Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Bancroft Elementary School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200120059 02 2/2/02 (BANCROFT) ASBESTOS ASSESSMENT REQ. BASEMENT/ GYM NEED A DOOR REKEYED. NEED ROOM SECURED. ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/24/01. LEROY MINTON - SAFETY (202)576-6691 (RG) | |||
| FM-200108799 01 2/4/02 BANCROFT PLAYGROUND GIRLS AND BOYS RESTROOM 1) ASBESTOS ASSESSMENT REQUIRED. 2) REPLACE WOODEN DOOR AND INSTALL TWO(2) METAL FIRE DOORS. SAFETY HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/25/01. HORNE ENGINEERING - SHARON VOSS (RG) | |||
| FM-200203063 02 3/21/02 (Bancroft) ****Very Urgent**** 1. Asbestos Assessment Required. Main Entrance/1st Floor: Leak in the cold water supply line; leaking from valves. ASBESTOS CODE A-CLEAR FOR REPAIR NO 2/20/02 HORNE ENGINEER: SHERYLL JAMES | |||
| FM-200203064 02 4/4/02 (Bancroft) ***Very Urgent*** Near Music Room/Boys Bathroom: Five (5) urinals are over-flowing in bathroom, flooding the floors, due to stopped up drain. | |||
| FM-200208077 02 5/22/02 Bancroft ****Urgent**** Basement Boiler Room #4447 The outlet in the basement boiler room sparked, tripped the circuit breaker and the electric power in the room will not come on---needs immediate attention. | |||
| FM-200207555 02 7/15/02 Bancroft 1. Asbestos Assessment Reqd. Top Floor Main Building Room 220 [Counselor's Office] 2. Need a 120V line for air conditioner with 10,000 BTUs. Line installed is for 330V as to-date. Asbestos Code A - Clear for repairs on 05/28/02. DCPS Safety - Richard Gibson (RG 05/28/02) | |||
| FM-200218995 02 1/29/03 (Bancroft) !!!URGENT!!! Primary wing/2nd Floor: No electrical power in this area since friday. Very dark in this area because of no lights. | |||
| FM-200109776 01 3/17/03 BANCROFT GROUNDS - PLAYGROUND EQUIPMENT A. REPLACE MISSING RUBBER PADDING ON PLAYGROUND SURFACE. B. INSTALL SAFETY RAIL ON SAFETY PANEL DECK. C. RODS ON SUSPENSION BRIDGE NEEDS WORK ON. D. DOUBLE WIDE SLIDE ON WEST SIDE EXIT NEEDS MORE PADDING AT END 64 INCHES HIGH. SAFETY HAZARD. | |||
| FM-200227391 03 3/21/03 (Bancroft) !!!VERY URGENT!!! 2nd Floor/Room #123: Roof leaking between slate and classroom, through ceiling. | |||
| FM-200221950 02 3/26/03 Bancroft Boiler Room Replace faulty McDonnell boiler control, model #51 SFHD. This safety device is not seating (closing) and opening properly. | |||
| FM-200227820 03 3/31/03 (Bancroft) !!!VERY URGENT!!! Primary side/2nd Floor: Need lock change on storage rooms in classrooms #313. | |||
| FM-200227842 03 4/1/03 (Bancroft) !!!VERY URGENT!!! Main office Replace door knob lock, unable to secure door properly. | |||
| FM-200227843 03 4/1/03 (Bancroft) !!!VERY URGENT!!! Second floor primary side (room 313) Replace locks because we are unable to open closetdorr due to bar locks / cylinders. | |||
| FM-200227490 03 5/15/03 (Bancroft) !!!VERY URGENT!!! First floor open space (unisex bathroom) Replace flush valve, will not flush and backing up. | |||
| FM-200227491 03 5/15/03 (Bancroft) !!!VERY URGENT!!! First bldg. boys bathroom near auditorium Replace packing behind second urinals. | |||
| FM-200227492 03 5/15/03 (Bancroft) !!!VERY URGENT!!! Second floor girls bathroom Sink needs to be replace due to a child sitting on it. It has become a safety hazard with sharp pipes hanging out. | |||
| FM-200331737 03 6/16/03 Bancroft Primary third floor room 322 Install lock and cylinder and also hole for safety glass. | |||
| FM-200331942 03 6/18/03 Bancroft Third floor 322 primary Install lock and cylinder, hole for safety glass. | |||
| FM-200337217 03 9/26/03 Bancroft Boiler Room A hydrostatic test is needed on boiler #1. This was requested by the D.C. Boiler Inspector. Code A - clear for repairs as of 9/24/03 by Sylvia Grimes DCPS safety. | |||
| FM-200338363 03 10/1/03 (Bancroft) !!!VERY URGENT!!! Open Space/Small Students Area: Sparks coming from outlet. Staff is unable to use outlet, as all power shuts down when in use. (Please send electrical, as we are very concerned with sparks) | |||
| FM-200228205 03 2/6/04 Bancroft Open space area Electrical problem with the exit lights. Will not come on five of them. The cause is unknown. Call management service because of safety and do not have the right tools to do the job. | |||
