Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Backus Middle School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200117713 01 9/10/01 BACKUS FIRST FLOOR - BUSINESS MANAGERS OFFICE 1) INSTALL (2) ELECTRICAL PLUGS IN MAIN OFFICE AND SUB-OFFICE. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY RONALD EDWARD 8/18/01. (CEB) | |||
| FM-200104065 01 9/13/01 Backus Boiler Room Replace safety valve on boiler #1, existing valve will not reset properly. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/24/01. | |||
| FM-200120001 01 9/26/01 (BACKUS) 1. ASBESTOS ASSESSMENT REQUIRED. 3RD FLOOR/TEACHERS BATHROOM: FOREIGN OBJECT STUCK IN LOCK, UNABLE TO RETRIEVE. NO ACCESS TO BATHROOM FOR TEACHERS/STAFF. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/17/01. LEROY MINTON - SAFETY (202)576-6691 | |||
| FM-200120748 01 10/2/01 BACKUS FIRST FLOOR - ROOM 103 URGENT!!! 1) BURNING SMELL COMING FROM LIGHTS... SMELL IS VERY STRONG!!! STUDENTS USE CLASSROOM FOR CLASSES. | |||
| FM-200115508 01 10/18/01 BACKUS CAFETERIA & BOYS GYM ASBESTOS ASSESSMENT REQUIRED REPAIR LIGHTINGS. LIGHTS ARE HANGING FRON CEILING. SAFETY HAZARD CODE A CLEAR FOR REPAIR HORNE ENG. BILL CAMPION 08-24-01. | |||
| FM-200119284 01 11/6/01 (BACKUS) ASBESTOS ASSESSMNET REQ. !!!!!!!!! EMERGENCY !!!!!!! 3RD FLOOR/ BY ROOM 304 PIECE OF FLOOR TILE HAS POPPED UP AND THE BLACK MASTIC IS EXPOSED AND IT HAS ASBESTOS ON IT. (SAFETY HAZARD) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/06/01. HONRE ENGINEERS - ROGER KAGER | |||
| FM-200122898 01 11/7/01 (BACKUS !!!EMERGENCY!!! 1) RE-WELD IRON STAIRWELL RAILING, LEADING TO PARKING LOT. "SUPERINTENDENT, DR. VANCE AND THE MAYORS PROGRAM TO TAKE PLACE ON NOVEMBER 07, 2001 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/03/01 LEROY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200117715 01 11/16/01 BACKUS THIRD FLOOR - 304 1) RELOCATE THERMOSTAT CONTROL WIRES FOR UNIVENT. PRESENTLY WIRES ARE ON FLOOR. WIRES WERE UNDER THE RISERS AND CLASSROOM IS BEING CHANGED TO REGULAR CLASSROOM INSTEAD OF BAND ROOM. RISERS ARE BEING DISGUARDED. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY RONALD EDWARD 8/18/01.(CEB) **(CURRENT REQUEST AS OF 1/15/02) 3RD FLOOR/ROOM 304 REATTACH THERMOSTAT CONTROL WIRES TO UNIVENT IN ROOM 304 TO HEAT ROOM (WIRES CUT BY DCPS BUT WERE NOT RECONNECTED). | |||
| FM-200126621 02 1/7/02 (BACKUS) !!URGENT!! 3RD FLOOR/ROOM #305: WINDOW PANE BROKEN. | |||
| FM-200201917 02 2/4/02 (BACKUS) ASSBESTOS ASSESSMENT REQUIRED 2ND FLOOR TEACHERS LAVATORY NEAR ROOM 204 REPLACE HOT WATER FAUCET WHICH IS CRACKED, RESULTING IN HOT WATER SHOOTING OUT WHEN USED (COULD CAUSE BURNING ACCIDENT) ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/28/02 RICHRRD GIBSON - SAFETY (202)576-5584 (RG)-01/28/02 | |||
| FM-200201928 02 2/5/02 (BACKUS) ***URGENT*** OUTSIDE GROUNDS/PARKING LOT--HAMILTON STREET SIDE RESURFACE BROKEN CONCRETE AT ENTRANCE DOORS AT TOP OF HANDICAPPED RAMP BY CAFETERIA. | |||
| FM-200203135 02 2/22/02 (Backus) ***Very Urgent*** 1. Asbestos Assessment Required. Request lock change on Main entry doors to Health Suite. Unknown person or person(s) entered the area and tampered with the students health records. ASBESTOS CODE A-CLEAR FOR REPAIR NO 2/21/02 HORNE ENGINEER: STEPHEN CALDWELL | |||
| FM-200203371 02 2/25/02 BACKUS !!!! EMERGENCY !!!! 1. ASBESTOS ASSESSMENT REQUIRED. 2. THIRD (3RD) FLOOR - GIRLS LOCKER ROOM PIPE LEAKING WATER FROM THE CEILING, WASTE LINE RUNNING DOWN TO SECOND (2ND) TEACHER CAFETERIA CONTINUOUS LEAKING (WATER). HEALTH AND SAFETY HAZARD. CODE A CLEAR FOR REPAIR BY HORNE ENGINEERING (ROGER KAGER) 02-22-02 DCPS SAFETY-SHEILA R. HOWARD 02-22-02 | |||
