Urgent Closed Repair Requests

See Also: All Closed Repair Requests at Johnson JHS

Detailed Reports

Urgent Closed Repair Requests
Description Open Date Close Date Time Elapsed
FM-200114563 01 9/5/01 JOHNSON LIBRARY 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPAIR PIPE RUPTURED IN CEILING. PIPE SIZE IS UNKNOWN, COVERED BY INSULATION. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 July 2, 2001 September 5, 2001 65 days
FM-200117493 01 9/7/01 JOHNSON BATHROOM - B WING AREA ASBESTOS ASSESSMENT REQUIRED EMERGENCY!!!!!!!!!!!!! BATHROOM TOILETS & UTILITY SINKS ARE CLOGGED UP. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 ASBESTOS CODE A - CLEAR FOR REPAIR ON 10/03/01, BY EDWARD RODRIGUEZ - HORNE ENGINEERING (RE-10/04/01) August 15, 2001 September 7, 2001 23 days
FM-200110879 01 10/1/01 JOHNSON EXTERIOR GROUNDS ATHLETIC FIELD 1) REPLACE WATER FAUCET BEHIND ATHLETIC FIELD BUILDING ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 May 23, 2001 October 1, 2001 131 days
FM-200115763 01 10/10/01 JOHNSON MAIN OFFICE / PRINCIPAL ASBESTOS ASSESSMENT REQUIRED BATHROOM TOILET IS BACKING UP. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 July 24, 2001 October 10, 2001 78 days
FM-200114565 01 10/22/01 JOHNSON ROOM 319 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPAIR PIPE RUPTURED IN CEILING. 3/4" DRAIN LINE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 July 2, 2001 October 22, 2001 112 days
FM-200108397 01 10/24/01 JOHNSON 1ST FL. ROOM 102 COMPUTER LAB AND CEILING TO UNIVENT IN ROOM#202 1. ASBESTOS ASSESSMENT REQUIRED IN ORDER TO RECEIVE WORK PERMIT. PIPE COVERED WITH INSULATION. 2. HOT WATER PIPE REPUPTURED IN CEILING. PIPE SIZE IS UNKNOWN. COVERD BY INSULATION. 3.REPLACE PIPE IN CEILING OF ROOM#102 COMPUTER LAB THROUGH FLOOR TO ROOM#202 UNIVENT SUPPLY AND RETURN LINE. CODE A-CLEAR FOR REPAIR BY HORNE ENG. STEPHEN CALDWILL 8/29/01. ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/30/01. LEROY MINTON - SAFETY (202)576-6691 April 13, 2001 October 24, 2001 194 days
FM-200113451 01 11/21/01 JOHNSON ROOM #421 REPAIR OR REPLACE WINDOW AIR CONDITIONING UNIT IN ROOM #421. THE UNIT HAS STOPPED COOLING . THERE IS NO VISUAL COOLANT LEAK. WP-200108868 ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 June 18, 2001 November 21, 2001 156 days
FM-200117147 01 11/21/01 (JOHNSON) AIR CONDITIONER LEAKING THE FOLLOWING CLASSROOMS: ROOMS #225, 221, 227, 428, 226, & 330. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 ASBESTOS CODE A - CLEAR FOR REPAIR ON 10/03/01, BY EDWARD RODRIGUEZ - HORNE ENGINEERING (RE-10/04/01) August 10, 2001 November 21, 2001 103 days
FM-200112202 01 11/27/01 JOHNSON FIRST FLOOR SECURITY OFFICE 1) NEED A WELDER TO CUT A WINDOW OUT FOR AIR-CONDITIONING UNIT ON ON SITE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 June 4, 2001 November 27, 2001 176 days
FM-200112200 01 11/30/01 JOHNSON FOURTH FLOOR COMPUTER LAB ROOMS 401 AND 402 1) RUN AN ELECTRICAL LINE FOR AIR-CONDITIONER ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 June 4, 2001 November 30, 2001 179 days
FM-200121838 /01 11/30/01 (JOHNSON) ASBESTOS ASSESSMENT REQ. 1ST AND 4TH FLOOR/ ROOM 412 AND NURSE OFFICE HAS NO POWER GOING TO UNIVENT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG October 17, 2001 November 30, 2001 44 days
FM-200116209 /01 12/1/01 JOHNSON, J.H. GYMNASIUM ASBESTOS ASSESSMENT REQUIRED PRINCIPAL REQUEST THAT THE GYMNASIUM AREA BE RE-KEYED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/07/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) November 29, 2001 December 1, 2001 2 days
FM-200109968 01 1/23/02 JOHNSON FIRST (1ST) FLOOR - RECREATION SIDE REMOVE TWO (2) WINDOW GUARDS FROM RECREATION SIDE OF BUILDING SO THAT GLAZERS ARE ARILE REPAIR BURNT WINDOWS. ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 May 10, 2001 January 23, 2002 258 days
FM-200122301 /01 2/5/02 (JOHNSON) ASBESTOS ASSESSMENT REQ. 2ND AND 3RD FLOOR/ ROOMS 306, 312, 227, AND 212 REPLACE WOOD ENTRANCE CLASSROOM DOORS. DOORS ARE SPLIT AND DANGEROUS. (SAFETY HAZARD) ASBESTOS/LEAD CODE A-CLEAR FOR REPAIR BY 11/01/01 HORNE ENGINEER: SAM EBRAHIM October 24, 2001 February 5, 2002 104 days
FM-200201809 02 2/7/02 (JOHNSON) ASBESTOS ASSESSMENT REQUIRED BOYS LOCKER ROOM REPAIR LOCKING DEVICE ON MECHANICAL ROOM (SAFETY HAZARD). ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/25/02 RICHARD GIBSON - SAFETY (202)576-5584(RG)-01/25/02 February 5, 2002 February 7, 2002 2 days
