Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Cardozo High School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200117095 01 8/31/01 (CARDOZO) 1. ASBESTOS ASSESSMENT REQUIRED. GROUND LEVEL: UNSTOP SLOP SINK DRAIN IN CUSTODIAL CLOSETS; WATER FLOODING FLOOR, AND LEAKING OUT AT FLOOR LEVEL FROM DRAINAGE TRAP. ASBESTOS CODE A -CLEAR FOR REPAIRS ON 08/13/01. SYLVIA GRIMES - SAFETY (202)576-5583 | |||
| FM-200117090 01 8/31/01 (CARDOZO) 1. ASBESTOS ASSESSMENT REQUIRED. GROUND LEVEL/GIRLS BATHROOM: REPLACE THE WAX RING AND TOILET FLANGE; WATER LEAKING AND FLOODING FLOORS. ASBESTOS CODE A -CLEAR FOR REPAIRS ON 08/13/01. SYLVIA GRIMES - SAFETY (202)576-5583 | |||
| FM-200111630 01 9/20/01 CARDOZO BASEMENT FAN ROOM TUNNEL (EAST) 1) REPAIR OR REPLACE LEAKING DOMESTIC COLD WATER PIPE PIPE IS GALVANIZED - 2 1/2 INCHES IN DIAMETER POSSIBLE IMPACT ON ON-GOING ASBESTOS REMOVAL PROJECT EMERGENCY!! ASBESTOS CODE A - CLEARED FOR REPAIRS ON 07-30-01. LEROY MINTON JR SAFETY OFFICE ( 202-576-8962 ) SAME AS WO# 200104205 | |||
| FM-200120672 01 10/11/01 CARDOZO BOILER ROOM REPAIR BOILER #1 BURNER KEEP GOING OFF ON PILOT FLAME FAILURE. IC-BURNER URGENT-ONLY BOILER #1 ABLE TO BE USED, #2 BOILER HAS LEAKING TUBES, #3 BOILER NEED TO BE INSPECTED FROM CLEANING. VERY URGENT. | |||
| FM-200112302 01 10/16/01 CARDOZO BOILER ROOM 1. ASBESTOS ASSESSMENT REQUIRED. 2. FURNISH AND INSTALL PIPING TO SAFETY RELIEF VALVES AND WITH PULL CHAINS. EACH BOILER HAS 3 (THREE) SAFETY VALVES AND THERE ARE 3 -BOILERS. VALVE SIZE APPROX. 4-1/4" - 4-1/2", TO FLOOR 16 FT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/01/01. HORNE ENGINEERS - STEPHEN CALDWELL | |||
| FM-200120099 01 10/17/01 (CARDOZO) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ GIRLS BATHROOM MOP SINK HAS STOPPAGE THAT NEEDS TO BE OPENED. POSSIBLE SNAKING NEEDED OR OPEN TRAP. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/20/01. RICHARD E GIBSON - SAFETY (202)576-5584 | |||
| FM-200112476 01 10/31/01 CARDOZO GROUND FLOOR FRONT OF CAFETERIA 1) FURNISH AND INSTALL SAFETY WIRE GLASS IN SIDE WINDOW GLASS BROKEN AND SHATTERED SIZE - 71 1/2 X 32 1/4 | |||
| FM-200118263 01 11/13/01 CARDOZO OUTSIDE REPLACE MISSING STEEL HAND-RAILS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200122908 01 11/17/01 (CARDOZO) 1. ASBESTOS ASSESSMENT REQUIRED. STADIUM LOCKER ROOM: REPAIR OR REPLACE SHOWER HEAD STEM. ASSESSMENT ON SHOWER WALLS NEEDED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/05/01 RICHARD GIBSON - SAFETY (202)576-5584 (RG) | |||
| FM-200110681 01 11/27/01 (CARDOZA) FIRE CODE VIOLATION: F-303.4 GROUND LEVEL/BY CAFETERIA: GATE OUT-SIDE OF EXIT DOORS NEAR CAFETERIA, WILL NOT OPEN ASBESTOS CODE A -CLEAR FOR REPAIRS ON 05/21/01. MR.LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200124437 /01 12/12/01 (CARDOZO) !! VERY URGENT !! 1ST AND 2ND FLOORS/ ROOMS: 109, 116, 215 REPAIR OR REPLACE CLASSROOMS AND TEACHERS PREP ROOM DOOR LOCKS CYLINDERS STOPPED WORKING UNABLE TO SECURE THESE AREAS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/08/01 RICHARD GIBSON - SAFETY (202)576-5584 | |||