| FM-200203566 02 3/6/02 (Backus) ***Urgent*** 1st Floor Principals Office The sink in the principals office was jarred way from the wall as a result of a fight between two students. [Teachers use this sink & it will leak onto the floor if not repaired] | |||
| FM-200204297 02 4/4/02 BACKUS BOILER ROOM Furnish materials to replace broken sewer ejector pump. NOTE: Urgent, flooding boiler room. | |||
| FM-200206785 02 4/30/02 ****Urgent**** Rekey or replace the entry lock on the door to classroom 302. The previous teacher left without turning in the key and the current teacher cannot secure the door. Code A-clear for repair by Horne Engineer by ( Philip Connolly ) on 4/26/02 ( CEB ) | |||
| FM-200206835 02 6/3/02 ****Very Urgent**** 1. Asbestos assessment required. South Dakota Ave. side: Drain stopped up; water will not go down and bugs are present. Visitors are expected in the school on 04/30/02. Asbestos Code A - Clear for repairs on 04/30/02. DCPS Safety - Richard Gibson (RG 04/30/02) | |||
| FM-200206184 02 7/8/02 (Backus) 1. Asbestos assessment required. 3rd Floor/boys locker room: Repair or replace door that has come off hinges. Asbestos Code A - Clear for repairs on 04/23/02. DCPS Safety - Ronaid Edwards (RG 04/23/02) | |||
| FM-200210988 02 7/17/02 (Backus) Fire code violation: Page 4 of 4 1. Asbestos assessment required. 1st Floor/Next to room #108: Door closure broken on exit door next to room #108. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) Disregard Lead Assessment Required type o by SKPjr. 7-15-02 | |||
| FM-200210978 02 7/17/02 (Backus) Fire code violation: Page 3 of 4 1. Asbestos assessment required. 2nd Floor/Multipurpose room; Electrical outlet needs to be replaced. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210952 02 7/17/02 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Boys locker room: Door needs to be re-checked/Restroom. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210969 02 7/17/02 (Backus) Fire code violation: Page 3 of 4 1. Asbestos assessment required. 2nd Floor/Room #212: Door closure broken. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210995 02 7/17/02 (Backus) Fire code violation: Page 4 of 4 1. Asbestos assessment required. 1st Floor/Stairway - A: Doors needs to be checked. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210985 02 7/17/02 (Backus) Fire code violation: 1. Asbestos assessment required. 2nd floor/Multipurpose room: Light fixture needs to be checked; electrical hazard through-out. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210984 02 7/18/02 (Backus) Fire code violation: 1. Asbestos assessment required. 2nd floor: Door closure broken on girls and boys restroom door. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210950 02 7/18/02 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Boys locker room storage room: Light fixtures needs to be repaired through-out. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210967 02 7/22/02 (Backus) Fire code violation: 1. Asbestos assessment required. 2nd Floor/Next to classroom #203: Ceiling tile missing in the hallway. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210968 02 7/22/02 (Backus) Fire code violation: Page 2 of 4 1. Asbestos assessment required. 2nd Floor/Room #202-203: Ceiling tile missing in storage room. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210951 02 7/24/02 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Boys locker room: Ceiling tile missing in storage room. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210993 02 7/26/02 (Backus) Fire code violation: Page 4 of 4 1. Asbestos assessment required. 1st Floor/Classroom #104: Breach in classroom. (Does not indicate ceiling breach or wall breach) Asbestos Code A clear for repairs, on 7/11/02 Per Mr. Gross(Custodian Supervisor) it is a ceiling breach.7-15-02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210981 02 7/29/02 (Backus) Fire code violation: Page 3 of 4 1. Asbestos assessment required. Multipurpose room: Ceiling tile missing through-out classroom #267. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200213328 02 8/2/02 (Backus) !!!Very Very Urgent!!! 1st Floor/Room #100: Staff member locked keys in the main office; staff unable to get in. (Need extra keys made for this door) | |||
| FM-200214078 02 8/13/02 Backus ****Urgent**** 1st Floor Principal's Office Repair fallen ceiling light fixture in the principal's office. The wires are now exposed. | |||
| FM-200206784 02 8/26/02 ****Urgent**** 1. Asbestos Assessment Reqd. 1st Floor Main Office Suite 2. Install electrical plugs in the office closet by office suite one. 3. Remove power strip for internet from the hole in the wall; close hole after removal. Code A-clear for repair by Horne Engineer by ( Philip Connolly ) on 4/26/02 ( CEB ) | |||
| FM-200217379 02 9/13/02 Backus ****Urgent**** Drain @ Exit From Auditorium to Outside The drain is stopped up and needs to be cleared. | |||
| FM-200218813 02 10/5/02 Backus M.S Boiler Room Start up burners and test safety controls on specified boilers. | |||
| FM-200216671 02 11/1/02 Backus ****Urgent**** 3rd Floor Rooms 310 & 303 None of the electrical outlets are working in rooms 301 & 303. Repair lights or restore power. | |||
| FM-200213257 02 11/13/02 Backus ****Very Urgent**** 2nd Floor Room 209 Heat pump cooling unit is leaking water profusely and causing the ceiling tiles in the classroom below [Rm. 105] to fall. Also, inspector is due to come and reinspect later this evening---would like to avoid being cited. | |||
| FM-200227611 03 3/25/03 Backus Boiler room (URGENT) Unstop floor drain in the boiler room area,this needed in order to drain the boilers for repairs | |||
| FM-200203194 02 3/28/03 (Backus) Asbestos Assessment Required 3rd Floor Gym Locker Rooms Furnish & install wooden benches in both boys and girls gyms. Asbestos Code A - Clear for repairs on 6/12/02 DCPS Safety - Ronald Edwards (RE-6/12/02) | |||
| FM-200210973 02 4/11/03 (Backus) Fire code violation: Page 3 of 4 1. Asbestos assessment required. 2nd Floor/Next to room #214: Door glass missing on exit door next to room #214. Site visit 4-10-03 by Julius Dancy Code Inspector repairs completed. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210954 02 7/7/03 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Boys/girls shower area: Light fixtures needs to be covered. (Electrical hazard) Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210949 02 7/7/03 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Boys locker room: Light fixtures needs to be repaired. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200332786 03 7/14/03 Backus Rooms 108, and 210 SUMMER SCHOOL SITE! 1) Restore electrical service to window A/C units outlet, cannot locate circuit in the pannel box, for room 108. 2) Upgrade electrical service in room 210 from 20 amp circuit to 30 amp circuit, a/c unit is on site in the window. Asbestos Code A - Cleared for repairs on 07-01-03 by Leroy Minton Jr. (LM/07-01-03) Safety Office 202-576-8962. | |||