FM-200204846 02 3/22/02 (Johnson) ***Very Urgent*** Stairwell #2 between 1st and 2nd floor: Large window blew out; unable to find window pane. March 22, 2002 March 22, 2002 0 days
FM-200204993 02 4/29/02 (Johnson) ****Urgent**** Asbestos Assessment Required 2nd Floor Boys Lavatory There is leaking from a toilet in the 2nd floor boys lavatory going down through the ceiling into classroom 106. The toilet needs snaking. Code A-clear for repair by Horne Engineer (Sam Ebrahim) on 3/28/02 (CEB) March 27, 2002 April 29, 2002 33 days
FM-200207116 02 5/10/02 Johnson ****Very Urgent**** 2nd Floor Room 214 Replace wire-mesh safety glass in window of room 214 [absence of window poses a serious safety hazard]. May 3, 2002 May 10, 2002 7 days
FM-200209305 02 6/12/02 Johnson !!! Emergency !!! Recreation - Rear Back Side of Kitchen 1. Window guard needs to be repaired. Safety Hazard. June 11, 2002 June 12, 2002 1 day
FM-200209314 02 6/12/02 Johnson !!! Emergency !!! Recreation - Rear Back Side of Kitchen 1. Broken out window glass needs to be replaced. Safety Hazard. June 11, 2002 June 12, 2002 1 day
FM-200209740 02 6/18/02 Johnson !!! Urgent !!! Roof Top - Sky Light Glass is broken and its hanging down out of the Sky light of the stairwell leading to cafeteria area. Health and Safety Hazard. June 18, 2002 June 18, 2002 0 days
FM-200215469 02 9/3/02 (Johnson) !!!URGENT!!! Main office: Install electrical wall out-let for new copier machine. Asbestos Code A-clear for repair by Horne Engineer Troy Wilcome on 8/26/02 DCPS Charles E. Buchanan August 23, 2002 September 3, 2002 11 days
FM-200201118 02 9/10/02 JOHNSON EXTERIOR FRONT OF BUILDING REMOVE TRIPPING HAZARD FROM METAL POLES TWO (2) ON FRONT PORCH OF BUILDING. SAFETY HAZARD. ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/16/02 SHEILA HOWARD - (202)576-8962 (RG) January 15, 2002 September 10, 2002 238 days
FM-200217622 02 10/31/02 Johnson 2nd Floor Girls' Lavatory Partition frame is bent causing doors to swing and not close. Repair or remove frame [safety hazard]. September 17, 2002 October 31, 2002 44 days
FM-200221391 /02 2/12/03 Johnson First floor room 106 Request additional wall plug in room 106 for the use of computer. Asbestos Code A - Clear for repairs on 11/20/02. DCPS Safety - Leroy Minton Jr. (RG 12/02/02) November 20, 2002 February 12, 2003 84 days
FM-200208679 02 3/19/03 Johnson ****Urgent**** Exterior Grounds/Lawn The lawn needs trimming and there is no lawn equipment on site. The grass has grown too tall for a small mower and there is a program planned for Saturday morning, 8:00am-5:00pm. Emergency assistance is requested. May 30, 2002 March 19, 2003 293 days
FM-200226564 03 3/25/03 Johnson Basement - stairwell #3 Foundation of steps has crack in it. When it rain basement floods. Safety Hazard March 5, 2003 March 25, 2003 20 days
FM-200218807 02 3/26/03 Johnson J.H.S Boiler Room Start up burners and test safety controls on specified boilers. October 3, 2002 March 26, 2003 174 days
FM-200221572 /02 3/26/03 JOHNSON JHS Room 204 1. Asbestos asessment may be required 2. Replace / repair leaking heat coil can not be isolated. Asbestos Code A - clear for repairs as of 12/3/02 by Horne Engineers Tony Marcolin DCPS safety Sylvia Grimes. November 25, 2002 March 26, 2003 121 days
FM-200221109 /02 3/26/03 JOHNSON JHS ROOM 305 "URGENT" 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPAIR/REPLACE RUPTURED 3/4 " HOT WATER SUPPLY TO UNIVENT. NOTE: CAN NOT BE ISOLATED. Asbestos Code C by Horne Engineer Bipin Nanavaty on 11/19/02 DCPS Charles E. Buchanan Code A - Asbestos abated on 11/25/02 PER Leroy Minton Jr. confirmation (RG 11/26/02) November 18, 2002 March 26, 2003 128 days
FM-200329097 03 4/25/03 (Johnson) !!!VERY URGENT!!! 2nd Floor/Room #204: Pipe leaking in ceiling. 3rd Floor/Room #305: Pipe leaking in ceiling. April 25, 2003 April 25, 2003 0 days
FM-200227986 03 5/5/03 Johnson Basement kitchen area Need a welder to come out and check steamtable. Pole is hanging off . Safety Hazard April 1, 2003 May 5, 2003 34 days
FM-200116966 01 5/5/03 JOHNSON FIRST )1ST) FLOOR - BOYS & GIRLS SHOWER-ROOMS 1. INSTALL SHOWER MIXING VALUES IN BOYS. 2. INSTALL SHOWER HEADS IN GIRLS. (NO PENETRATION) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 August 8, 2001 May 5, 2003 635 days