| FM-200108989 01 12/18/01 CARDOZO 1ST FL. & 2ND FL. 1. ASBESTOS ASSESSMENT REQUIRED. INSTALL WINDOW AC UNITS IN THESE AREAS - ROOMS #116, 120, 109, LIBRARY. 1 EA. - 24,000 BTU Requester Phone: 671-1777 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/16/01. MR. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200127239 02 1/16/02 (CARDOZO) ASBESTOS ASSESSMENT REQUIRED ALL THROUGHOUT BUILDING FURNISH SAFETY-WIRE GLASS FOR DOORS AND WINDOWS AS NEEDED. CODE A- CLEAR FOR REPAIR BY HORNE ENGINEERING SAM EBRAHIM 01-11-02 (SRH)01-11-02. | |||
| FM-200111471 01 1/16/02 CARDOZO SUB BASEMENT NORTHEAST SIDE, FIRST FLOOR NORTH SIDE AND BASEMENT SOUTHEAT SIDE 1) REPLACE WIRE SAFETY GLASS SIZES - 1 PIECE 6 INCHES X 60 INCHES 3 PIECES 10 INCHES X 19 1/4 INCHES 1 PIECE 10 3/4 INCHES X 13 INCHES | |||
| FM-200122786 02 1/27/02 (CARDOZO) !!!VERY URGENT!!! 1ST FLOOR/ROOM #116: REPAIR LOCK TO SCIENCE ROOM, LOCK WORKS INTERMITTENTLY. | |||
| FM-200124023 02 1/27/02 (CARDOZO) ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR/GIRLS GYMNASIUM FURNISH AND INSTALL A NEW CYLINDRICAL DEADBOLT ON DOUBLE DOORS TO THE GIRLS GYM (NEEDED TO SECURE GYM AREA) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/29/01. LEROY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200118431 01 3/3/02 CARDOZO OUTSIDE - GROUNDS REMOVE LITTER CAUGHT BETWEEN FENCE AND BALUSTRADE ALONG FLORIDA AVENUE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200118264 01 3/5/02 CARDOZO OUTSIDE BERM AND PLANT AREAS TWO (2) NEAR ENTRANCE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200122982 01 4/29/02 (CARDOZO) 1ST FLOOR/ ROOM 106-B REPLACE BULLETIN BOARD ON WALL. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/16/01. LEROY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200206047 02 5/3/02 (Cardozo) ***Very Very Urgent*** 1. Asbestos assessment required Ground Floor/room #6: Repair or replace leaking 5 inch PVC waste line drain pipe; Pipe is broken; appears that someone has been standing on it. Asbestos Code A - Clear for repairs on 04/18/02. DCPS Safety - Ronald Edwards (RG 04/18/02) Code A-clear for repair by Horne Engineer ( Roger Kager ) on 4/18/02 ( CEB ) | |||
| FM-200207059 02 5/9/02 (Cardozo) FIRE CODE VIOLATION: Page 1 of 7 1. Asbestos assessment required. 3rd Floor: Balcony door closure broken. Asbestos Code A - Clear for repairs on 05/03/02. DCPS Safety - Ronald Edwards (RG 05/06/02) | |||
| FM-200207131 02 5/14/02 (Cardozo) Fire Code Violation: Wood Shop corridor door: Defective hardware/metal door. Asbestos Code A - Clear for repairs on 05/10/02. DCPS Safety - Ronald Edwards (RG 05/10/02) | |||
| FM-200207063 02 5/23/02 (Cardozo) FIRE CODE VIOLATION: Page 1 of 7 1. Asbestos assessment required. 3rd Floor: Room #321 A: Door closure needs to be repaired. Assessment was by Ronald Edwards of DCPS - door could not be open,must assume it Asbestos. Solomon Palmer of Structural Maintenence was given work order # to get the door measured for replacement 05/09/02. Asbestos Code A - Clear for repairs on 05/10/02. DCPS Safety - Ronald Edwards (RG 05/10/02) | |||
| FM-200205461 02 6/3/02 (Cardozo) ***Urgent*** 1. Asbestos assessment required. 1st floor/near rm. #107: Repair or replace water fountain, waste water backing up. Code A-clear for repair by Honre Engineer ( Stephen Caldwell ) on 4/08/02 | |||