| FM-200337489 03 9/29/03 Backus EMERGENCY Room 211 fire sparks when switch come on. Room 213 wall plug unit is out, because it was on fire sparks no electricity in the room. Asbestos Code A - Clear for repairs on 09/15/03. DCPS Safety - Richard Gibson (RG) | |||
| FM-200338676 03 10/8/03 (Backus) !!!VERY URGENT!!! 3rd Floor Girls Locker Room/Bathroom: Leaking down in 2nd floor kitchen; bathroom above Possible leaking from that bathroom. | |||
| FM-200336603 03 10/15/03 Backus URGENT Second floor room 211 Fire coming out of light fixture when lights are turn on. Possible balance firing. | |||
| FM-200443416 04 2/27/04 Backus Classrooms #106, #108, #202, #211, #214, #302 and #306 Correct what appears to be circulating problem with heating system in these areas. Bleeding system regularly. Note: This is an old problem. Urgent !!!! | |||
| FM-200447797 04 5/14/04 (Backus) !!!URGENT!!! 1st Floor/Room #107: Restore electrical power to wall outlets; all lights are working. | |||
| FM-200217377 02 6/3/04 Backus ****Urgent**** Rooms 206 [Teachers' Lounge] & 208 1. The ballast is smoking when the switch in room 208 is in the "on" position--replace ballast; and 2. There is a power outtage in the teachers' lounge #206. The breaker has been checked, so there is some other cause of the outtage. | |||
| FM-200451424 04 8/6/04 (Backus) !!!URGENT!!! 1st Floor/Boys, and Girls Lavatories: Repair or replace automotive flush not working. The water over-flows on the commode in the girls. | |||
| FM-200336537 03 9/9/04 (Backus) !!!VERY URGENT!!! 1st Floor/Room #107: No power to electrical outlets. | |||
| FM-200336834 03 9/13/04 (Backus) !!!URGENT!!! 1st, & 2nd Floor: No electrical power to outlets in room #104, #107, and sparks coming from lights. Partial lights in room #206, #211, and sparks are coming from lights. | |||
| FM-200228296 03 9/14/04 (Backus) !!!VERY URGENT!!! 3rd Floor/Room #310: Lights are out in the hallway and room #310 | |||
| FM-200503771 05 4/18/05 (Backus) "Urgent" Kitchen Area. Install electric hot water heater in kitchen area. | |||
| FM-200214999 02 5/3/05 Backus ****Urgent**** 1. Asbestos Assessment Reqd. 2nd Floor Multi-purpose Room 2. Install two electrical outlets, one by the recreation kitchen under the new telepholne outlet; and one by the weight room for the new election polling equipment. The election is on September 10, 2002. Asbestos code A-clear for repair by Horne Engineer ( Philip Connolly ) on 8/20/02 Charles E. Buchanan | |||
| FM-200201951 02 5/3/05 (BACKUS) ASBESTOS ASSESSMENT REQUIRED 2ND FLOOR RECREATION ROOM REPLACE BREAKER #1 IN PANEL BOX (FEDERAL 30 AMP BREAKER WHICH SUPPORTS 2 ROWS OF LIGHTS IS NOT WORKING) ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/29/02 RICHARD GIBSON - SAFETY (202)576-5584 (RG)-01/29/02 | |||
| FM-200506120 05 6/27/05 (Backus) "Urgent" Grounds/Pond Area. Furnish and install 6' fence and gate to enclose and secure pond next to tennis court. Note: This is a Safety Hazard. 6' poles are present 3' fencing is also there. Dedication of pond is 06/05/05. | |||
| FM-200108277 01 7/25/05 BACKUS SECOND (2ND) FLOOR CLASSROOM 212 AND ASST. PRINCIPAL OFFICE 1) A/C UNIT IS TRIPPING THE BRAKER SYSTEM THIRD (3RD) FLOOR CLASSROOM 307 - SPOT COOLER AND CLASSROOM 316 - WINDOW A/C UNIT 1) ASBESTOS ASSESSMENT REQUIRED 2) REPLACE PLUGS, NEEDS MORE UPGRADE ELECTRICAL OUTLETS. URGENT! ASBESTOS CODE A - CLEAR FOR REPAIRS ON 04/23/01. | |||
| FM-200108471 01 7/25/05 BACKUS FIRST (1ST) AND SECOND (2ND) FLOOR CLASSROOMS FURNISH AND INSTALL SIXTY-FOUR (64) ELECTROIC INSTANT START 120 VOLTS 60 HZ BALLAST IN THE FOLLOWING LOCATION CLASSROOM. 102 - 2 202 - 12 208 - 4 105 - 4 204 - 10 210 - 8 106 - 12 206 - 8 212 - 4 SAFETY HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/02/01. | |||