FM-200221782 02 5/8/03 Harris, C.W. Second floor room 225 & 113 Replace wood entrance classroom door. Door split and dangerous. Collect bulk sample from damage door for asbestos analysis. Asbestos Code A - Clear for repairs on 12/05/02. Horne Engineering - Philp Connolly (RG 12/13/02) December 2, 2002 May 8, 2003 157 days
FM-200329653 03 5/30/03 Johnson !! EMERGENCY !! Basement - Cafeteria Radiator pipe that runs along the cafeteria floor was jumped on by students and the pipe burst and water running everywhere . Unable to shut off the water. Code A - clear for repairs as of 5/6/03 by Sylvia Grimes DCPS Safety. May 6, 2003 May 30, 2003 24 days
FM-200331174 03 6/25/03 Johnson URGENT First Floor - nurses and principal bathroom Unstop toilets. June 4, 2003 June 25, 2003 21 days
FM-200331175 03 7/9/03 Johnson URGENT First Floor - Engineers office Unstop toilet. The toilet is backing up and smelling. June 4, 2003 July 9, 2003 35 days
FM-200331176 03 7/14/03 Johnson URGENT Second Floor - girls lavatory Unstop toilet on the end in girls lavatory. June 4, 2003 July 14, 2003 40 days
FM-200228049 03 7/22/03 Johnson Second floor classroom 202 Replace wood entrance room door. Door is split and dangerous. Safety Health Hazard. Asbestos Code A-clear for repair by Horne Engineering Sharon Voss on 04/07/03 Charles Buchanan April 1, 2003 July 22, 2003 112 days
FM-200334494 03 8/20/03 Johnson F-110.0 FIRE CODE VIOLATION: Basement By girls gym Safety glass. August 5, 2003 August 20, 2003 15 days
FM-200334490 03 8/20/03 Johnson F-110.0 FIRE CODE VIOLATION: Fourth floor by room 414 Safety glass. August 5, 2003 August 20, 2003 15 days
FM-200334491 03 8/20/03 Johnson F-110.0 FIRE CODE VIOLATION: Third floor by room 315 Safety glass. August 5, 2003 August 20, 2003 15 days
FM-200334492 03 8/20/03 Johnson F-110.0 FIRE CODE VIOLATION: Third floor by room 301 Safety glass. August 5, 2003 August 20, 2003 15 days
FM-200337631 03 10/7/03 Johnson Urgent Health suite and room 318 Repair or replace faucet on sink in the main office principal lavatory. It continue to run , also health suite, and the sink in roon 318 is clogged up and backing up. September 16, 2003 October 7, 2003 21 days
FM-200340308 /03 12/9/03 (Johnson Jr.) !!!URGENT!!! Basement/Back Entry Door: Panic bar damaged (broken) staff leave the builidng through this entrance. Engineer will secure door until locksmith arrives. November 14, 2003 December 9, 2003 25 days
FM-200443711 04 2/10/04 JOHNSON JHS URGENT !!! Classroom - 319 ASBESTOS ASSESSMENT MAY BE REQUIRED LEAK CAN NOT BE ISOLATED Repair rupture domestic water line. Line is leaking from inside concrete and brick wall of room 319. Asbestos Code A - Clear for repairs on 02/05/04. Horne Engineering - Bipin Nanavaty (RG 02/05/04) February 5, 2004 February 10, 2004 5 days
FM-200338184 03 4/1/04 Johnson Urgent Fourth and third floor custodian closet Utility sinks need new faucets. September 29, 2003 April 1, 2004 185 days
FM-200447895 04 8/11/04 (Johnson) !!!VERY URGENT!!! 2nd Floor/Room #229: Teacher unable to get into room, cylinder continues to spin. May 13, 2004 August 11, 2004 90 days
FM-200332784 03 8/18/04 Johnson First & Third Floor 1. Install electrical outlets for the new installation of a/c units in (1) assist. principal office ,classrooms D109 (2) ,107 (2) and (1) on 3rd floor assist. principal office across from elevator - a/c units are on site. Asbesros Code A - Clear for repairs on 07/01/03. DCPS Safety - Leroy Minton Jr. (RG 07/02/03) July 1, 2003 August 18, 2004 414 days
FM-200451269 04 9/16/04 (Johnson) FIRE CODE VIOLATION: Room #312: Safety glass needed. August 2, 2004 September 16, 2004 45 days
FM-200451316 04 9/16/04 (Johnson) FIRE CODE VIOLATION: 2nd Floor/Stairwell #3: One (1) safety glass. August 2, 2004 September 16, 2004 45 days
FM-200451308 04 9/16/04 (Johnson) FIRE CODE VIOLATION: 2nd Floor/Stairwell #4: Safety glass missing from doors. (2) August 2, 2004 September 16, 2004 45 days
FM-200451286 04 9/16/04 (Johnson) FIRE CODE VIOLATION: Exit Stairwell #3: Door safety glass. August 2, 2004 September 16, 2004 45 days
FM-200451270 04 9/16/04 (Johnson) FIRE CODE VIOLATION: Stairwell #2: Replace broken safety glass. August 2, 2004 September 16, 2004 45 days
FM-200456585 04 10/8/04 Johnson EMERGENY Asbestos Assessment Required. Room #416 Damage Frame and door to classroom. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Charles Buchanan (RG 10/07/04) October 7, 2004 October 8, 2004 1 day
