Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Bruce-Monroe Elementary School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200118159 01 9/13/01 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQD. THROUGHOUT REPAIR OR REPLACE ALL DEFECTIVE FLUSH VALVES, AND UNSTOP TOILETS, URINALS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/28/01. RONALD EDWARDS - SAFETY (202)576-6693 | |||
| FM-200117838 01 9/25/01 BRUCE MONROE EXTERIOR 1) REPLACE EXTERIOR LIGHTING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. RONALD EDWARDS - SAFETY (202)576-6693 | |||
| FM-200120492 01 10/2/01 BRUCE MONROE MECHANICAL ROOM SURVEY AND SERVICE MULTI STACK AIR CONDITIONING SYSTEM, SYSTEM HIGH PRESSURE CUT OUT SAFETY SWITCHES ARE TRIPPING AT A RATE OF 15 TO 20 EVERY MORNING. CONDENSER WATER TEMP TO SYSTEM IS 75-80. | |||
| FM-200118163 01 11/13/01 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQD. FRONT OF LOBBY REPAIR OR REPLACE WATER COOLERS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/28/01. RONALD EDWARDS - SAFETY (202)576-6693 | |||
| FM-200122445 /01 11/15/01 BRUCE-MONROE OLD BLDG. BOILER RM. REMOVE PORTABLE POWER SOURCE AND REINSTALL COVER PANEL FOR ELECTRICAL BREAKER CABINET. Requester Phone: 541-6254 Requestor Phone: 541-6254 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/05/01 LEORY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200207309 02 7/3/02 Bruce-Monroe 1. Asbestos Assessment Reqd. 1st Floor West Stairway Remount hand-rail to wall where it has been pulled away. Bolts & screws need to be replaced, and some welding may be needed. Asbestos Code A - Clear for repairs on 5/08/02 DCPS Safety, Leroy Minton Jr.(RE- 5/08/02) | |||
| FM-200218078 02 9/25/02 Bruce-Monroe First Floor - Kitchen 1) Repair/replace drain pipe on steam table. Lines coming out of floor. Asbestos Code A - Cleared for repairs on 09-24-02 (LM / 09-24-02) Leroy Minton Jr. Safety Office 202-576-8962. | |||
| FM-200218045 02 1/29/03 (Bruce Monroe) Kitchen: Peeling paint and plaster in large sections. (FINAL NOTICE) Supervisor: A. Alston, Supervisor; telephone #535-2183. Asbestos Code A - Cleared for repairs on 09-23-02 (LM / 09-23-02) Leroy Minton Jr. Safety Office 202-576-8962. Lead-Based Paint Code A - Cleared for repairs on 09-23-02 (LM / 09-23-02) Leroy Minton Jr. Safety Office 202-576-8962. Asbesstos Code A-clear for repair by Horne Engineer Stephen Caldwell DCPS Charles E. Buchanan on 9/24/02 | |||
| FM-200224230 03 2/11/03 (Bruce-Monroe) 1. Asbestos Assessment Required. 1st Floor/South Stairway: Repair stairwell nosing through-out the building. Asbestos Code A - Clear for repairs on 01/23/03. Horne Engineering - Troy Wilcome (RG 01/24/03) (If Tiles Are Damaged Stop And Call DCPS- Safety For Instructions ) | |||
| FM-200228792 03 4/15/03 Bruce-Monroe Entrance Urgent: Request for emergency repair on front lobby entrance door, has malfunction again. | |||
| FM-200202357 02 5/5/03 BRUCE MONROE REQUEST ASBESTOS ASSESSMENT OF SCOPE OF WORK ATTACHED. SCHOOL GROUNDS - EXTERIOR WORK ONLY 1) REPLACE CHAINLINK FENCE,REPLACE CONCRETE/MASONARY RETAINING WALL WITH CAPSTONE, REPAIR OR REPLACE ASPHALT PAVING AND OR CONCRETE PAVING /STAIRS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/04/02. RICHARD GIBSON - SAFETY (202)576-5584 (RG) | |||
| FM-200212979 02 6/11/03 Bruce-Monroe 1. Asbestos Assessment Reqd. 1st Floor Asst. Principal's Office 2. Install four (4) dedicated electrical outlets to support computers and copy machine. Currently using inadquate power that will not allow the computers and copier to be used at the same time. Code A Clear for Repair by DCPS Safety-Leroy Minton, Jr. 07-26-02 DCPS Safety-Sheila R. Howard 07-26-02 | |||
| FM-200334950 03 8/13/03 (Bruce-Monroe) !!!VERY URGENT!!! 3rd Floor/Center #304: Faucet continues to run scalding hot water, flooding the floors, and running down to the 2nd floor. | |||
| FM-200335109 03 8/14/03 (Bruce-Monroe) !!!VERY URGENT!!! Exterior: Window grate needs to be secure around perimeter of old building; also, secure vents leading to tunnel due to break-in | |||
| FM-200443390 04 1/30/04 Bruce-Monroe Boiler Room Repair or replace air compressor tank. (Hole in bottom of tank). Model #A5150-4 Serial #AG17 Urgent !!! | |||
| FM-200335108 03 2/12/04 (Bruce-Monroe) !!!VERY URGENT!!! Old Gym area: Center mullion damaged on door, due to break-in. | |||
| FM-200447539 04 5/10/04 Bruce-Monroe 3RD Floor AHU #1 Mechanical Repair or replace air handler unit coil on 3rd floor mechanical room. Unit servers main office. Need electrician to remove or disconnect unit one electric box. This is Urgent !!!!!! | |||
| FM-200451159 04 1/3/05 (Bruce-Monroe) FIRE CODE VIOLATION: 1st Floor/Lobby: Exit door not closing properly. Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Leroy Minton Jr. (RG 08/20/04) | |||
