| FM-200100191 01 9/13/01 ELIOT BOILER ROOM: REPAIR OR REPLACE 10 SECTIONS OF 4" RETURN LINE IN THE BOILER ROOM OVER DOOR, LEADING TO THE BUILDING. THE LINE HAS NEW INSULATION ON IT. SAFETY AND HEALTH HAZARD. HC-20000750 | |||
| FM-200102021 01 9/13/01 ELIOT 1ST FL. HEALTH SUITE 1. ASBESTOS ASSESSMENT REQUIRED 2. REPAIR 3/4" STEAM RETURN LINE ON CONVENT IN THE HEALTH SUITE BY ENTRANCE DOOR. 9 X 9" BLACK TILE CONCRETE FLOOR. LINE IS LEAKING WATER ON TO THE FLOOR. SAFETY HAZARD. POC MR. BRADLEY CELL #438-7437 CODE A- ASBESTOS ABATED ON 2/16/01. | |||
| FM-200106292 01 12/6/01 ELIOT GIRLS GYMNASIUM ROOF (NEW) IS LEAKING WATER. COMING DOWN IN THE CEILING. PROPERTY DAMAGE HAZARD. ASBESTOS CODE A - ABATED ON 05-05-01(LM) PER LEROY MINTON CONFIRMATION SAFETY OFFICE (202-576-8962) THIS WORK ORDER IS THE SAME AS WO# 200123837 | |||
| FM-200110616 01 1/8/02 (ELIOT) 1. ASBESTOS ASSESSMENT REQUIRED. 1ST FLOOR CUSTODIAL CLOSET/NEAR GIRLS BATHROOM: SINK FAUCET IS STRIPPED, WATER WILL NOT TURN OFF. WATER RUNS IN-TO THE SINK DRAIN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/03/01. RICHARD GIBSON- SAFETY (202)576-5584(RG) | |||
| FM-200201063 02 1/30/02 ELIOT 1ST FL. BY GYM 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPLACE INOPERABLE CONVECTOR TRAP, TRAP LEAKS AT THE SPUD NIPPLE, NIPPLE NUT IS CRACKED. CODE A -CLEAR FOR REPAIR BY HORNE ENG. BIPIN NANAVATY 01-16-02 DCPS SAFETY SHEILA R. HOWARD 01-16-02 | |||
| FM-200201083 02 2/12/02 ELIOT ROOMS 109, 209, HALL BY 103 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPLACE MISSING UNIVENT COIL IN ROOM 105. 3. REPLACE CRACKED RADIATOR IN STARWELL BY RM. 103 4. REPLACE CRACKED RADIATOR IN ROOM 209. CODE A- CLEAR FOR REPAIR BY HORNE ENG. BIPIN NANAVATY 01-16-02 DCPS SAFETY SHEILA R. HOWARD 01-16-02 | |||
| FM-200111875 01 5/2/02 (ELIOT) "URGENT" 1. ASBESTOS ASSESSMENT REQUIRED. 1ST FLOOR CORRIDOR: NO LIGHTS IN THE CORRIDOR. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/31/01. | |||
| FM-200207242 02 5/8/02 Eliot ****Urgent**** 3rd Floor Room 302 The key broke when inserted into the lock. The cylinders appear not to be working. Rekey lock. | |||
| FM-200103815 01 8/5/02 ELIOT CLASSROOM 103 AND OUTSIDE OF CLASSROOM HALLWAY FIRE ENTRANCE BROKEN WINDOWS NEEDS REPLACE TWO (2) WINDOWS DOOR. HEALTH AND SAFETY HAZARD. | |||
| FM-200121990 /01 8/20/02 (ELIOT) ASBESTOS ASSESSMENT REQ. GIRLS GYM TOILETS NEED WAX RINGS. WATER IS COMING FROM UNDER TOILETS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/20/01. RICHARD E GIBSON - SAFETY (202)576-5584 (RG) | |||
| FM-200206983 02 2/6/03 Roof-top: Hole in skylight, piece of plexi-glass broken off. Rain is coming in room #200 on the 2nd floor. Asbestos Code A - Clear for repairs on 05/02/02. DCPS Safety - Richard Gibson (RG 05/02/02) | |||
| FM-200218247 02 3/4/03 (Eliot) Fire code violation: Page 1 of 2 1st Floor: Wall breach in boys gym. Asbestos Code A - Cleared for repairs on 12-02-02 (LM / 12-02-02) Leroy Minton Jr. / Safety Office 202-576-8962. | |||
| FM-200201081 02 3/26/03 ELIOT HALLWAY BY ROOM 209 REPLACE UNIVENT OR COIL, COIL LEAKING. ASBESTOS ASSESSMENT REQUIRED. CODE A -CLEAR FOR REPAIR BY HORNE ENG. BIPIN NANAVATY 01-16-02 DCPS SAFETY SHEILA R. HOWARD 01-16-02 | |||
| FM-200201074 02 3/26/03 ELIOT 2ND FL. ROOM 209A 1. ASBESTOS ASSESSMENT REQUIRED ON PIPE INSULATION AND FLOOR. 2. RADIATOR CAPPED OFF BECAUSE OF LEAK. NEEDS TO BE REPAIRED FOR HEATING. CODE A -CLEAR FOR REPAIR BY HORNE ENG. BIPIN NANAVATY 01-16-02 DCPS SAFETY SHEILA R. HOWARD 01-16-02 | |||