FM-200457080 /04 10/27/04 (Johnson) 4th Floor/Near Elevator: 1. Water fountain leaking on the floor; possible busted line in the wall. 2. Ceiling fell due to leaking in the recreation area. Asbestos Code A - Clear for repairs on 10/19/04. DCPS Safety - Richard Gibson (RG) October 19, 2004 October 27, 2004 8 days
FM-200457458 /04 11/2/04 (Johnson) !!!URGENT!!! Headstart Main Office, and Room #104: Change locks, issue keys, due to theft. The director of operation need her small closet lock changed. October 26, 2004 November 2, 2004 7 days
FM-200457412 /04 11/4/04 Johnson Room #102 -Head Start Asbestos assessment required Repair or replace ruptured 2" line in the ceiling (10' Feet) Urgent !!!! Asbestos Code A - Clear for repairs on 10/26/04. DCPS Safety - Charles Buchanan (RG 10/26/04) October 26, 2004 November 4, 2004 9 days
FM-200456613 04 11/30/04 Johnson Basement recreation area Ceiling in rec fell due to water damage, light fixture hanging live wire. Asbestos Code A - Clear for repairs on 10/15/04. DCPS Safety - Richard Gibson (RG) October 7, 2004 November 30, 2004 54 days
FM-200457520 /04 12/2/04 (Johnson) !!!URGENT!!! Second floor teacher bathroom Teacher has broken her key off in bathroom door need to get door open. October 27, 2004 December 2, 2004 36 days
FM-200453773 04 12/30/04 (Johnson) Basement area hallway near cafeteria Fire box need to be bolted back into wall. Asbestos Code A - Clear for repairs on 09/01/04. DCPS Safety - Richard Gibson ( 09/01/04 ) September 1, 2004 December 30, 2004 120 days
FM-200456506 04 1/4/05 Johnson Second floor room 220 Small window (wire mesh) glass in room need to be replace student vandalized. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/06/04) October 5, 2004 January 4, 2005 91 days
FM-200500343 05 1/27/05 Johnson Rec. Area Storage Room Repair or replace 3/4" rupture pipe in Rec. Area Storage Room. No insulation and no isolation valves. Urgent !!!!!! January 12, 2005 January 27, 2005 15 days
FM-200500839 05 1/27/05 Johnson First floor door by the gym The exit door can not be secure, it is coming off the hinges. Asbestos Code A - Clear for repairs on 01/26/05. DCPS Safety - Richard Gibson (RG) January 26, 2005 January 27, 2005 1 day
FM-200506014 05 5/27/05 (Johnson) "Urgent" Fourth floor/Right side of building. Need electrician to assess and repair electrical problem. May 26, 2005 May 27, 2005 1 day
FM-200457083 /04 8/1/05 (Johnson) !!!VERY URGENT!!! Asbestos Assessment Required. 1st Floor/Recreation Area: Ceiling fell, water leaking, and live electrical wire hanging from the ceiling. Asbestos Code A - Clear for repairs on 10/19/04. DCPS Safety - Richard Gibson (RG) October 19, 2004 August 1, 2005 286 days
FM-200456999 /04 8/1/05 Johnson Third floor room 318 Room 318 door entrance wire mesh glass need to be replace / student vandalized. Asbestos Code A - Clear for repairs on 08/27/04. DCPS Safety -Leroy Minton Jr. (RG 08/29/04) October 18, 2004 August 1, 2005 287 days
FM-200457042 /04 8/1/05 (Johnson) !!!VERY URGENT!!! 3rd Floor/Classroom #318: Sinks in art room clogged up with a very bad smell; water will not go down. October 19, 2004 August 1, 2005 286 days
FM-200451292 04 8/26/05 (Johnson) FIRE CODE VIOLATION: Room #313: Door won't close in frame. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 August 26, 2005 389 days
FM-200451274 04 8/26/05 (Johnson) FIRE CODE VIOLATION: 3rd Floor/Across from Room #306: Door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 August 26, 2005 389 days
FM-200451273 04 8/26/05 (Johnson) FIRE CODE VIOLATION: 3rd Floor/Boys Room: Door closer next to Stairwell #2. Code A -clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 August 26, 2005 389 days
FM-200451264 04 8/26/05 (Johnson) FIRE CODE VIOLATION: 3rd Floor: Door closer missing on stairwell #1 Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 August 26, 2005 389 days
FM-200451212 04 8/26/05 (Johnson) FIRE CODE VIOLATION: Asbestos Assessment Required. Room #420: Repair broken door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. July 30, 2004 August 26, 2005 392 days
FM-200451211 04 8/26/05 (Johnson) FIRE CODE VIOLATION: Asbestos Assessment Required. Across from Room #420: Door closer missing in boys restroom. Code A - clear for repairs as of 8/6/04 safety Sylvia. July 30, 2004 August 26, 2005 392 days
FM-200451284 04 9/7/05 (Johnson) FIRE CODE VIOLATION: Room #308: Door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 September 7, 2005 401 days
FM-200451213 04 9/7/05 (Johnson) FIRE CODE VIOLATION: Asbestos Assessment Required. Room #411: Repair broken door closer. Code A- clear for repairs as of 8/6/04 safety Sylvia. July 30, 2004 September 7, 2005 404 days
