Closed Repair Requests: February 2006

See Also: All Closed Repair Requests at Ballou Senior High School

February 2006 Summary

  • Urgent Requests
    5
    Average Time Elapsed: 1,006.8 Days
  • Routine Requests
    26
    Average Time Elapsed: 907.9 Days
  • Total Requests
    31

Detailed Reports

Urgent Repair Requests Completed in February 2006 (5)
Description Open Date Close Date Time Elapsed
FM-200118037 01 2/3/06 (BALLOU) ASBESTOS ASSESSMENT REQD. SUB-BASEMENT FLOOR CORRIDOR PANEL BOX NEEDS TO BE SURVEYED BY ELECTRICIANS- INSPECTOR *DAVID BRYANT* HAS REQUESTED THIS SURVEY ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. RONALD EDWARDS - SAFETY (202)576-6693 August 21, 2001 February 3, 2006 1,627 days
FM-200114105 01 2/3/06 BALLOU (STAY) SUB-BASEMENT ROOMS A-4 AND A-9 1) ELECTRICAL UPGRADE FOR COMPUTERS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/30/01. SYLVIA GRIMES - SAFETY (202)576-5583 (RG) June 26, 2001 February 3, 2006 1,683 days
FM-200120876 01 2/3/06 BALLOU 1ST FL. ASST. PRINCIPALS OFFICE 1. ASBESTOS ASSESSMENT IS REQUIRED. 2. REPLACE (1) WINDOW A/C UNIT. iNFO: AMANA MOD #S1082R, SER. # 022350773 V. 115, HZ 60, AMP 7.5, BTU 8200. ASBESTOS CODE A-CLEAR FOR REPAIR 12/03/01 BY DCPS SAFETY : RONALD EDWARDS 202 439 8094 REPAIR WAS COMPLETED AT TIME OF INSPECTION. October 2, 2001 February 3, 2006 1,585 days
FM-200517122 06 2/9/06 Furnish and Install rim cylinder lock to new doors. "Urgent" Note: This is a issue of safety. January 5, 2006 February 9, 2006 35 days
FM-200515099 05 2/16/06 "Urgent" Replace/Secure girls restroom door on the first floor near the gym due to a fire. Asbestos Code A - Clear for repairs on 11/09/05. Tidewater - Rodney Distance (RG 11/14/05) November 4, 2005 February 16, 2006 104 days