| FM-200112796 01 6/3/02 CARDOZO SUB-BASEMENT WEIGHT ROOM 1) REPLACE DOORS LEADING TO WEIGHT ROOM ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/27/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) | |||
| FM-200210603 02 7/15/02 Cardozo ****Urgent**** Ground Floor Girls' Restroom Two basins in the girls' restroom are not draining at all---both are on the same drain line. | |||
| FM-200106740 01 7/29/02 CARDOZO BASEMENT - BOYS GYMNASIUM/SHOWER ROOM FURNISH AND INSTALL MIXING VALVE FOR SHOWER. DOMESTIC HOT WATER MIGRATING INTO COLD WATER SUPPLY FOR TOILETS AND WATER COOLERS, WATER COOLERS ARE NEW AND CAN BE DAMAGED BY HOT WATER GOING THRU SYSTEM. URGENT. SAFETY HAZARD. Asbsetos Code A - Clear for repairs 02/25/02 DCPS Safety - Ronald Edwards (RE | |||
| FM-200115946 01 8/20/02 CARDOZO BASEMENT - EAST FAN ROOM ASBESTOS ASSESSMENT REQUIRED REPLACE 3/4in x 15ft GALVINIZE DOMESTIC WATER PIPE. PIPE CORRODED AND LEAKING BAG=D. WATER IS TURNED OFF. URGENT!! ASBESTOS CODE A-CLEAR FOR REPAIRS BY 8/10/01 HORNE ENGINEER : STEPHEN CALDWELL | |||
| FM-200211138 02 8/28/02 Cardozo 1. Asbestos Assessment Reqd. Ground, 1st, 2nd & 3rd Floor Hallways 2. Need survey of hallway walls to make repairs and reanchor lockers which have loosened and are no longer held securely on the walls---the lockers could potentially fall and injure someone. Asbestos Code A-clear for repair by Horne Engineer (Sharon Voss) on 7/16/02 Charles E. Buchanan DPCS | |||
| FM-200218536 02 9/30/02 Repair ruptured safety valve nipple on the top of the storage tank in the boilerroom . | |||
| FM-200218811 02 10/4/02 Cardozo S.H.S Boiler Room Start up burners and test safety controls on specified boilers. | |||
| FM-200203901 02 11/22/02 (Cardozo) ****Urgent**** Ground Floor Kitchen Replace two (2) basket strainer gaskets on two (2) double sinks in the kitchen which are leaking from numerous places in the drain pipes and traps. | |||
| FM-200218058 02 12/3/02 Cardozo Asbestos Assessment Reqd. Ground Floor Cafeteria 1. Assess doors for hardware installation [panic bars and locks]; and 2. Replace 8 panic bars [Yale #1H820, rim device, 2100 exit device]. Asbestos Code A - Cleared for repairs on 10-17-02 (LM / 10-18-02) Leroy Minton Jr. Safety Office 202-576-8962. | |||
| FM-200219981 /02 1/6/03 CARDOZO BOILER ROOM "URGENT NO HEAT" REPAIR/REPLACE BURNER PILOT FLAME FAILURE. | |||
| FM-200223989 03 1/16/03 Cardozo Boiler room (URGENT) Replace leaking pit cock valve on the the domestic hot water boiler, unit was shut down by the gas co.1/14/03 | |||
| FM-200211137 02 2/24/03 Cardozo 1. Asbestos Assessment Reqd. Basement Tunnel 2. Repair or replace leaking 3" galvanized, insultated, domestic cold-water pipe. Asbestos Code A - Clear for repairs. (LM) Abated on 08/13/02 per Leroy Minton confirmation. Safety Office 202-576-8962. | |||
| FM-200122675 /01 3/19/03 (CARDOZO) !!EMERGENCY!! DUGOUT STADIUM SIDE: A LARGE CHUNK OF CONCRETE LOOSE AND HANGING FROM THE CEILING OF THE DUGOUT. (INJURIES COULD BE SUSTAINED, IF CONCRETE FALLS ON SOMEONE) | |||
| FM-200228257 03 5/23/03 Cardozo URGENT Eleventh (11th) Street exit door Repair or replace metal door and panic bar. (By day care room). | |||
| FM-200204619 02 5/28/03 (Cardozo) Asbestos Assessment Reqd. 1st Floor Room 120 Repair steps near room 120--existing damage poses a safety hazard. Asbestos Code A - Clear for repairs on 05/29/02. Horne Engineering - Philp Connollly (RG 05/30/02) | |||
