-200340847 03 10/19/05 (Webb) !!!VERY URGENT!!! Roof Top: Mount trap door damaged by vandals attempting to break-in. | |||
| FM-200221016 /02 10/19/05 Webb First floor - Teacher's lounge Replace door - door has deteriorated. Urgent Safety Hazard Asbestos Code A - Clear for repairs on 12/12/02. DCPS Safety - Leroy Minton Jr. (RG 12/13/02) March 31, 2004: Staff called in with concern. | |||
| FM-200448831 04 10/19/05 (Webb) !!!VERY URGENT!!! 1st Floor/Teachers Lounge: Repair plexi-glass windows that are loose, and falling apart. There is a total of four windows, and one window fell to the ground. | |||
| FM-200228588 03 10/20/05 Webb URGENT First floor girls restroom Unstop two sinks need to be repaired. Health Hazard unable to wash there hands. | |||
| FM-200506183 05 10/20/05 ( WEBB ) URGENT!!!! First Floor - Room 141B 1) Repair/Replace sink faucet it's broken, preventing the pre-K class from washing their hands | |||
| FM-200447788 04 10/20/05 Webb Urgent !!! First Floor - Kitchen Repair or replace hot water faucet on sink. | |||
| FM-200447787 04 10/20/05 Webb Urgent !!! First Floor - Kitchen Repair pipe on hot water heater and top need to be repaired. Installation is needed on pipe. | |||
| FM-200340962 03 10/20/05 (Webb) !!!VERY URGENT!!! 2nd Floor/Girls Restroom: Busted pipe on toilet flush valve. (Leaking) | |||
| FM-200330416 03 10/20/05 Webb !! EMERGENCY !! First Floor - Stairwell #1 1. Pipe burst behind wall in stairwell #1 water seeping from wall ,please repair . Asbestos Code A - Clear for repairs on 06/26/03. DCPS Safety - Ronald Edwards (RG 06/26/03) | |||
| FM-200445231 04 10/20/05 (Webb) !!!URGENT!!! 1st Floor/Next to office: Toilet over-flowing in the men's room. | |||
| FM-200336816 03 10/21/05 (Webb) !!!URGENT!!! Outside Building: Busted pipe in the back of building; water running through the playground. | |||
| FM-200514951 05 11/15/05 Urgent: Second Floor-Boys Restroom: Re-mount urinal on wall. (Water has been cut off) | |||
| FM-200510627 05 12/12/05 Webb Fire Code Violation Thru-Out Replace all ceiling tiles IFC 110.0 Asbestos Code A - Clear for repairs on 08/17/05. DCPS Safety - Richard Gibson (RG) | |||
| FM-200456249 04 12/13/05 Webb Fire Code Violation First floor S.E. corner on the building; exit door self closing mechanism broken outside learning center # 1.. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200330930 03 12/14/05 (Webb) !!!VERY URGENT!!! Playground Area: Repair hole in black top on the playground. (Safety Hazard) | |||
| FM-200456250 04 12/15/05 Webb Fire Code Violation Second floor Learning center # 2 carpet is a trip hazard. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456230 04 12/15/05 Webb Fire Code Violation First floor Plaster breach in the ceiling in room # 141A. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200456232 04 12/27/05 Webb Fire Code Violation First floor Breach in the wall on top of the electric panel next to room 133. Asbestos Code A - Clear for repairs on 10/05/04. DCPS Safety - Leroy Mintion Jr. (RG 10/06/04) | |||
| FM-200517339 06 1/11/06 First floor, Boys' restroom near cafeteria. "Urgent" Repair or Replace flush valve on urinal. Note: Water is leaking all over floor. | |||
| FM-200517066 06 1/26/06 Playground Area, Rear of Building. "Urgent" Remove vandalized slides and seal all holes. Note: Preventive Maintenance. | |||