FM-200451210 04 9/7/05 (Johnson) FIRE CODE VIOLATION: Room #404: Door closer. Code A - clear for repairs as of 8/6/04. safety Sylvia. July 30, 2004 September 7, 2005 404 days
FM-200451214 04 9/7/05 (Johnson) FIRE CODE VIOLATION: Asbestos Assessment Required. Across from Room #416: Replace door closer. Code A -clear for repairs as of 8/6/04 safety Sylvia. July 30, 2004 September 7, 2005 404 days
FM-200451275 04 10/13/05 (Johnson) FIRE CODE VIOLATION: Storage Room #326: Door hardware knob. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 October 13, 2005 437 days
FM-200509096 05 10/13/05 Johnson "Fire Code Violation" Third Floor Ceiling tile missing in room 318 Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 13, 2005 76 days
FM-200509097 05 10/13/05 Johnson "Fire Code Violation" Third Floor Ceiling tile missing in hallway third floor Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 13, 2005 76 days
FM-200451306 04 10/13/05 (Johnson) FIRE CODE VIOLATION: 2nd Floor/Stairwell #4: Door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 October 13, 2005 437 days
FM-200451295 04 10/13/05 (Johnson) FIRE CODE VIOLATION: 3rd Floor/Hallway: Ceiling tile. Code A- clear for repairs. Replace ceiling tile only safety Sylvia. August 2, 2004 October 13, 2005 437 days
FM-200451294 04 10/13/05 (Johnson) FIRE CODE VIOLATION: Room #318: Ceiling tile missing. Code A- clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 October 13, 2005 437 days
FM-200451321 04 10/18/05 (Johnson) FIRE CODE VIOLATION: Room #227: Ceiling tiles missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 October 18, 2005 442 days
FM-200451312 04 10/18/05 (Johnson) FIRE CODE VIOLATION: Room #218: Missing ceiling tile. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 October 18, 2005 442 days
FM-200509101 05 10/25/05 Johnson "Fire Code Violation" Second Floor Ceiling tile missing in hallway by room 220 Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 25, 2005 88 days
FM-200451322 04 10/25/05 (Johnson) FIRE CODE VIOLATION: Room #204: Ceiling tiles missing. (2) Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 October 25, 2005 449 days
FM-200451323 04 10/25/05 (Johnson) FIRE CODE VIOLATION: Room #202 Ceiling tiles missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 October 25, 2005 449 days
FM-200451327 04 10/25/05 (Johnson) FIRE CODE VIOLATION: Room #229: Ceiling tile missing. Code A- clear for repairs. Replace ceiling tile only safety Sylvia. August 2, 2004 October 25, 2005 449 days
FM-200509099 05 10/25/05 Johnson "Fire Code Violation" Second Floor Ceiling tile missing in room 202 Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 25, 2005 88 days
FM-200509112 05 10/26/05 Johnson "Fire Code Violation" Basement Ceiling tile missing (hallway by stairwell out side of head start) Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 26, 2005 89 days
FM-200509105 05 10/26/05 Johnson "Fire Code Violation" First Floor Ceiling tile missing by elevator (hallway) Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 26, 2005 89 days
FM-200509111 05 10/26/05 Johnson "Fire Code Violation" Basement Ceiling tile missing (by elevator) hallway Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 October 26, 2005 89 days
FM-200451392 04 10/26/05 (Johnson) FIRE CODE VIOLATION Cafeteria/Rear Exit: Four (4) ceiling tiles missing. Asbestos Code A - Clear for repairs on 09/09/04. DCPS Safety - Leroy Minton Jr. (RG 09/09/04) August 3, 2004 October 26, 2005 449 days
FM-200451333 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Room #154: Door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 November 16, 2005 471 days
FM-200458722 /04 11/16/05 JOHNSON Third Floor RM 315 Install DOOR ON RM 315 Asbestos Code A - Clear for repairs on 12/01/04. DCPS Safety - Leroy Minton Jr. (RG 12/01/04) November 26, 2004 November 16, 2005 355 days
FM-200456612 04 11/16/05 Johnson Third floor room 315 Replace wood entrance room door. Door is hanging off. Safety Health Hazard Asbestos Code A - Clear for repairs on 10/07/04. DCPS Safety - Charles Buchanan (RG 10/08/04) October 7, 2004 November 16, 2005 405 days
FM-200451385 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Gym Door Exit to Locker Room: Gym door closer missing. Code A- clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 November 16, 2005 470 days