| FM-200451157 04 1/3/05 (Bruce-Monroe) FIRE CODE VIOLATION: 1st Floor/West Stairway: Replace door hardware on door leading to playground. Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Leroy Minton Jr. (RG 08/20/04) | |||
| FM-200451158 04 1/3/05 (Bruce-Monroe) FIRE CODE VIOLATION: 3rd Floor/Room #302: Needs door hardware. Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Leroy Minton Jr. (RG 08/20/04) | |||
| FM-200451160 04 4/7/05 (Bruce-Monroe) FIRE CODE VIOLATION: 1st Floor/North Stairway: Both exit doors do not latch. Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Leroy Minton Jr. (RG 08/20/04) THIS FCV NEED TO BE FORWARD TO LOCK SMITHS 12-09-04 | |||
| FM-200506863 05 6/22/05 (Bruce-Monroe) "Urgent" Exterior Wall, Columbia Rd. side. Remove graffito from wall. | |||
| FM-200110707 01 7/25/05 BRUCE-MONROE 1) ASBESTOS ASSESSMENT REQUIRED 2) REPAIR WALL IN PARENT CENTER WALL IS A POTENTIAL SAFETY HAZARD COULD FALL ON SOMEONE ASBESTOS CODE A -CLEAR FOR REPAIRS ON 05/21/01. (THE CEILING TILE HAS ASBESTOS IN IT, SO NO WORK CAN BE DONE ABOVE THE CEILING WITH OUT AN ABATEMENT DONE FIRST) | |||
| FM-200335022 03 10/21/05 Bruce- Monroe Work repair need to be done in the parking lot on Irving Street. There is a breech in the wall (hole) that needs to be covered with agrate etc.... It is urgent that this be done as soon as possible because of resent burglaries here at the school. | |||
| FM-200445041 04 10/21/05 (Bruce-Monroe) !!!VERY URGENT!!! Roof: Unstop roof drains filled with dirt, and debris, water leaking inside. | |||
| FM-200228793 03 10/21/05 Bruce-Monroe Main front lobby entrance Urgent: Panel bar on lobby door will not closeand latch when you close the door.Repairmen have come and repaired this same door numerous times, only for this same door to start malfunctioning over and over again. This problem needs attention as soon as possible. | |||
| FM-200222782 /02 10/21/05 (Bruce-Monroe) 3rd Floor/Through-out building: Replace key and knob locks on doors in learning center #305, conference -A, and conference-C. Replace dead-bolt mortise lock on storage room door, near conference room B, in learning center #2. Asbestos Code A - Clear for repairs on 01-13-03 by Leroy Minton Jr. (LM/01-14-03) Safety Office (202) 576-8962. | |||
| FM-200118162 01 2/3/06 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQD. THROUGHOUT REPAIR OR REPLACE HAND WASHING SINKS/FAUCETS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/28/01. RONALD EDWARDS - SAFETY (202)576-6693 | |||
| FM-200112886 01 2/3/06 BRUCE-MONROE THIRD FLOOR ROOF 1) INSTALL AIR VENTILATORS PREVIOUS VENTILATORS NOT WORKING ASBESTOS CODE A - CLEAR FOR REPAIRS ON 01/07/02. RONALD EDWARDS - SAFETY (202)576-6691 | |||
| FM-200122178 /01 2/3/06 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ OLD GYM STAIRWAY REPLACEMENT OF CEILING. CEILING HAS FALLEN IN DUE TO ROOF DAMAGE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/01/01. CHARLES BUCHANAN - SAFETY (202)576-5582(RG) | |||
| FM-200515628 /05 2/6/06 Bruce-Monroe Boiler room Boiler #1 and #2 keep going off on flame failure. Have to keep resetting safety on starter | |||
| FM-200617795 06 2/13/06 BRUCE-MONROE Old wing Boiler room HOT!!!!!! URGENT!!!!! Install bucket trap on return side of condensate return tank. Note: Traps are bad Asbestos assessment not required. | |||
| FM-200617794 06 2/13/06 BRUCE-MONROE Old wing stairway (right side) HOT!!!!!! URGENT!!!!! Repair or replace crack radiator (leaking) Unit is isolated (no heat) | |||
| FM-200517033 /05 2/13/06 Bruce-Monroe Tunnel (Old Building) Repair or replace steam line leak on return. Approx. size is about 1-1/2". Boiler is off because of leak. Urgent !!!! | |||
| FM-200631476 10/29/06 11/8/06 Bruce-Monroe Boiler Room Repair or replace leaking copper line to water regulator approx. 1/2" line about 10' high. Urgent !!!!! | |||
| FM-200516902 /05 1/5/07 Bruce-Monroe Old Wing,Boiler Room Repair or replace #150, automatic water feeder on Boiler #3. Feeder is not putting water in boiler properly. Urgent !!!!! | |||
| FM-200458539 /04 1/9/07 Bruce-Monroe Hallway near auditoreium Replace exterior door, door has 15 bullet holes init. Asbestos Code A - Clear for repairs on 11/23/04. DCPS Safety - Leroy Minton Jr. (RG 11/23/04) | |||
| FM-200631477 10/29/06 1/9/07 Bruce-Monroe Boiler Room Repair or replace pneumatic controls thru-out building. Parts to system are missing, disconnected etc. Building is extremly hot. Urgent !!!!! | |||
| FM-200513044 05 2/7/07 (Bruce-Monroe) Electrical Lights must be removed as part of ongoing construction project, please confirm presence of asbestos in ceiling tile. Asbestos Code D - on 11/01/05. Tidewater - Tony Marcolin (RG 11/16/05 Asbestos Code A - Abated and cleared fpr repairs on 10/23/06 per Goel confirmation (LM/10-23-06) Safety Office. 202-576-8962. |