Urgent Closed Repair Requests

See Also: All Closed Repair Requests at Eaton Elementary School

Detailed Reports

Urgent Closed Repair Requests
Description Open Date Close Date Time Elapsed
FM-200105059 01 4/4/02 EATON PLAYGROUND AREA CLEAN OUT AND UNSTOP PLAYGROUND DRAINS. ALL THREE (3) DRAINS NEED CLEANING OUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/24/01. MR. CHARLES BUCHANAN - SAFETY (202)439-7840 March 6, 2001 April 4, 2002 394 days
FM-200209171 02 6/12/02 2-Door Hardware Fire code violation: (Eaton) Page 1 of 1 1st Floor/Next to elevator: Door closer broken on exit door. Asbestos Code A - Clear for repairs for on 06/06/02. DCPS Safety - Leroy Minton Jr. (RG 06/07/02) June 6, 2002 June 12, 2002 6 days
FM-200221172 /02 11/19/02 Eaton Boiler room URGENT NO HEAT Repair broken pneumatic main control switch for heating and cooling ,need switch replaced to heat all class rooms and open space area. November 18, 2002 November 19, 2002 1 day
FM-200222910 /02 3/25/03 (Eaton) Entrance Door: Door is off line and unable to lock properly; staff has to use force to close door. Please service this door. Asbestos Code A - Cleared for repairs on 01-17-03 by Leroy Minton Jr. (LM/01-17-03) Safety Office (202) 576-8962. December 20, 2002 March 25, 2003 95 days
FM-200227755 03 3/27/03 (Eaton) !!!URGENT!!! 2nd Floor/Room #223: Unable to open door, not a lock problem; students are unable to get into the classroom. March 27, 2003 March 27, 2003 0 days
FM-200110559 01 4/28/03 EATON PLAYGROUND EQUIPMENT 1) EMERGENCY REPAIRS FROM SAFETY INSPECTION. May 18, 2001 April 28, 2003 710 days
FM-200207383 02 4/28/03 Eaton Grounds/Playground Area Repair pot-holes and cracks in the asphalt surface. Erosion of surface is creating dangerous stripping hazards. POC: Wilkerson May 8, 2002 April 28, 2003 355 days
FM-200225171 03 6/3/03 Eaton Outside playground area Busted under ground pipe leaking water very bad ,needs to be repair or replace. A student might get hurt. February 4, 2003 June 3, 2003 119 days
FM-200444661 04 4/3/04 Eaton Urgent !!! Main Floor 1) Switches keep tripping in panel box. Switch that controls oven keeps popping off. March 2, 2004 April 3, 2004 32 days
FM-200449816 04 6/28/04 Eaton Chiller Room Repair or replace chiller #1 and #2. Chiller is not working. No air in Building. Urgent !!!!! Replace timer for chiller # 1,2 June 25, 2004 June 28, 2004 3 days
FM-200455476 04 9/23/04 Eaton EMERGENCY Third floor room 308 west side Replace light fixture in book room on 3rd floor next to room 308 and 309. (EMERGENCY situation) Latter to roof is located here, book are everywhere. Asbestos Code A - Clear for repairs on 09/23/04. DCPS Safety - Leroy Minton Jr. (RG 09/23/04) September 22, 2004 September 23, 2004 1 day
FM-200458918 04 12/17/04 EATON Second Floor-Boys Toilet RM 221 West Replace Wax Ring on urnail. Wtaer constantly running down wall. Asbestos Code A - Clear for repairs on 12/02/04. DCPS Safety - Leroy Minton Jr. (RG 12/02/04) December 1, 2004 December 17, 2004 16 days
FM-200458910 04 12/17/04 EATON Third Floor-Boys Toilet RM 316 Replace Wax Ring on urinal. Constantly running down wall. Asbestos Code A - Clear for repairs on 12/02/04. DCPS Safety - Leroy Minton Jr. (RG 12/02/04) December 1, 2004 December 17, 2004 16 days
FM-200503298 05 3/30/05 EATON ES boiler room Pnuematic controls are down Urgent Air compressor air dryer bypass control valve has air leak. Make: Hankison Model: 1701-2 March 28, 2005 March 30, 2005 2 days
FM-200506273 05 6/7/05 (Eaton) "Emergency" Asbestos Assessment Required. First floor, Main entrance. Repair or Replace Entrance door. 1) The doors are coming off the hinges and the building cannot be secured. (The carpenters have already repaired the door on 6/3/05.) 2) Door now need panic bar and cylinder. Asbestos Code A - Clear for repairs on 06/03/05. DCPS Safety - Richard Gibson (RG) June 2, 2005 June 7, 2005 5 days
FM-200513590 05 11/8/05 Eaton Urgent Replace broken water fountain on the third floor "See Maria" October 6, 2005 November 8, 2005 33 days
FM-200221975 02 11/9/05 Eaton Outside - playground area Repair or replace busted under ground pipe, leaking very bad . A kid may get hurt this is very emergency. December 3, 2002 November 9, 2005 1,072 days
FM-200515649 /05 12/28/05 Eaton Boiler Room Replace broken feed water regulator on Boiler #2. Boiler not in use. Safety November 21, 2005 December 28, 2005 37 days