| FM-200332989 03 7/9/03 Cardozo Basement Level - Boys Gym 1. Install new lock on newly installed door in boys locker room. Asbestos Code A - Clear for repairs on 07/08/03. DCPS Safety - Richard Gibson ( RG ) | |||
| FM-200218544 02 7/16/03 Cardozo Urgent !!! Ground Floor - 10a 1) Repair or replace window due to break-In. | |||
| FM-200332491 03 7/28/03 (Cardozo) !!!VERY URGENT!!! Asbestos Assessment Required. ELECTRICAL WORK 1. Install emergency battery pack, connected to emergency exit lighting circuit at entrance doors to daycare and suspension class room, and one in the children's toilet. 2. Install emergancy exit lights above vestibule doors - one at vestibule on the daycare stairwell and one at the suspension classroom stairwell. 3. Install tamper proof plate covers at all power receptacles. (Approximately 6). Asbestos Code A - Clear for repairs on 06/30/03. Horne Engineering - Bipin Nanavaty (RG 07/02/03) | |||
| FM-200337780 03 10/1/03 Cardozo !!!VERY URGENT!!! Sub Basement - Fan Room 1. Repair floor drain need to be unclogged. Code A-clear for repair by DCPS Charles Buchanan on 9/25/03 Wednesday, October 01, 2003-10:10 a.m., Call came in of concern of when repairs are going to be made, as conditions are very serious, and the water has a much heavier flow. | |||
| FM-200338286 03 10/29/03 Cardozo URGENT Second floor room 209 Replace classroom door lock and rekey cylinder to old master key. Room can not be secured. | |||
| FM-200218110 02 2/12/04 Cardozo Asbestos Assessment Reqd. Ground Floor Classroom #3 Computer Lab 1. Install a/c unit that is on site. At present, there is no a/c unit to cool this lab; and 2. Welders need to fabricate a bracket and bore a hole in the window grate. [NOTE: Installation of a 220v line has already in place.] Asbestos Code A - Cleared for repairs on 09-23-02 (LM / 09-23-02) Leroy Minton Jr. Safety Office 202-576-8962. | |||
| FM-200106899 01 3/15/04 CARDOZO GROUND - BOYS BATHROOM SURVEY AND CORRECT URINALS AND DRAINS STOPPAGES. BATHROOM HAS BEEN RENOVATED AND MADE HANDICAPPED ACCESSIBLE, DUE TO SOME URINALS STOPPAGES BATHROOM CANNOT BE USED BY MALE STUDENT. Asbsetos Code A - Clear for repairs 02/25/02 DCPS Safety - Ronald Edwards (RE | |||
| FM-200338290 03 3/15/04 Cardozo URGENT Front of building North Clifton St. Replace missing section of down spout, rain water damaging wall plaster. | |||
| FM-200331963 03 3/15/04 Cardozo Ground floor hall and cafeteria Replace safety wire glass that is broken and shattered. Hall approx. 25 7/8 inches x 44 3/4 inches. Cafeteria approx. 71 1/2 inch x 32 1/4 inches. | |||
| FM-200220010 /02 3/15/04 CARDOZO Room #101, Rest room' Floor. ( Assistant' Pricipals' Office) Asbestos Assessment Required Floor tile has been damaged by water and needs to be replaced. (Tile 12X12). Asbestos Code A - Clear for repairs on 10/28/02. DCPS Safety - Leroy Minton Jr. (RG 10/29/02) | |||
| FM-200124026 /01 3/15/04 (CARDOZO) ASBESTOS ASSESSMENT REQUIRED SUB-BASEMENT/ARMORY REPLACE APPROX. 25-30 FEET OF 2 INCH BLACK PIPE FOR STEAM SUPPLY FOR OVERHEAD HEATERS. PIPE IS LEAKING FROM THREADS AND HAS NO WRAPPING MATERIALS ON IT. STOP IS HOLDING AND PIPE CAN BE ISOLATED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/29/01. LEROY MINTON - SAFETY (202)576-6691(RG) | |||