| FM-200619554 06 3/27/06 Front of School - Fence is down, sharp poles sticking out. (safety hazard). | |||
| FM-200618543 06 4/3/06 Webb Boiler room URGENT!!!!!!! Repair leaking dicharge line on the relief valve of #2 boiler , water has leaked into the insulation of the boiler and is sagging loose. | |||
| FM-200513077 05 4/27/06 (Webb) "Urgent" Parking lot area. Repair or Replace parking lot lights. Note: Several cars were vandalized on 09/21/06. | |||
| FM-200340330 /03 5/19/06 (Webb) Asbestos Assessment Required. 1st Floor/Ladies Restroom: Repair breech in wall. (Safety Hazard) Asbestos Code A - Clear for repairs on 11/18/03. Honre Engineering - Sheryll James (RG 11/19/03) | |||
| FM-200223763 03 5/22/06 Webb Boiler room (URGENT) Repair or replace circulating pumps #1 and # 2 , #1 pump has bad bearing and # 2 pump has missing parts. | |||
| FM-200450549 04 5/22/06 Webb First floor hallway Repair breach in wall near room 133. Safety hazard Asbestos Code A - Clear for repairs on 07/21/04. DCPS Safety - Leroy Minton Jr. (RG 07/21/04) | |||
| FM-200450125 04 5/22/06 Webb Parking lot Remove bulk trash. Safety and Health Hazard | |||
| FM-200445810 04 5/22/06 Webb Boiler room Need a density test of the thickness of the boilers # 1 and 2 outer shell to assure the safety of the vessel under pressure. | |||
| FM-200339805 03 5/22/06 WEBB Westside stairwell EMERGENCY! Repair ruptured supply line to the convector unit on the first floor (1 inch supply line) Assessment may be needed on floor possiblity of going into floor. Contact Mr. Bradley before assessment. Asbestos Code A - Abated on 11/14/03 DCPS Safety - per Ronald Edwards comfirmed. (RG 11/21/03) | |||
| FM-200337311 03 5/22/06 Webb First floor Repair outside lights above the doors around building. Safety hazard | |||
| FM-200333392 03 5/22/06 (Webb) !!!VERY URGENT!!! 2nd Floor/Learning Center #2: Leaking a/c unit; water coming through ceiling, and lights. | |||
| FM-200333232 03 5/22/06 (Webb) !!!VERY URGENT!!! 2nd Floor/Library: Repair or replace leaking ceiling a/c unit; using buckets, and trash cans to contain water. | |||
| FM-200228030 03 5/22/06 Webb Second floor corridor LC II Replace light fixtures in classroom areas do to roof leak. Rooms 203 and 208. URGENT | |||
| FM-200618807 06 5/22/06 Exterior of Building. "Urgent" Replace (4) outside metal air vent covers, to prevent entry of rodents. | |||
| FM-200620265 06 5/22/06 Urgent First Floor-Restroom Near Office Wax ring need to be replaced on the toilet-It's worn. | |||
| FM-200622843 06 5/26/06 First Floor-Multi Service Center Missing Ceiling Tile Asbestos Code A - Clear for repairs on 05/17/06. DCPS Safety - Richard Gibson (RG) | |||
| FM-200501207 05 9/21/06 Webb Rooftop Unit Repair or replace 2 out of 4 rooftop units. Units blowing cold air, which control open space area. Unit will not lit. Urgent !!!!! | |||
| FM-200505804 05 9/22/06 (Webb) HEALTH CODE VIOLATION: Asbestos Assessment Required. Kitchen Area: Provide mixing hot, and cold water in the prep area also, install sink. Mixing hot, and cold in restroom. Asbestos Code A - Clear for repairs on 05/24/05. DCPS Safety - Leroy Minton Jr. (RG 05/24/05) | |||