| FM-200446840 04 6/4/04 (Bancroft) !!!VERY URGENT!!! Outside/Upper Playground: Spigot attached to wall running water profusely. | |||
| FM-200449224 04 6/15/04 Bancroft First floor girls bathroom (main bldg.) Stopped up and may need to be snaked out or even replaced. (toilet)Re-attach partition railing. Sharp edge may cause someone to get hurt. | |||
| FM-200453790 04 9/10/04 Bancroft Ground floor cafeteria Replace wall receptable, surging with electrical sparks. Asbestos Code A - Clear for repairs on 09/01/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200454812 04 9/16/04 (Bancroft EMERGENCY First floor boys bathroom The partition fell on a student (Jose Guzman). Need to be repair/ replace. Asbestos Code A - Clear for repairs on 09/15/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200456278 04 12/7/04 Bancroft URGENT Third Floor Primary wing Replace stop valve and flush valve assembly. Water will not stop running. | |||
| FM-200456275 04 12/7/04 Bancroft URGENT Second Floor Primary wing Replace stop valve and flush valve assembly. Water will not stop running. | |||
| FM-200456273 04 12/7/04 Bancroft URGENT First Floor Primary wing Replace stop valve on toilet and sloan assembly. | |||
| FM-200457676 /04 1/6/05 Bancroft First floor music room (main bldg) Re-attach window guard falling to ground. Asbestos Code A - Clear for repairs on 10/29/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200501075 05 3/2/05 Bancroft Main Building/girls Restroom Replacee faucets . no running water. Asbestos Code A - Clear for repairs on 02/01/05. DCPS Safety - Leroy Minton (RG 02/01/05) 02/01/2005 11:06 OB - | |||
| FM-200450992 04 3/16/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 3rd Floor/Room 312: Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450991 04 3/16/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 3rd Floor/Room #311: Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450990 04 3/16/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 3rd Floor/Room #310: Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200502933 05 3/30/05 Bancroft EMERGENCY Cafeteria Replace table, broken legs and a safety hazard. | |||
| FM-200502570 05 3/31/05 (Bancroft) "Urgent" First floor/Main bldg./Auditorium Repair or Replace wall sockets , they have sparks flying from them. | |||
| FM-200503374 05 3/31/05 (Bancroft) "Urgent" Openspace. Repair or Replace wall receptacle sparking very badly, may catch on fire. | |||
| FM-200450981 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Room #8: Door not working properly. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451337 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Level Open Space 1) Exit door in disrepair coming from Art Room. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451026 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. Learning Center: 1) Exit doors in disrepair , rear Learning Center. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451007 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. Door to Room #210: Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451006 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 1st Floor/Leading to Parking Lot Exit door near music room in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451005 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 1st Floor/18th Street Side: Exit door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451002 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor: Door hardware in dis-repair to art room. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451001 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Level Open Space 1) Door leading to parking lot does not positively latch. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451000 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 4 exit doors 1st Level/Open Space: Area needs hardware. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450988 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. Breach in floor, rear room #111. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450983 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Computer Room: Breach in wall, rear of computer room. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450976 04 4/5/05 (Bancroft) FIRE CODE VIOLATION: 2nd Floor/Stairwell: Door across from room #202 needs hardware frame. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450985 04 5/4/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Computer Room: Damaged floor. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450979 04 6/7/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Room #6: Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200456992 /04 8/1/05 Bancroft First floor auditorium (outside) Replace / Repair exterior light, it is very dark, and vandals are beginning to vandalize the building. Asbestos Code A - Clear for repairs on 10/18/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200507376 05 9/19/05 URGENT!!!!! First Floor - Girl's Restroom (Yellow Floor Near Room 110) Re-attach the sink to the wall, Unable to secure the sink, water has begun to leak on the floor. | |||
| FM-200503973 05 9/19/05 ( BANCROFT ) Outside Playground 1) Re-attach drain pipe extension near boiler room and auditorium. Asbestos Code A - Clear for repairs on 04/19/05. DCPS Safety - Leory Minton Jr.(RG 04/19/05) | |||
| FM-200226868 03 9/19/05 (Bancroft) !!!URGENT!!! 2nd Floor/Girls restroom: Sink was removed from wall for other repairs; supply lines, and sharpe objects exposed. Please replace sink. Asbestos Code A - Clear for repairs on 03/12/03. Hone Engineering - Bipin Nanavaty (RG 03/13/03) | |||
| FM-200506665 05 9/19/05 (BANCROFT) URGENT!!!! Third Floor - Boys Restroom (Main Building) 1) Replace leaking handle flush valve, water keeps running. | |||
| FM-200506666 05 9/20/05 (BANCROFT) URGENT!!!! First Floor - Girls Restroom (Main Building) 1) Repair leaking flush valve assembly on two toilets. | |||
| FM-200506204 05 9/20/05 ( BANCROFT ) URGENT!!!! First Floor - Girls Restroom (main bldg.) 1) Repair leaking flush valve assembly on two toilets. | |||
| FM-200341250 03 9/20/05 Bancroft Ground floor cafeteria / kitchen Repair / Replace trap on procelain sink water dripping constantly. Repair / replace leaking trap on hot water line. Extremely hot and dangerous. | |||
| FM-200507415 05 9/22/05 VERY URGENT!!! Outside Front of Building, Newton ST. Side Near Auditorium Replace spigot, it's leaking very badly, and is water coming through the wall. Asbestos Code A - Clear for repairs on 07/05/05. DCPS Safety - Richard Gibson (RG) | |||
| FM-200500022 05 10/3/05 Bancroft Main office Window fell on custodians hand, resulting in a broken finger. Window need to be replaced. See linked documents for additonal information on employee injury. | |||
| FM-200507387 05 10/3/05 URGENT!!! First Floor - Hallway Exit Door (Near Room 110) Replace door closure, door is slamming and may hurt someone. Code A-clear for repair by DCPS charles Buchanan on 7/05/05 | |||
| FM-200506669 05 10/3/05 (BANCROFT) URGENT!!!! First Floor - Hallway (Main Building) Exit Door 1) Change door closure, hanging off and causing the door to slam. | |||
| FM-200506667 05 10/3/05 (BANCROFT) URGENT!!!! Outside Playground (Open Space) 1) Door is hanging off and may hurt somebody. Code A-clear for repair by DCPS Charles Buchanan on 6/13/05 | |||
| FM-200459708 /04 10/3/05 BANCROFT EXIT DOOR NEAR MUSIC RM. REPAIR OR REPLACE Asbestos Code A - Clear for repairs on 12/22/04. DCPS Safety - Leroy Minton Jr. (RG 12/22/04) | |||
| FM-200503354 05 10/3/05 Bancroft Library 1) Repair or Replace 30 - 40 light fextures, very dim lighting. Asbestos Code A - Clear for repairs on 04/21/05. DCPS Safety - Leroy Minton Jr. (RG 04/21/05) | |||
| FM-200506206 05 10/3/05 ( BANCROFT ) URGENT!!!! Third Floor - Boys Restroom 1) Repair leaking handle flush valve assembly. | |||
| FM-200459725 /04 10/28/05 BANCROFT First Fl. Art room 110 Replace 8" deck-mounted kitchen faucet. Asbestos Code A - Clear for repairs on 12/22/04. DCPS Safety - Leroy Minton Jr. (RG 12/22/04) | |||