| FM-200123737 /01 3/15/04 CARDOZO FAN ROOM SURVEY AND CORRECT BURNING ELECTRICAL SMELL ODER AT HEATING FAN MOTOR #7, ODER IS GETTING INTO THE CLASSROOMS AND HALLS FROM GROUND FLOOR TO 3 RD FLOOR ON EAST SIDE OF BUILDING, FAN MOTOR NEEDED TO SEND HEAT TO THESE AREAS. URGENT | |||
| FM-200108990 01 3/15/04 CARDOZO 1ST FL. & 2ND FL. 1. ASBESTOS ASSESSMENT REQUIRED. INSTALL ELECTRICAL SERVICE FOR NEW WINDOW AC UNITS IN ROOMS 116, 120, 109, LIBRARY #234 - 24,000 BTU FEDDERS #232 - 18,000 BTU WHITE WESTINGHOUSE #171 - 25,000 BTU FEDDERS #282 - 25,000 BTU FEDDERS Requester Phone: 671-1777 Requestor Phone: 671-1777 Asbsetos Code A - Clear for repairs 02/25/02 DCPS Safety - Ronald Edwards (RE) | |||
| FM-200106820 01 3/15/04 CARDOZO DUG-OUT HOMESIDE FURNISH AND INSTALL NEW MIXING VALVE FOR WHIRPOOL. DOMESTIC HOT WATER MIGRATING INTO COLD WATER SUPPLY FOR TOILETS AND WATER COOLERS, WATER COOLERS ARE NEW AND CAN BE DAMAGED BY HOT WATER GOING THRU SYSTEM. URGENT. | |||
| FM-200446152 04 4/9/04 (Cardozo) !!!URGENT!!! 3rd Floor/Room #110: Key broke off in lock of classroom door. | |||
| FM-200442294 04 4/13/04 (Cardozo) Through-Out Building: Furnish boiler room staff with safety wire mesh glass. | |||
| FM-200452737 04 8/27/04 (Cardozo) Outside /11th Street Stadium: Repair hole in fence on stadium. Asbestos Code A - Clear for repairs on 08/17/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200228250 03 10/15/04 Cardozo URGENT Staium walk way rear armory - security Furnish and install wire mesk screen windows guards. Total of nine (9) windows. Pool area has the type of guards that is needed. | |||
| FM-200454270 04 12/13/04 (Cardozo) FIRE CODE VIOLATION: 3rd Floor/Adjacent to Room #304: Replace door closer. Asbestos Code A - Clear for repairs on 09/24/04. DCPS Safety Leroy Minton Jr. (RG 09/24/04) | |||
| FM-200500980 05 2/3/05 Cardozo Fan #1 Repair or replace fan heating coil motor, motor was arcking. No heat on southwest side of building. Room #8, 110,114,116,212,214,216, teacher lounge,308,310,312 and 314, all these rooms has no heat because of #1 Fan motor is gone. Urgent !!!!! | |||
| FM-200456502 04 6/14/05 Cardozo Ground floor southwest 13th St. Repair or replace exterior door, metal door, that has been vandalized. Metal door is deteriorating from rusting. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/06/04) | |||
| FM-200104225 01 7/22/05 CARDOZO NORTH & NORTHWEST ASBESTOS ASSESSMENT ASSESS PIPE WRAP MATERIAL FOR REMOVAL FOR PIPE STEAM LEAK REPAIR. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/27/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) | |||
| FM-200102379 /01 7/22/05 (CARDOZO) BOYS BATHROOM GYM: MAKE REPAIRS TO VANDALIZED BATHROOM. REPLACE URINALS AND FACE BOWLS. Asbsetos Code A - Clear for repairs 02/25/02 DCPS Safety - Ronald Edwards (RE | |||
| FM-200453776 04 7/26/05 Cardozo Ground floor kitchen Replace broken floor tiles. 32 avanti 7x7". Assbestos Code A - Clear for refpairs on 01/18/05. DCPS Safety - Leroy Minton JR (RG 01/31/05) | |||
| FM-200456651 04 8/1/05 Cardozo Second floor room 221 Request new door frame, door and accessories. To be installed. Wood door and frame rotted out 38x80 opening. Asbestos Code A - Clear for repairs on 10/12/04. DCPS Safety -Leroy Minton Jr.(RG 10/12/04) | |||