| FM-200500315 05 9/26/06 Webb Second floor Boys restroom Need a door knob the boys can not get out of the bathroom. Asbestos Code A - Clear for repairs on 01/11/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200450548 04 9/26/06 Webb First floor room 141B, 141A and 142 Repair ceiling, ceiling is in very bad condition. Safety hazard HA 003 Plaster White Textured ceiling plaster NAD HA 703 Brown Coat with HA 003 NAD Code A-clear for repair by DCPS Charles Buchan on 7/10/04 | |||
| FM-200506039 05 11/20/06 ( WEBB ) First Floor Corridors, Lobby (Floor Tile Replacement) 1) Re-apply 12x12 in. vinyl floor tiles. The initial application was applied during spring break, by Motir Construction, however work was not accepted during final inspection. The work was completed per DCPS Safety - Ronald Edwards comfrimed (RG 06/10/05) | |||
| FM-200629663 06 11/30/06 Webb Boiler Room Repair or replace domestic hot water heater. No hot water in Building. Urgent !!!!! | |||
| FM-200618050 06 12/11/06 Urgent: Parking Lot Area-Repair or Replace Gate It Can't Be Secured. | |||
| FM-200505963 05 1/24/07 ( WEBB ) URGENT!!!! Second Floor - Room 206 1) Repair or Replace classroom door, it's broken. Asbestos Code A - Clear for repairs on 06/27/05. DCPS Safety - Leroy Minton Jr. (RG 06/27/05) | |||
| FM-200617973 06 1/24/07 First floor, Kitchen Area/Staff Restroom. "Urgent" Repair or Replace leaking sink pipe, water is spewing all over the floor. Note: This is the only sink that the kitchen staff have to wash their hands. | |||
| FM-200620317 06 1/24/07 First floor, Exterior Door/Learning Center I. "Urgent" Repair or Replace rusted and corroded door frame on metal exit doors. Note: Rodents are using this path to enter the building. Asbestos Code A on 03/27/06 Tidewater - Kenny Long (RG 03/30/06) | |||
| FM-200450550 04 1/24/07 Webb First floor hallway near 139 Repair plaster ceiling. Safety hazard Asbestos Code A - Clear for repairs on 07/21/04. DCPS Safety - Leroy Minton Jr. (RG 07/21/04) | |||
| FM-200619965 06 1/24/07 Roof Area. "Urgent" Reinstall vent covers on roof to prevent leaks in the kitchen and cafeteria areas. Note: This needs to be done asap! | |||
| FM-200458182 /04 1/24/07 Webb Room 141B Kgn room Plaster is falling out of the ceiling. Asbestos Code A - Clear for repairs on 11/10/04. DCPS Safety - Leroy Minton Jr. (RG 11/10/04) | |||
| FM-200509331 05 1/24/07 (Webb) "Urgent" Entire building. Principal needs all locks keyed to master key. | |||
| FM-200505278 05 1/24/07 (Webb) 1st Floor/Kitchen (Hallway) Repair or replace door closer on exit door. Asbestos Code A - Clear for repairs on 05/09/05. DCPS Safety - Richard Gibson (RG) | |||
| FM-200333537 03 1/24/07 Webb Second floor exit door Repair exit door will not close properly. Safety Hazard, very urgent | |||
| FM-200513846 /05 1/24/07 Webb Rm 100 Repair lock ( Urgent that RM. BE SECURED} | |||
| FM-200514022 /05 1/24/07 Webb Very Urgent First Floor-Multiservice Center Need Four locks changed to protect personal and confiditional records. | |||
| FM-200515881 /05 1/24/07 Urgent: Unstop water fountains in the cafeteria area on the first floor. | |||
| FM-200516993 /05 1/24/07 Webb Main Office Repair or replace univent motor in main office. No heat in office. Urgent !!!!! | |||
| FM-200507634 05 1/24/07 (Webb) !!!!VERY URGENT!!!! Roof The roof top turbines has been removed. Due to vandalism it needs to be replaced. | |||
| FM-200512038 05 3/27/07 Webb Boiler Room Repair or replace circulating pump for hot water is binding. Urgent !!!! | |||
| FM-200617688 06 3/27/07 Webb Boiler Room Replace leaking seal on pump #4 Urgent !!!!! |