| FM-200457079 /04 8/1/05 Backus Second floor Replace the handle on the hallway door by 214, handle is missing unable to access. Asbestos Code A - Clear for repairs on 10/22/04. DCPS Safety - Leroy Minton Jr. (RG 10/23/04) | |||
| FM-200457081 /04 8/1/05 Backus First and Second floor Realign room doors 104, 208, 205, 213 and 315. Also 4 exit doors need to be realign on the first floor, one on the second floor. This door will not open in case of fire. Asbestos Code A - Clear for repairs on 10/19/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200457085 /04 8/1/05 Backus First floor Ceiling tile need to be replace in the rooms 104, 105 and 106 to third floor hallways is a lot missing tile throughout the building. Asbestos Code A - Clear for repairs on 10/22/04. DCPS Safety - Leroy Minton Jr. (RG 10/23/04) | |||
| FM-200457273 /04 8/3/05 (Backus) HEALTH CODE VIOLATION: Kitchen: Peeling paint, and plaster in dry goods. Asbestos Code A - Clear for repairs on 10/25/04. DCPS Safety - Leroy Minton Jr. (RG 10/25/04) | |||
| FM-200209261 02 8/3/05 Backus ****Urgent**** 3rd Floor Room 304 [Band Room] The lock on the door to the band room [304] was broken during an attempted break-in. The instruments are badly needed for graudation exercise practice [can not get into the band room]. | |||
| FM-200443619 04 8/3/05 (Backus) !!!URGENT!!! 2nd Floor/Cafeteria: Unable too get water, and leaking. 3rd Floor: Unable to get drinking water from the fountain. | |||
| FM-200455462 04 8/3/05 (Backus) !!!VERY URGENT!!! 1st Floor/Room #102: Burning electrical smell; students were moved to another room. | |||
| FM-200447949 04 9/26/05 Backus URGENT Rooms 315, 313 and girlsa locker Key handles were damaged in the following areas by students. Teachers get lock in above rooms and can not get out. VANDALISM | |||
| FM-200222872 /02 12/7/05 (Backus) !!!VERY URGENT!!! 1st Floor/Near nurse's office: Repair or replace water cooler. | |||
| FM-200227527 03 12/14/05 (Backus) Parking lot Hamilton St. Lot is coming apart, need refacing before someone gets injured due to loose surface. | |||
| FM-200227552 03 12/14/05 (Backus) Parking lot/Hamilton: Lot is coming apart; lot needs re-facing before someone is injured. | |||
| FM-200220101 /02 12/15/05 (Backus) !!!URGENT!!! 1. Asbestos assessment required. 1st Floor/Boys bathroom: Water leaking from sink; unable to access cut-off valves. | |||
| FM-200202031 02 2/3/06 (BACKUS) ***URGENT*** ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR MAIN HALLWAY AREA NEED TO DRILL 12 HOLES IN WALLS TO SUPPORT BRACKETS FOR DISPLAYING FIRE SAFETY PICTORIAL INSTRUCTIONS (WILL BE DONE IN-HOUSE BY MR. GROSS). THE PICTURES WERE PROVIDED BY DCPS & IT IS A FIRE CODE VIOLATION NOT TO HAVE THE PICTURES PROMINENTLY DISPLAYED AT EYE-LEVEL. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: EDWARD RODRIGUEZ | |||
| FM-200118868 01 2/3/06 (BACKUS) 3RD FLOOR/ ALL OF THE FLOOR NEED 390 DEFUSER COVERS FOR EGGSHELL CRATE LIGHTS. (SAFETY HAZARD) ISOLATE EMERGENCY!!! | |||
| FM-200202074 02 2/3/06 BACKUS !!!! EMERGENCY !!!! SECOND (2ND) FLOOR - ACTIVITY ROOM (WEIGHT AREA) SMELL OF SMOKE IS SMELL IN THE AREA, DONOT KNOW WHERE IT IS COMING FROM. SAFETY HAZARD. | |||
| FM-200618318 06 2/6/06 First Floor-Nurse Suite Very Urgent Toilet is running over and the pipe to the toilet is leaking, investigate and repair the problem. Note: The water was turned off | |||