| FM-200457140 /04 8/1/05 Cardozo Boiler Room Fabricate bracket for pull chains for safety valve on all Boilers | |||
| FM-200456654 04 8/1/05 Cardozo First floor boys restroom Re-anchor hand sink to wall. Asbestos Code A - Clear for repairs on 10/12/04. DCPS Safety -Leroy Minton Jr.(RG 10/12/04) | |||
| FM-200504757 05 8/4/05 (Cardozo) !!!URGENT!!! furnish and install new thermostats for heat pumps control.old thermostats with mercury bulbs were removed during mercury clean up.there are no controls for heat or a/c. | |||
| FM-200340106 03 8/4/05 (Cardozo) !!!EMERGENCY!!! 1st Floor/Room #123: Replace receptacle on television, student injured from electrical shock. This is an emergency, Per. Mr. Henry. | |||
| FM-200443068 04 8/4/05 Cardozo Boiler Room Replace small domestic hot water circulating motor. No motor information- Tag is missing. Urgent !!!!! | |||
| FM-200454272 04 9/7/05 (Cardozo) FIRE CODE VIOLATION: 1st Floor/Room #123: Replace door closer. Asbestos Code A - Clear for repairs on 09/24/04. DCPS Safety Leroy Minton Jr. (RG 09/24/04) | |||
| FM-200454271 04 9/7/05 (Cardozo) FIRE CODE VIOLATION: 3rd Floor/Room #318: Replace door closer adjacent to room #318. Asbestos Code A - Clear for repairs on 09/24/04. DCPS Safety Leroy Minton Jr. (RG 09/24/04) | |||
| FM-200508627 05 9/20/05 Cardozo Fire Code Violation Ground, First, Second and Third Floor Rooms - 316,314,312,312a,303,313,319,219,206,214,220,109,15, and Door in Cafeteria. 1) Doors off line. Code A - clear for repairs as of 8/2/05 Sylvia Grimes safety office. | |||
| FM-200513052 05 10/25/05 Cardozo Urgent Second Floor-Library Replace door locks on three doors, 1 interior Office door, 2 Hall entrance doors. | |||
| FM-200203279 02 11/1/05 (Cardoza) **Very Urgent** Cardozo Sub-basement fan rm-east Replace leaking galvanized domestic cold water supply pipe 3" in cir. | |||
| FM-200501634 05 11/1/05 Cardozo Pipe On Floor 1) Pipe burst in cafeteria area this is a health code violation this is an urgent matter repair must be completed today or the cafeteria must be closed 2/16/05. | |||
| FM-200442693 04 11/3/05 Cardozo Urgent Health Unit Replace leaking domestic cold and hot water supply valves - also replace leaking domestic cold water supply pipe to hand sink. Supply valves approx. 3/4" supply pipe approx. 1/2" domestic cold water supply needed for water cooler. | |||
| FM-200212931 02 11/3/05 Cardozo 1. Asbestos Assessment Reqd. Sub-basement Fan Room [Northeast Area] 2. Replace three (3) leaking 3" galvanized domestic cold water pies and valves. Code A Clear for Repair-by DCPS Safety-Leroy Minton, Jr. 07-26-02 DCPS Safety-Sheila R. Howard 07-26-02 | |||
| FM-200447267 04 11/3/05 Cardozo Sub basement armory Survey and access and remove ACM from armory pipes-so plumbing repairs can be done. Domestic hot and cold water pipes. Code 'A' cleared for repairs to leaking galvanized pipe and plaster wall cavity 12/29/04. DCPS Safety R. Edwards (RE-12/29/04) Abatement conducted by EnviroBate Global; Air Monitoring conducted by USA Environmental Inc Note: After galvanized pipe is repaired contact R Edwards, DCPS Safety at (202 439 8094). Pipe line will be reinsulated followed by wall cavity enclosure. (R. Edwards) | |||