| FM-200218245 02 4/14/03 (Eliot) Fire code violation: Page 1 of 2 1st Floor: Breach in ceiling next to health suite. Asbestos Code A - Cleared for repairs on 12-02-02 (LM / 12-02-02) Leroy Minton Jr. / Safety Office 202-576-8962. | |||
| FM-200333453 03 7/28/03 Eloit !! Urgent !! First Floor - Transition service Unit #104 1. Install a/c unit . a/c unit is on site . | |||
| FM-200334493 03 4/19/04 (Eliot) FIRE CODE VIOLATION: Basement/Multipurpose Room: Safety glass missing from door. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200334469 03 4/19/04 (Eliot) FIRE CODE VIOLATION: 1st Floor/Gym: Safety glass broken to exit door. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200334405 03 4/19/04 (Eliot) FIRE CODE VIOLATION: 2nd Floor/Rear Door: Safety glass missing. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200334389 03 4/19/04 (Eliot) FIRE CODE VIOLATION: 3rd Floor Stairwell: Safety glass in door. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200334414 03 4/19/04 (Eliot) FIRE CODE VIOLATION: 2nd Floor/Balcony: Safety glass to door at balcony. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200334468 03 4/19/04 (Eliot) FIRE CODE VIOLATION: 1st Floor Gym/Locker room: Safety glass missing from door. Asbestos Code A - Clear for repairs on 09/11/03. Horne Engineering - Tony Marcolin (RG 09/12/03) | |||
| FM-200450942 04 12/23/04 Eliot FIRE CODE VIOLATION: Exposed wiring (rooms 303, 310 and 315). IFC 605.1 Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Ricardo Eley (RG 08/19/04) | |||
| FM-200102386 01 7/22/05 (ELIOT) BASEMENT LEVEL/STORAGE ROOM: 1) ASBESTOS ASSESSMENT REQUIRED. 2) REMOVE ALL MATERIAL FROM FLAMABLE STORAGE AREA, OUTSIDE INCINERATOR ROOM. REQUEST SAFETY INSPECTION OF MATERIAL. REQUEST SENT TO SAFETY. Asbestos Code A - Clear for repairs on 03/10/03. Horne Engineering - Philp Connolly (RG 03/11/03) | |||
| FM-200450945 04 10/6/05 Eliot FIRE CODE VIOLATION: Door nor properly labeled ( next to room 310 storage). IFC 703.2 Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Ricardo Eley (RG 08/19/04) | |||
| FM-200450946 04 12/27/05 Eliot FIRE CODE VIOLATION: Electrical cover plate missing ( next to room 310 storage). IFC 605.6 Asbestos Code A - Clear for repairs on 07/28/04. DCPS Safety - Richard Gibson (RG 07/28/04) | |||
| FM-200450965 04 12/27/05 Eliot FIRE CODE VIOLATION: Surge protectors need mounting (thru-out) 2nd floor rooms and offices. IFC 605.3 Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Ricardo Eley (RG 08/19/04) | |||
| FM-200450947 04 12/27/05 Eliot FIRE CODE VIOLATION: Surge protectors need mounting (room 310). IFC 605.3 Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Ricardo Eley (RG 08/19/04) | |||
| FM-200450953 04 12/27/05 Eliot FIRE CODE VIOLATION: Surge protectors need mounting (thru-out 2nd floor rooms). IFC 605.3 Asbestos Code A - Clear for repairs on 08/19/04. DCPS Safety - Ricardo Eley (RG 08/19/04) | |||
| FM-200121894 /01 2/3/06 (ELIOT) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ HALLWAY REPLACE BURNED OUT CIRCUT (#22) BREAKER MAIN HALLWAY 3RD FLOOR CIRCUT BREAKER WILL NOT RESET. HALF OF THE HALLWAY LIGHTS ARE OUT. ALSO CIRCUT BREAKER GIRLS GYM HAS BURNED OPUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG | |||
| FM-200114408 01 2/3/06 ELIOT GYM 1) REMOVE CLIMBING ROPES AND CHAINS FROM GYM CEILING STUDENTS SWINGING AND GETTING HURT ROPES ARE NOT IN USE | |||