FM-200116794 01 2/3/06 EATON BOILER ROOM ASBESTOS ASSESSMENT REQUIRED ENGINEER NEED TO GAIN ACCESS TO BOILER ROOM. BOILER ROOM DOOR HAS NO KEY. RE-KEY FALCOM LOCK TO ACCOMMADATE ACCESS. URGENT CODE A-CLEAR FOR REPAIR BY DCPS SAFETY LM 8/9/01. August 6, 2001 February 3, 2006 1,642 days
FM-200111391 01 2/3/06 EATON DR. WILLIE MCELROY PTA COMMUNITY GROUP MULTI-PURPOSE ROOM 1) CEILING TILES IN MULTI-PURPOSE NEEDED 12 INCHES X 12 INCHES CEILING HA032 NAD CEB SAFETY OFFICE Asbestos Code A-Clear For Repairs May 29, 2001 February 3, 2006 1,711 days
FM-200517375 06 2/13/06 Eaton Boiler room Repair or replace rupture by pass line and /or valve on air dryer for compressor. Urgent !!!!! January 12, 2006 February 13, 2006 32 days
FM-200618842 06 3/8/06 Eaton Boiler Room Boiler #1 and #2, Need burner cailbration. Urgent !!!! February 21, 2006 March 8, 2006 15 days
FM-200619066 06 3/8/06 Eaton Boiler Room Repair or replace broken feed water regulator on Boiler #1. Boiler not in use for Safety Urgent !!!! February 23, 2006 March 8, 2006 13 days
FM-200334685 03 4/11/06 Eaton Second floor east wing Repair or replace water from control stop valve. Will not shut off. Wall mounted Halsey-Taylor drinking fountain. Leaking URGENT August 8, 2003 April 11, 2006 977 days
FM-200212783 02 4/14/06 Eaton 1. Asbestos Assessment Reqd. Multi-Purpose Room 2. Collect bulk samples of the 12"x12" floor tile and mastic for immediate TAT of samples. **Special Note: Samples were collected of the floor tile and mastics as well as the leveling compound, all sample results as No Asbestos Detected. DCPS Safety-Sheila R. Howard 07-26-02 Code A Clear for Repair by Horne Eng. (Philip Connolloy) 7-25-02 DCPS Safety-Sheila R. Howard 07-26-02 July 24, 2002 April 14, 2006 1,360 days
FM-200458398 /04 4/18/06 Eaton Boy Toilet 3rd Floor Asbestos assessment required. Repair or replace busted steam line leaking very bad. Pipe is 1" going into the floor. Heater is in the Boys Toilet. No Heat. Asbestos code 'A' cleared for repairs. Assessed materials: Ceramic Tile Grout HA 008/040 and fiberglass insulation DCPS Safety, R. Edwards November 17, 2004 April 18, 2006 517 days
FM-200501558 05 4/18/06 Eaton Install 120 volt quad outlet near security console unit to be installed in main entrance lobby. Code A- clear for repairs as of 3/4/05. Sylvia Grimes Safety office. February 11, 2005 April 18, 2006 431 days
FM-200506607 05 8/1/06 Eaton Boiler Room A/C system need to be charge. System is down. Urgent !!!!! June 10, 2005 August 1, 2006 417 days
FM-200621203 06 10/19/06 Exterior Front & Rear of Building & Playground Area. 1.) Install bulbs in outside fixtures. 2.) Furnish & Install additional light fixtures & bulbs in rear of building. Note: This is a safety hazard. April 11, 2006 October 19, 2006 191 days
FM-200459287 04 12/14/06 Eaton Exterior of building Replace exterior light bulbs around perimeter of building. Situation is causing safety issues in the evening and early morning. December 7, 2004 December 14, 2006 737 days
FM-200458463 /04 1/22/07 Eaton Roof area Replace or Repair Roof on Entire Building. 11/18/2004 10:29 OB - Asbestos Code A - Clear for repairs on 11/16/04. DCPS Safety - Charles Buchanan (RG 11/19/04) DUPLICATE WORK ORDER November 18, 2004 January 22, 2007 795 days
FM-200514947 05 1/22/07 Urgent: First Floor-Cafeteria: Repair/Replace flooring, it's warped in several spots throughout cafeteria Asbestos Code A - Clear for repairs on 11/08/05. Tidewater - Tom Marcolin (RG 11/09/05) SEE ASSESSMENTS DUPLICATE WORK ORDER November 1, 2005 January 22, 2007 447 days
FM-200225232 03 1/23/07 (Eaton) !!!VERY URGENT!!! Asbestos assessment required. 1st Floor/Auditorium: Broken tile through-out room. (Asbestos present) Asbestos Code A clear for repairs 2/28/03 DCPS Safety R. Edwards (RE) February 5, 2003 January 23, 2007 1,448 days
FM-200633240 06 3/7/07 Eaton School - Boiler Room - Urgent Request - Send H.V.A.C. machanic to repair or replace pneumatic control system for H.V.A.C. equipment. Appears to be a bad filter valve. Valve Information: PP902D-1007-2-9807, ( Press-Reg. ) Made by Honeywell. Difficult to control heat in some areas. December 9, 2006 March 7, 2007 88 days
FM-200507630 05 3/12/07 !!!!VERY URGENT!!!! First Floor - Main Lobby Area Main security door can't be secured and is falling off the henge. July 11, 2005 March 12, 2007 609 days