| FM-200124790 /01 11/4/05 (CARDOZO) ASBESTOS ASSESSMENT REQUIRED 1) 1ST FLOOR/BOYS BATHROOM REPLACE 1 1.2-INCH VALVE ON DOMESTIC COLD WATER SUPPLY TO URINALS--VALVE NOT HOLDING & WATER FLOW CANNOT BE STOPPED TO MAKE REPAIRS. 2) REPLACE 2 FLUSH VALVES ON URINALS THAT HAVE A CONSTANT FLUSH--STOP VALVES NOT HOLDING. Asbsetos Code A - Clear for repairs 02/25/02 DCPS Safety - Ronald Edwards (RE | |||
| FM-200516064 05 12/7/05 "Urgent" First floor, Nurse's Suite. Need electrician to assess and correct electrical issue. There was a lost of power on one whole side of the nurse's suite, school staff checked breaker box but could not resolve issue. | |||
| FM-200617790 06 1/25/06 "Urgent" First floor, Counselor's Suite. Repair or Replace door lock because the lock is sticking. Note: The counselor was locked in her office, the staff were able to get herout but now there's no way to secure the office. | |||
| FM-200508642 05 1/30/06 Cardozo Fire Code Violation Second Floor - Out Side of Balcony 1) Breech in wall. Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200508650 05 1/30/06 Cardozo Fire Code Violation First Floor - Near Room 15 1) Breech in wall. If any fool tile is to be disturbed in repairing breech wall at floor or wall, then abatement will be necessary. Call Safety Office on 202 576-8962 Code A-clear for repair byTilewater Kenny Long on 8/02/05 (SEE ASSESSMENTS) | |||
| FM-200508638 05 1/30/06 Cardozo Fire Code Violation Third Floor - 311 1) Breech in wall . Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200112365 01 2/3/06 CARDOZO SUBBASEMENT- BOYS GYMNASIUM, LOCKER ROOM, SHOWER ROOM AND RESTROOM 1) ASBESTOS ASSESSMENT REQUIRED 2) A. GYMNASIUM AREA INSTALL ONE (1) WATER COOLER IN CORRIDOR OUTSIDE BOYS GYMNASIUM. B. UPGRADE PLUMBING IN BOYS RESTROOM TO INCLUDE ADA COMMIDE, URINALS AND HAND BOWL. C. SHOWER ROOM INSTALL MIXING VALVES, SHOWER HEADS AND UNCLOG FLOOR DRAINS. HEALTH AND SAFETY HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/16/01. HORNE ENGINEERS - TROY WILCOME | |||
| FM-200119567 01 2/3/06 (CARDOZO) ASBESTOS ASSESSMENT REQ. !!!!!!!! URGENT !!!!!! BASEMENT/ B-7 WOODSHOP INSTALL ELECTRIC SERVICE FOR COMPUTERS, 115 VOLTS AND MOUNT POWER STRIPS AS WELL AS WALL OUTLETS. WORK WAS STARTED BUT NEVER FINISHED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/16/01. LEROY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200115692 01 2/3/06 CARDOZO PAINT SCOREBOARD URGENT !!! LEAD BASE PAINT IS CODE A-CLEAR FOR REPAIR BY CEB 7/27/01 | |||
| FM-200112795 01 2/3/06 CARDOZO SUB-BASEMENT WEIGHT ROOM 1) RENOVATE WEIGHT ROOM TO INCLUDE CARPET WITH WALL MIRRORS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/27/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) | |||
| FM-200112794 01 2/3/06 CARDOZO SUB-BASEMENT WEIGHT ROOM 1) RENOVATEWEIGHT ROOM TO INCLUDE LIGHTING UPGRADE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/27/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) | |||
| FM-200508634 05 2/16/06 Cardozo Fire Code Violation Third Floor - Back Stairwell ( N.W. side) 1) Breech in wall. Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200617643 06 3/6/06 "Urgent" Basement Level, Girls' Restroom. Repair or Replace 5" galvanized waste line in girls' restroom. | |||