| FM-200201939 02 2/3/06 (ELIOT) ***EMERGENCY*** ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR--CLASSROOM 107 REPLACE PLASTER CEILING TILES (6) WHICH HAVE FALLEN THIS MORNING OVER THE TEACHERS DESK. THE TILES ARE PLASTER & HEAVY (COULD CAUSE SERIOUS INJURY). OTHER SPACES CAN BE SEEN WHERE TILES HAVE FALLEN IN THE PAST. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/29/02 BY HORNE ENGINEER: RAY AGNANT LEAD BASE PAINT CODE A-CLEAR FOR REPAIR ON 1/29/02 BY HORNE ENGINEER: RAY AGNANT DO NOT SCRAPE CHIP OR PEEL ANY OF THIS PAINT SURFACE RE-PAINT OVER ONLY | |||
| FM-200455875 04 2/6/06 (Eliot) HEALTH CODE VIOLTION: Kitchen: Remove scaling paint from ceiling over-head dry food items in storeroom. Asbestos Code A - Clear for repairs on 09/29/04. DCPS Safety - Leroy Minton Jr. (RG) | |||
| FM-200331705 03 2/6/06 (Eliot) !!!VERY URGENT!!! 2nd Floor/Room #209 West wing: Repair a/c in the Transition Service Unit. (Ms. Mc Manus office) | |||
| FM-200330097 03 2/6/06 "URGENT" Eliot Basement Kitchen Area Repair or replace 4" inch. nipple and 3/4" inch in cap. Water dripping on food prep area and in the sink | |||
| FM-200227050 03 2/6/06 ELIOT JHS boiler room "URGENT NO ISOLATION VALVES" Replace two 1 1/4 inch lines from condensate tank to vacuum pumps. Lines are ruptured . | |||
| FM-200221478 /02 2/6/06 Eliot - URGENT!!!! Throughout building Scrape peeling paint from walls and ceiling stairwells #1, 2, 3, 6, 7 and 8, peeling paint is falling daily. Scrape and repaint. Also rooms 103A and 103B. Asbestos/Lead Code A-clear for repair by Horne Engineer Edward Rodriguez DCPS Safety Charles E. Buchanan on 11/26/02 | |||
| FM-200221477 /02 2/6/06 Eliot - URGENT!!!! Basement - kitchen/cafeteria Scrape peeling paint and paint dry good storage room. Scrape peeling paint from ceiling in cafeteria overtop steam-table and paint both areas. Asbestos/Lead Code A-clear for repair by Horne Engineer Edwara Rodriguez DCPS Safety Charles E. Buchanan on 11/26/02 | |||
| FM-200209604 02 2/6/06 Eliot 2nd Floor space Area 170 Replace existing lock with a new lock and provide three keys. Asbestos Code A - Clear for repairs, on 6/27/02 DCPS Safety, R. Edwards (RE-6/27/02) | |||
| FM-200207014 02 2/6/06 Eliot Third (3rd) Floor - to 1st Floor Roof leaking water now in Room #104. Water is pouring in the area. Safety Hazard to Students. | |||
| FM-200207003 02 2/6/06 (Eliot Center) !!Very Urgent!! 2nd floor/Girls bathroom: Leaking down in-to boys bathroom on the 1st floor. At this time, there is a steady stream of water coming down. | |||
| FM-200202372 02 2/6/06 (ELIOT[CENTER]) !!!!EMERGENCY!!!! ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR MUSIC ROOM (#101) CEILING TILES ARE FALLING DOWN ONTO THE STUDENTS (POSING SAFETY ISSUES BECAUSE THE CEILING TILES ARE LARGE & HEAVY) POC: MR. DIXON, PRINCIPAL ASBESTOS CODE A-CLEAR FOR REPAIR ON 2/05/02 BY HORNE ENGINEER: EDWARD RODRIGUEZ | |||
| FM-200333962 03 2/6/06 Eliot Room 202 and 306 Survey and install electrical service for window A/C ,in rooms 202 and 306 ,for 26,000 Btu's units Code A-clesr for repair by DCPS Safety Office on 7/31/03 Charles Buchanan | |||
| FM-200448303 04 5/24/06 Eliot URGENT Third floor girls gym Replace panic bar and re-key to exiting master key. | |||
| FM-200633534 /26/06 1/29/07 Third Floor - Mech Room - Repair steam leak. Asbestos Code "A" cleared for repairs 12/29/06--DCPS Safety/Tidewater | |||
| FM-200619201 06 1/29/07 Very Urgent DUPLICATE REQUEST Kitchen-Investigate and repair or replace the garbage disposal may need an electricians help, its unhooked and wires are exposed. | |||
| FM-200500041 05 2/7/07 Eliot Refinish gym floor. Asbestos Code A - Clear for repairs on 01/03/05. DCPS Safety - Richard Gibson (RG 01/04/05) |