FM-200451383 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Egresser Rear Stairwell: Gym door closer missing. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 November 16, 2005 470 days
FM-200451356 04 11/16/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Egress Stairwell: Broken door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 November 16, 2005 470 days
FM-200451325 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Room #204: Door closer missing. Code A- clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 November 16, 2005 471 days
FM-200451324 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Room #233: Ceiling tiles missing. (1) Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 November 16, 2005 471 days
FM-200451319 04 11/16/05 (Johnson) FIRE CODE VIOLATION: Room #227: Repair door closer. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 November 16, 2005 471 days
FM-200451276 04 11/30/05 (Johnson) FIRE CODE VIOLATION: Boys Room Across from #306: Door closer. Code A- clear for repairs as of 8/6/04 safety Sylvia. August 2, 2004 November 30, 2005 485 days
FM-200509095 05 11/30/05 Johnson "Fire Code Violation" Third Floor Ceiling tile missing by room 315 Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 November 30, 2005 124 days
FM-200451206 04 12/7/05 (Johnson) FIRE CODE VIOLATION: Asbestos Assessment Required. Next to Room #425: Door hardware/Replace door knob. Code A- clear for repairs as of 8/6/04 safety Sylvia. July 30, 2004 December 7, 2005 495 days
FM-200515873 /05 12/12/05 Urgent: Repair cylinder lock to the asst. principal office on the first floor, the key is stuck and the lock is turning in the cylinder. The door can't be opened. November 29, 2005 December 12, 2005 13 days
FM-200452163 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Recreation, and Cafeteria: Repair door hardware/knob, door closer, ceiiing tile, and missing door safety glass. Asbestos Code A - Clear for repairs on 09/09/04. DCPS Safety - Leroy Minton Jr. (RG 09/09/04) August 11, 2004 December 27, 2005 503 days
FM-200451334 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Library: Ceiling tiles missing. (3) Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 2, 2004 December 27, 2005 512 days
FM-200451345 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Breezeway Corridor Ceiling tiles missing. (3) Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451354 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Bruce Pl. Side: Ceiling tile missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451374 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Bruce Pl. Side: Push bars need to be re-mounted exit egress. Code A-clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451436 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Head Start Exit: Three (3) ceiling tile missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia 8/4/04. August 4, 2004 December 27, 2005 510 days
FM-200451442 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Exit Door: Re-attach closer. Asbestos Code A - Clear for repairs on 09/01/04. DCPS Safety - Richard Gibson ( 09/01/04 ) August 4, 2004 December 27, 2005 510 days
FM-200451457 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Breezeway Corridor: A total of two (2) ceiling tile needed. Code A- clear for repairs as of 8/5/04 safety Sylvia August 4, 2004 December 27, 2005 510 days
FM-200451386 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Rear Cafeteria Door: Total (4) broken door closers. Code A-clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451355 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Next to Office: Door closer broken at main exit. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451358 04 12/27/05 (Johnson) FIRE CODE VIOLATION: 1st Floor/Across from Office: Unable to get door to close in frame in stairwell Exit. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451365 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Auditorium Lobby Area: Two (2) ceiling tiles missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451366 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Auditorium Corridor Area: Large breach hole. Code A - clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451369 04 12/27/05 (Johnson) FIRE CODE VIOLATION: Auditorium Side/Stage door: Breach hole over auditorium across from room #10: Code A -clear for repairs as of 8/6/04 safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200451370 04 12/27/05 (Johnson) FIRE CODE VIOLATION: D-112: Ceiling tiles missing. Code A - clear for repairs. Replace ceiling tile only. safety Sylvia. August 3, 2004 December 27, 2005 511 days