| FM-200508635 05 3/7/06 Cardozo Fire Code Violation Third Floor - 304 1) Breech in wall and ceiling. Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200508637 05 3/7/06 Cardozo Fire Code Violation Third Floor - 303 1) Breech in wall . Code A- clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200118655 01 4/14/06 (CARDOZO) ASBESTOS ASSESSMENT REQ. 3RD ST. WALL BY PARKING LOT REPAIR LOOSE CEMENT CAP ON BRICK WALL, COULD FALL ON SOMEONE AND INJURE THEM. CEMENT CAP IS 8FT. LONG BY 2FT. WIDE BY 4INCHES THICK-CAP HAS BEEN PUSHED AWAY FROM THE EDGE OF WALL AND IF PUSHED AWAY ANYMORE POSSIBLY COULD FALL ONTO SOMEONE WALKING UNDER. WALL HAS A DOOR WAY LEADING INTO BUILDING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/01/01. HORNE ENGINEERS - STEPHEN CALDWELL | |||
| FM-200620556 06 4/18/06 Ground floor, Gymnasium. "Urgent" Remove electrical outlet & conduit in gymnasium because the students keep pulling it down. Note This is a safety hazard. | |||
| FM-200512202 05 5/16/06 Cardozo Urgent Foorball Stadium-Gate need to be re-attached to the fence | |||
| FM-200508636 05 5/22/06 Cardozo Fire Code Violation Third Floor - Balcony ( Auditorium) 1) Breech in wall . Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. | |||
| FM-200515210 05 6/7/06 Urgent: Remove graffitti from the dug out in the stadium area. | |||
| FM-200221881 02 8/25/06 Cardozo Hallway by Room #10 Asbestos assessment required Replace rupture 3/4"steam line in hallway by room #10. Asbestos Code A - clear for repairs as of 12/3/02 by Horne Engineers Sharon Voss DCPS safety Sylvia Grimes | |||
| FM-200623881 06 11/13/06 CARDOZO- GROUNDS, NORTH WEST SIDE OF BUILDING, REPLACE MISSING RAILING. SAFETY HAZZARD-FALLING DOWN ( 8 TO 10 FEET ) AIR WAY. | |||
| FM-200631062 /06 11/28/06 Cardozo Boiler Room Replace 1" ; 1-1/2 nipples and elbows on steam line in hall by engineers office close nipple leaking on return side. Urgent !!!! | |||
| FM-200448062 04 1/4/07 CARDOZO SHS Urgent Replace packing gland plate on domestic hot water heating circulating pump. | |||
| FM-200627596 06 1/9/07 Building/Furnish safety wire glass 11 inches by 11 inches for replacement in hall fire doors. Asbestos Code A - Clear for repairs on 08/16/06. Tidewater - Carlos Vera (RG 08/17/06) | |||
| FM-200509481 05 1/26/07 (Cardozo) "Urgent" Exterior front of building. Remove down tree in front of building . Note: Safety hazard. | |||
| FM-200506579 05 1/26/07 (Cardozo) "Urgent" Front Entrance. Repair concrete walkway and stairs, concrete is crumbling. | |||
| FM-200512203 05 1/26/07 Cardozo Urgent Foorball Stadium-Cement wall is breaking (pillar on the stadium) | |||
| FM-200449341 04 1/30/07 Cardozo Ground floor hall by room 10 Replace door glass - safety glass size approx: 6 feet by 5 1/4 inch. | |||
| FM-200515534 /05 2/2/07 Urgent: Un-stop sinks in both custodian closets on the second floor, one is across from rm. 212 and the other is across from rm. 211. | |||
| FM-200206112 02 2/20/07 (Cardozo) 1. Asbestos assessment required. REPAIR SAFE IN CAFETERIA OFFICE. CHANGE COMBINATION. Asbestos Code A - Clear for repairs on 05/16/02. DCPS Safety - Leroy Minton Jr. (RG 05/16/02) |