Routine Repair Requests Completed in February 2006 (26)
Description Open Date Close Date Time Elapsed
FM-200617625 06 2/1/06 Ground Floor-Boys PE Office Change the lock on the door, can't get into the room (Key it to the building master) January 20, 2006 February 1, 2006 12 days
FM-200618007 06 2/2/06 First Floor - Main Office - Can not unlock door, lock is stuck... January 30, 2006 February 2, 2006 3 days
FM-200110983 01 2/3/06 BALLOU SUB-BASEMENT A-6 REPAIR WATER COOLER LINE CLOGGED UP - WATER LEAKING IN IN CORRIDOR. EMERGENCY!! NO PENETRATION May 24, 2001 February 3, 2006 1,716 days
FM-200123367 01 2/3/06 BALLOU 2ND & 3RD FL. ENTIRE CLASSROOMS RECONNECT MAIN EXISTING ELECTRICAL POWER SOURCE TO THE HEATING UNIVENTS ON THE 2ND & 3RD FL. CLASSROOMS. (NO HEAT) NOTE: CONTRACTOR WORK HAS HAD AN EFFECT ON THIS POWER SOURCE LOSS. ELECTRICAL SOURCE TO UNITS WERE OPERATIONAL UNTIL THE RENOVATION AND MODIFCATION TOOK PLACE. ASBESTOS CODE A-CLEAR FOR REPAIR 11/30/01 BY HORNE ENGINEER: ROGER KAGER November 2, 2001 February 3, 2006 1,554 days
FM-200121644 /01 2/3/06 (BALLOU) ASBESTOS ASSESSMENT REQ. 1ST FIRST/ FITNESS CENTER THIS FITNESS CENTER NEEDS SOME SORT OF LOCK, DEAD BOLT IF POSSIBLE. THIS AREA NEEDS TO BE SECURED. ASBESTOS CODE A-CLEAR FOR REPAIRS BY 10/17/01 HORNE ENGINEER : ROGER KAGER October 15, 2001 February 3, 2006 1,572 days
FM-200119806 01 2/3/06 BALLOU OUTSIDE STADIUM MECHANICAL RM. WEST. REPAIR ENTIRE AIR HANDLER UNIT, INCLUDING MOTOR. (FOR HEATING). NOTE: FIRE DAMAGE TO THIS UNIT. September 14, 2001 February 3, 2006 1,603 days
FM-200119770 01 2/3/06 BALLOU 1. ASBESTOS ASSESSMENT REQUIRED. 1ST FL. ATTENDANCE OFFICE ROOM 109 INCREASE ELECTRICAL AMPERE FROM 20 AMPS TO 40 AMPS CIRCUIT BREAKER. INFO: PANEL BOX - QOC420L NOTE: 20 AMP. CIRCUIT BREAKER DOES NOT PROVIDE ENOUGH POWER FOR THE ELECTRICAL EQUIPMENT. Requester Phone: 645-3385 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/01/01. HORNE ENGINEERING - TROY WILCOME (RG) September 7, 2001 February 3, 2006 1,610 days
FM-200116661 01 2/3/06 BALLOU FIRST (1ST) AND THIRD (3RD) FLOORS AMP ROOMS #119, 120, 121, 122, 123, 124, 149 , 353 ,150 AND 137. 1) ASBESTOS ASSESSMENT REQUIRED. 2) THE FLOOR TILES TO BE REMOVED HAVE BEEN MARKED WITH ORANGE PAINT (DOT). IN ROOM #A-36/107 (AMP ROOM #119) THE CONTRACTOR MARKED THE OUTLINE OF THE FLOOR TILES. ENVIROBATE (IT GROUP) 703-461-6848 CODE A - ASBESTOS ABATED ON 8/5/01 (SG) PER LEROY MINTONS CONFIRMATION. August 3, 2001 February 3, 2006 1,645 days
FM-200116089 01 2/3/06 BALLOU AUDITORIUM 1) ASBESTOS ASSESSMENT REQUIRED. SUPPLY POWER FOR FLOOR FANS AND STOP COOLERS RUN CORDS AND WIRING FROM EACH UNITS TO EXISTING ELECTRICAL PANELS IN HALLWAY. POC: MR. TONY CAMPBELL (202) 576-8045 (NO PENETRATION) CODE A-CLEAR FOR REPAIR BY HORNE ENG. ON 7/27/01 July 27, 2001 February 3, 2006 1,652 days
FM-200115453 01 2/3/06 BALLOU 1) ASBESTOS ASSESSMENT REQUIRED. 2) FLOOR TILES REMOVAL FROM ROOM #105, #150b AND #104b. **REPAIR/REPLACE CEILING RESTORATION FOR DROP CEILING INSTALLATION. ENVIROBATE (IT GROUP) 703-461-6848 CODE A - ASBESTOS ABATED ON 7/22/01(SG) PER LEROY MINTONS CONFIRMATION. Centennial Contractors - Paul McCoy - 202-635-0482 July 20, 2001 February 3, 2006 1,659 days