FM-200510574 05 1/26/06 (Johnson) "Urgent" Rear exterior of building. Remove bulk trash from premises. August 17, 2005 January 26, 2006 162 days
FM-200201813 02 2/3/06 (JOHNSON) ASBESTOS ASSESSMENT REQUIRED BOYS LOCKER ROOM THE SQUIRREL CAGE SHOULD BE REPAIRED & COVER FOR THE HEATING UNIT IS MISSING & SHOULD BE REPLACED OR REPAIRED IN THE BOYS LOCKER ROOM (SAFETY HAZARD). ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/29/02 RICHARD GIBSON - SAFETY (202)576-5584 (RG)-01/29/02 January 25, 2002 February 3, 2006 1,470 days
FM-200111468 01 2/3/06 JOHNSON FIRST FLOOR AUDITORIUM 1) ROOF LEAK AFFECTING AREA BELOW ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 ASBESTOS CODE A - CLEAR FOR REPAIR ON 10/03/01, BY EDWARD RODRIGUEZ - HORNE ENGINEERING (RE-10/04/01) May 29, 2001 February 3, 2006 1,711 days
FM-200112106 01 2/3/06 JOHNSON 1) REPLACE (90) STAINED CEILING TILE (2X4) REPLACE (150 ) MISSING OR BROKEN (2X4) 2) REPLACE (0) STAINED CEILING TILE (12X12) REPLACE (0) MISSING OR BROKEN (12X12) 3) REPAIR OR REPLACE LIGHT FIXTURES AS NEEDED. (CEILING TILE REPLACEMENT PROJECT) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 June 4, 2001 February 3, 2006 1,705 days
FM-200114223 01 2/3/06 JOHNSON FOURTH FLOOR ROOMS 401AND 402 COMPUTER LAB 1) NEED AN ELECTRICIAN TO RUN A LINE FOR USE OF AIR CONDITIONER ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 June 28, 2001 February 3, 2006 1,681 days
FM-200114668 01 2/3/06 JOHNSON FRONT OF BUILDING AND MAIN OFFICE 1) FURNISH AND INSTALL PLEXIGLASS IN ALL WINDOWS ON FRONT AND MAIN OFFICE SIDES OF BUILDING PLEXIGLASS IS DARK AND FADED ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 July 3, 2001 February 3, 2006 1,676 days
FM-200115895 01 2/3/06 JOHNSON 1ST, 2ND, 3RD & 4TH HALLWAYS ASBESTOS ASSESSMENT REQUIRED SHOWER / LOCKER ROOMS REPAIR 300 HANDLES, REMOVE ROUGH EDGES ON FRAMES, FIX OR REPLACE 200 BENT DOORS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/07/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) July 25, 2001 February 3, 2006 1,654 days
FM-200125505 /01 2/3/06 (JOHNSON) 1. ASBESTOS ASSESSMENT REQUIRED. EXTERIOR PARKING LOT: REPLACE EXTERIOR LIGHTS ON SMALL PARKING LOT. CUSTODIAL CARS WERE VANDALIZED ON 12/12/01. (SECURITY) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/22/02. DCPS - SAFETY - SHEILA R. HOWARD (RG 02/22/02) December 17, 2001 February 3, 2006 1,509 days
FM-200201816 02 2/3/06 (JOHNSON) ASBESTOS ASSESSMENT REQUIRED BOYS LOCKER ROOM WOODEN BENCHES ARE GONE FROM THE BOYS LOCKER ROOM & THE BRACKETS WHICH ANCHORED THE MISSING BENCHES NEED TO BE REMOVED OR THE BENCHES NEED TO BE REPLACED (SAFETY HAZARD). ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: STEPHEN CALDWELL January 25, 2002 February 3, 2006 1,470 days
FM-200332795 03 2/16/06 (Johnson Jr. High) !!!VERY URGENT!!! 2nd Floor/Classroom #201: Principal request to have a/c installed. Air conditioning units on site. Asbestos Code A - Clear for repairs on 07/03/03. Horne Engineering - Troy Wilcome ( RG 07/03/03 ) July 1, 2003 February 16, 2006 961 days
FM-200512613 05 2/16/06 Johnson Second Floor-Classroom 227 Replace wire-mesh safety glass in window of room 227 student vandalized. September 15, 2005 February 16, 2006 154 days
FM-200510653 05 2/24/06 (Johnson) Jasper st. side of Building Repair Entrance Door Asbestos A A Cleared for repairs on 08/18/05 by Leroy Minton Jr. (LMJ/08-18-05) Safety Office 202-576-8962. August 17, 2005 February 24, 2006 191 days
FM-200505363 05 2/28/06 (Johnson) "Urgent" Exterior rear of building./Third floor. Weld window guard and secure to building, currently it is hanging on by a nail. May 11, 2005 February 28, 2006 293 days
FM-200620199 06 3/29/06 Very Urgent Second Floor-Classroom 202 Replace wood entrance door its hanging on one bolt. Asbestos Code A - Clear for repairs on 03/27/06. DCPS Safety - Leroy Minton Jr. (RG 03/27/06) March 22, 2006 March 29, 2006 7 days
FM-200506478 05 4/11/06 (Johnson) "Urgent" Specified areas. Install water coolers (4) in areas needed. Note: Install water coolers in areas that are specified by staff members. June 7, 2005 April 11, 2006 308 days