| FM-200210977 02 4/14/06 (Backus) Fire code violation: Page 3 of 4 1. Asbestos assessment required. 2nd Floor/Multipurpose center room: Breach in wall. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200210953 02 4/14/06 (Backus) Fire code violation: Page 1 of 4 3rd Floor/Girls locker room: Breach in wall. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200116502 01 4/14/06 BACKUS 2ND & 3RD FLOOR ASBESTOS ASSESSMENT REQUIRED POINT UP MORTISE JOINTS & CINDER BLOCK WALLS IN THE FOLLOWING CLASSROOMS: 201, 202, 203, 203A, 204, 205, 206, 206A, 208, 210, 211, 212, 214, 301, 302, 303, 304, 305, 306, 307, 308, 309, 310, 312, 313, 314, 315, 316 & 317 JOINTS ARE WASHING OUT DUE TO HEAVY RAIN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. CHARLES BUCHANAN - SAFETY (202)576-5582 | |||
| FM-200210979 02 4/18/06 (Backus) Fire code violation: Page 4 of 4 1. Asbestos assessment required. 1st Floor/Main office: Breach in wall next to office #1. Asbestos Code A clear for repairs, on 7/11/02 DCPS Safety, L. Minton (RE - 7/11/02) | |||
| FM-200620387 06 5/8/06 First & Second floors. "Urgent" 1.) First floor remount or replace electrical box that is hanging from the wall. 2.) Second floor/Rec. Area, repair or replace breaker # 1 (R) that has a shortage, the breaker is continuously tripping. | |||
| FM-200513750 /05 6/2/06 Backus Urgent Front Side Of Building-Entrance Door near Gallatin St. Exit Install hand rail on the Steps, the railing has rusted away, also the steps have shifted need to be repaired | |||
| FM-200617642 06 6/7/06 "Urgent" Lower Level, Kitchen Area. Install Circulation pump in kitchen. | |||
| FM-200627553 06 10/10/06 Second Floor/Rm. 206 missing safety glass. Asbestos Code A - Clear for repairs on 08/16/06. Tidewater - Kenny Long (RG 08/17/06) | |||
| FM-200504002 05 10/23/06 (Backus, Bernie) "Urgent" Asbestos Assessment Required. Throughout building. Replace a broken glass in room 208 (1) panel, Rec. Area (1) door glass and Office in Boys' locker room (1) glass. Asbestos Code A - Clear for repairs on 04/14/05. DCPS Safety - Leroy Minton Jr. (RG 04/14/05) | |||
| FM-200216431 02 12/6/06 Backus Asbestos Assessment Reqd. 3rd Floor Classroom 308 Repair holes in the sheet-rock wall in classroom 308 by the door and storage room. Asbestos Code A - Clear for repairs on 09/04/02. DCPS Safety - Leroy Minton Jr. (RG 09/05/02) | |||
| FM-200512538 05 1/11/07 Backus Urgent Door by room 101 is broken and need to be repaired/replaced Code A-clear for repair by DCPS Charles Buchanan on 9/16/05 | |||
| FM-200453184 04 1/11/07 Backus First, Second Floor - Main Entrance - 104 and 205 1) Re-align entrance door on Main Lobby, Room 104 and Storage Room 205., so Locksmith can secure door. Asbestos Code A - Clear for repairs on 08/27/04. DCPS Safety - Leroy Minton (RG 08/27/04) | |||
| FM-200453430 04 1/11/07 Backus exterior first by the big parking lot Repair door the hinge reattach and panic bar. Asbestos Code A - Clear for repairs on 08/27/04. DCPS Safety - Leroy Minton (RG 08/27/04) | |||
| FM-200513752 /05 1/11/07 Backus Urgent Install a new A/C unit in the window of rooms 304, and 316 | |||
| FM-200206736 02 1/29/07 ****Urgent**** 1. Asbestos Assessment Reqd. 1st Floor Auditorium 2. Install electrical plugs on right side of Aisle F. The junction box is under the seat. This is for a special media event "Together for Freedom" to take place april 30, 2002. Code A Clear For Repair by Horne Engineering (Sheryll James) 04-26-02. DCPS Sheila R. Howard 04-26-02 | |||
| FM-200460111 /04 1/29/07 Backus URGENT Room 308 Furnish and install flourescent lights for the journalize lab. | |||