FM-200113585 01 2/3/06 BALLOU FIRST FLOOR BOYS AND GIRLS RESTROOM 1) RE-INSTALL DOORS DOORS WERE RECENTLY INSTALLED BY CONTRACTOR (EMERGENCY) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 06/19/01. June 19, 2001 February 3, 2006 1,690 days
FM-200113523 01 2/3/06 BALLOU 1ST FL. KITCHEN (EMERGENCY) REPLACE (1) ONE 1" GATE VALVE ON THE HOT WATER SUPPLY LINE THAT SUPPLIES HW TO THE KITCHEN SINKS. NOTE: INHOUSE STAFF CANNOT REPLACE VALVE DUE TO ASBESTOS RESTRICTION ON THE TUNNEL AREA. ASBESTOS ASSESSMENT REQUIRED. Requester Phone: 645-0417 Requestor Phone: 645-0417 ASBESTOS CODE A - CLEAR FOR REPAIR ON 07/20/01. June 8, 2001 February 3, 2006 1,701 days
FM-200111289 01 2/3/06 BALLOU SUB BASEMENT BOYS RESTROOM 1) CEILING IS LEAKING SUSPECT A PIPE BURST CODE A - ASBESTOS ABATED ON 02/14/02 PER RONALD EDWARDS CONFIRMATION.(RG 02/20/02) May 25, 2001 February 3, 2006 1,715 days
FM-200201787 02 2/3/06 BALLOU SUB-BASEMENT BOILER ROOM REPLACE SHAFT BEARING ASSEMBLY FOR THE (ID) INDUCE DRAFT FAN ON BOILER #2. INFO: DRAFT INDUCER SER #D1-15764, SIZE 28 DH-2. January 25, 2002 February 3, 2006 1,470 days
FM-200127187 02 2/3/06 BALLOU ENTIRE 3RD FL ROOMS & CLASSROOMS REPAIR MAIN ELECTRICAL POWER SOURCE TO THE HEATING UNIVENTS. UNIVENTS ARE NOT OPERATIONAL DUE TO POWER-LOSS (NO HEAT) NOTE: EXISTING CIRCUIT BREAKERS SET SCREWS ARE MISSING THRU-OUT PANEL. PANEL BOARD LK SER # V810788 Requester Phone: 698-1750 January 8, 2002 February 3, 2006 1,487 days
FM-200124590 01 2/3/06 (BALLOU) SUB-BASE/ BOILER ROOM UNSTOP FLOOR DRAIN DIRECTLY BEHIND #3 BOILER. NOTE: CONCRETE HAS BEEN DUMPED IN THE DRAIN. December 6, 2001 February 3, 2006 1,520 days
FM-200514783 /05 2/9/06 Ballou Basement-Locker Room/Shower Room Replace lock to shower room to prevent students from gaining access to the tunnel and the girls locker room. October 31, 2005 February 9, 2006 101 days
FM-200617655 06 2/13/06 Need electrician survey and repair electrical outlets in T.V.studio for computers and other equipement for grand opening. January 13, 2006 February 13, 2006 31 days
FM-200617787 06 2/13/06 Repair or Replace electrial work in TV studio to the following 1.Quad box,master control in conference rm.,thermostats. January 19, 2006 February 13, 2006 25 days
FM-200617950 06 2/15/06 First Floor - Auditorium Stage Door and Gym - Replace vertical rod and panic bars. January 27, 2006 February 15, 2006 19 days
FM-200505115 05 2/16/06 Ballou Auditurium Tack Weld Window Gaurd May 4, 2005 February 16, 2006 288 days
FM-200511895 05 2/16/06 Ballou Fire Code Violation B-Broken door in weight room Asbestos Code A - Clear for repairs on 09/07/05. Tidewater - Tony Marcolin (RG 09/07/05) September 6, 2005 February 16, 2006 163 days
FM-200618524 06 2/16/06 Third Floor-Room 301 Repair or replace the door-The door was knock down-Can't Secure the room (Computer equipment). February 9, 2006 February 16, 2006 7 days
FM-200618435 06 2/23/06 Ballou PM Chiller Check equipment and perform PM on equipment. February 8, 2006 February 23, 2006 15 days
FM-200511824 05 2/27/06 Ballou Fire Code Violation Second Floor-Missing fire glass near rm. 208 stairwell September 6, 2005 February 27, 2006 174 days
FM-200511818 05 2/27/06 Ballou Fire Code Violation Third Floor-Missing fire glass in stairwell near rm. 308 September 6, 2005 February 27, 2006 174 days