FM-200202236 02 4/14/06 (JOHNSON JR.) !!!EMERGENCY!!! EXPLORATORY DEMOLITION IN GROUND FLOOR. 1. ASBESTOS ASSESSMENT REQUIRED. 2. 3RD CONVECTOR/OUTSIDE BASEMENT: RUPTURED GALVANIZED UNIVENT PIPE IN FLOOR, LEADING TO CAFETERIA, LEAKING AND FLOODING THE FLOOR. LEAKING. DCB (IT GROUP)/703-461-6848 THIS JOB WENT THROUGH ASBESTOS ABATEMENT BUT WAS NOT DONE PROPERLY, THE WORK IS NOT CLEARED FOR REPAIR AT THIS TIME 02-06-02. DCPS SAFETY-SHEILA R. HOWARD 02-06-02. CODE A - ASBESTOS ABATED ON 02/11/02 PER SHEILA R HOWARD CONFIRMATION.(RG 02/12/02) January 31, 2002 April 14, 2006 1,534 days
FM-200620847 06 4/26/06 Johnson Room #102 Head Start Side Replace 3/4" supply line on univent. Can not be isolated. Urgent !!!!! April 4, 2006 April 26, 2006 22 days
FM-200621076 06 4/26/06 Johnson Room #102 Head Start Side Replace 1-1/4" brushing 3/4"supply line and union ceiling univent. Can not be isolated. Urgent !!!!! April 4, 2006 April 26, 2006 22 days
FM-200509109 05 9/11/06 Johnson "Fire Code Violation" First Floor Ceiling tile missing in first floor hallway (thru-out) Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 September 11, 2006 409 days
FM-200509110 05 9/11/06 Johnson "Fire Code Violation" First Floor Ceiling tile missing (room 104 head start) Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 September 11, 2006 409 days
FM-200509106 05 9/11/06 Johnson "Fire Code Violation" First Floor Ceiling tile missing in library Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 September 11, 2006 409 days
FM-200509102 05 9/11/06 Johnson "Fire Code Violation" First Floor Ceiling tile missing (hallway outside of gym) Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 September 11, 2006 409 days
FM-200509107 05 9/11/06 Johnson "Fire Code Violation" First Floor Ceiling tile missing in library Asbestos Code A - Clear for repairs on 08/08/05. DCPS Safety - Richard Gibson (RG) July 29, 2005 September 11, 2006 409 days
FM-200631119 /06 11/9/06 JOHNSON URGENT No HEAT! Boiler room Boiler # 1tap broken end of temperature gauge off to replace with new one. October 23, 2006 November 9, 2006 17 days
FM-200506524 05 1/4/07 ( JOHNSON ) URGENT!!! Fourth Floor - Room 419 1) Replace a large broken out window June 8, 2005 January 4, 2007 575 days
FM-200619915 06 1/12/07 Very Urgent Second floor-exterior walkway Patio near library railings are loose. Weld-Student almost fell off of patio March 14, 2006 January 12, 2007 304 days
FM-200502719 05 1/22/07 (Johnson) "Emergency" Asbestos Assessment Required. Third floor/Room 315. Repair and Replace large wire mesh glass in door. Note: Student vandalized. Asbestos Code A - Clear for repairs on 03/30/05. DCPS Safety - Leroy Minton Jr. (RG 03/30/05) March 15, 2005 January 22, 2007 678 days
FM-200337635 03 1/22/07 Johnson Second floor room 213 Replace wood entrance door. Door is split and dangerous. Code A-clear for repair by DCPS Charles Buchanan on 9/17/03 September 16, 2003 January 22, 2007 1,224 days
FM-200619668 06 1/26/07 Urgent Second Floor-Boys Bathroom Door broken-Can not service-Need new door. Asbestos Code A - Clear for repairs on 03/09/06. Tidewater - Henry Addison (RG 03/13/06) March 8, 2006 January 26, 2007 324 days
FM-200338185 03 2/2/07 Johnson Urgent Fourth and third floor, rec area custodian closet Principal request the knob lock be changed with new lock cut to grandmaster. September 29, 2003 February 2, 2007 1,222 days
FM-200224603 03 2/5/07 JOHNSON JHS "URGENT NO HEAT IN CLASSROOMS" Room temperatures are 55 degrees F Restore eletrical service to univent motors in the following areas Room 412, 413 and univent near room 414. Urgent no heat in classrooms room temp is 55 degrees F Asbestos Code A- Cleared for repairs on 01-27-03 by Leroy Minton Jr (LM/01-15-04) Safety Office. 202-576-8962. January 27, 2003 February 5, 2007 1,470 days
FM-200336588 03 3/28/07 Johnson Second floor room 213 Replace wood entrance door. Door is split and dangerous. Asbestos Code A - Clear for repairs on 08/29/03. Horne Engineering - Edward Rodriguez ( RG 09/02/03 ) August 29, 2003 March 28, 2007 1,307 days
FM-200456053 04 3/30/07 Johnson EMERGENY Third floor room 416: Door is hanging on one hinge. Damaged door to room #416 Asbestos Code A - Clear for repairs on 10/15/04. DCPS Safety - Richard Gibson (RG) September 29, 2004 March 30, 2007 912 days
FM-200443916 04 3/30/07 Johnson First floor gym Very dangerous, two sets of bleachers are broken need to be repair. Asbestos Code A - Clear for repairs on 02/11/04. Horne Engineering - Edward Rodriguez (RG 02/12/04) February 10, 2004 March 30, 2007 1,144 days