| FM-200508965 05 1/30/07 Backus Auditorium Correct problem that causing two (2) window A/C units to trip electric circuit breaker when in operation. Urgent !!!! | |||
| FM-200515874 /05 1/30/07 Urgent: Second Floor-Recreational Area: electrical outlets have sparks coming from them one on the wall and one on the column. | |||
| FM-200512622 05 1/30/07 (Backus) "Urgent" First floor, Main Office. Need electricians to assess and repair problem. A/C units have shut off temperature is extremely hot!! | |||
| FM-200626368 06 1/30/07 Second Floor/Rm. 208 - Door glass broken Asbestos Code A - Cleared for repairs on 08/02/06 by Tidewater/Kenny Belton (LM-08/02/06) Safety Office 202-576-8962. | |||
| FM-200206783 02 2/6/07 ****Urgent**** 1. Asbestos Assessment Reqd. 2nd Floor Recreation Room 2. Reattach electrical box to the wall. The box is live and there are exposed wires. 3. Install an (2) electrical outlet (plug for telephone rack to electrion office) in the rec room near the weight room. Code A-clear for repair by Horne Engineer by ( Philip Connolly ) on 4/26/02 ( CEB ) | |||
| FM-200218268 02 2/6/07 Backus ****Urgent**** Basement Boiler Room Newly installed sump pump is not working and water is all over the floor. Workers who would be working in the boiler room will not work with the water all over the floor. | |||
| FM-200207546 02 2/6/07 Backus !!! Emergency !!! Third (3rd) Floor - Girls Locker Restroom Two (2) Sink. Water is leaking all over the floor. Two (2) Toilet and T-Trap. Not working properly. Safety Hazard. | |||
| FM-200227550 03 2/6/07 (Backus) Panel Box: Shortage in breaker box, one (1) circuit keeps kicking out. Asbestos Code A - Clear for repairs on 03/24/03. DCPS Safety - Richard Gibson (RG) | |||
| FM-200517014 /05 2/6/07 Backus Classrooms Replace burnt out motors on univent in room #101, #104, #106,#206, #204, #302, #314 and #304 Urgent !!!! | |||
| FM-200513146 05 2/6/07 (Backus) "Urgent" Near lobby. Electrical boxes are about to fall off of wall, they are currently being held in by two screws. | |||
| FM-200502495 05 2/6/07 {Backus) "Very Urgent" Asbestos Assessment Required. Second/Third floor. Replace missing ceiling tile on second and third floor. Students knocked tile down. Notice: Urgent dust falling from ceiling Asbestos Code A - Clear for repairs on 03/14/05. DCPS Safety - Leroy Minton Jr. (RG 03/15/05) | |||
| FM-200213527 02 2/6/07 Backus ****Urgent**** 1. Asbestos Assessment Reqd. 1st & 3rd Floors/Classrooms 102 and 308 2. Repair breaches in wall: Room 102--breach left from repair measures 12"X12"; Room 308--breach left in sheet-rock wall measures 2' across by 3' in height. School due for re-inspection by fire marshall on 8/8/02----need repair ASAP. Asbestos Code A - Clear for repairs on 08/19/02. DCPS Safety - Leroy Minton Jr (RG 08/20/02) | |||
| FM-200504339 05 2/20/07 ( BACKUS ) URGENT!!!! Rooms 301-303 1) The electrical plugs are burned out. 2) The panel box on the side, the brakers are broken. (principal is requesting to upgrade the electricity in whole building) | |||
| FM-200511565 05 2/21/07 Backus Boiler Room Repair or replace couplin 1 1/4" on pump. Repair or replace hot water circulating pump #1 and #2 both pumps not working properly, need work badly, Urgent !!!!! | |||
| FM-200218488 02 3/20/07 Backus ****Urgent**** Asbestos Assessment Reqd. 1st Floor Room 104 Replace/upgrade lights and ballasts. The ballast exploded in room 104. POC: Mr. Belzher 576-6112 Asbestos Code A - Clear for repairs on 09/30/02. Horne Engineering - Bipin Nanavaty ( RG 10/01/02) |