| FM-200450998 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: 3rd Floor/Leading to Open Space: Hole in ceiling near door. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451010 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 1st Floor/Leading to Primary Wing: Hole in wall at 2nd Floor Entrance. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450977 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: 2nd Floor/Across from Room #5: Breaches in wall. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451008 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 1st Floor/Adjacent to Music Room: Breaches in wall. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200451009 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 2nd Floor/Next to Room #9: Hole in wall. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450993 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. 3rd Floor: Hole in ceiling by doors leading to open space. Door in dis-repair. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200450989 04 12/27/05 (Bancroft) FIRE CODE VIOLATION: Asbestos Assessment Required. Loose cord around door, room #210. Asbestos Code A - Clear for repairs on 08/18/04. DCPS Safety - Leroy Minton Jr. (RG 08/19/04) | |||
| FM-200617402 06 2/13/06 Very Urgent: Replace the light fixtures in the main hallway near the office on the first floor. | |||
| FM-200513906 /05 3/6/06 Bancroft Very Urgent Second Floor-Primary Wing (Rm. 313) Replace spud/tail pipe on toilet unable to remove nut. | |||
| FM-200514792 /05 3/6/06 Bancroft Urgent Repair back gate behind the library, unable to close and lock. | |||
| FM-200618704 06 3/6/06 Very Urgent Exterior Library Window Attempted break-in - Replace Plexiglas, there is a hole in it and it's cracked | |||
| FM-200331551 03 3/6/06 (Bancroft) !!!EMERGENCY!!! Balance all windows; unable to open all windows. A student was injured. | |||
| FM-200228626 03 3/6/06 (Bancroft) Asbestos Assessment Required. Basement/Cafeteria: Replace damage ceiling tile with 12" X 12" . cafeteria. (Emergency) Asbestos Code A, clear for repairs on 4/11/03 DCPS Safety R. Edwards Abatement contractors perform emergency clean-up of debris from fallen 12"x12" acoustical ceiling tile. Completed 4/11/03. | |||
| FM-200228557 03 3/6/06 (Bancroft) !!!VERY VERY URGENT!!! 3rd Floor/Room #120 & #121: Ceiling attempting to collapse, !!!NOW!!! Asbestos Code A - Clear for repairs on 04/10/03. Horne Engineering - Roger Kager (RG 04/11/03) | |||
| FM-200618309 06 3/6/06 Very Urgent: First Floor-Principals' Office. Repair the window that is beginning to fall off the hinges. | |||
| FM-200220673 /02 3/6/06 Bancroft Second floor - Rooms 120 and 122 Replace floor, Wood sub floor has badly deteriorated. Asbestos Code A - Clear for repairs on 04/16/03. (Do not distrub floor - repair by filling it in) DCPS Safety - Dr.Saeed Rahimi\Richard Gibson (RG 04/17/03) | |||
| FM-200220970 /02 3/6/06 Bancroft Cafeteria The cafeteria back room plaster is falling from ceiling. It is a safety and health violation for the children eating in there. "EMERGENCY" Asbestos Code A- clear for repairs as of 11/18/02 by Horne Engineers Edward Rodriquez. | |||
| FM-200617409 06 3/6/06 Very Urgent: First Floor-Open Space (Girls Restroom) Replace the toilet assembly, water backing up causing a flood. | |||
| FM-200516557 /05 3/6/06 Bancroft Room #301 Repair or replace motor in univent motor going bad. No access to information on motor (upside down) Urgent !!!!! | |||
| FM-200516664 /05 3/6/06 Urgent: Repair or replace the doors to classroom 223 on the top floor (main bldg.), it's hanging off the hinges. Asbestos Code A - Clear for repairs on 12/20/05. Tidewater - Thomas Johnson (RG 12/21/05) | |||
| FM-200227489 03 3/6/06 (Bancroft) !!!VERY URGENT!!! 322 Primary side Replace door handing off by hinge, endangering children/staff. Asbestos Code A - Clear for repairs on 03/24/03. Horne Engineering - Sheryll James (RG 03/25/03) | |||
| FM-200227487 03 3/6/06 (Bancroft) !!!VERY URGENT!!! Library (open space) Skylight needs to be sealed or replaced due to an extreme amount of water. Carpet is bulging because of water coming in. | |||
| FM-200227486 03 3/6/06 (Bancroft) !!!VERY URGENT!!! First floor -120 main bldg. Roof leaking onto flourescent light fixture. | |||
| FM-200516970 /05 3/6/06 Urgent: Ground Floor-Cafeteria Replace faucet on porcelain sink, water will not stop running. | |||
| FM-200619211 06 3/6/06 Very Urgent Third Floor-Teacher's Lounge (primary wing) No Hot Water In Hand Sink | |||
| FM-200619205 06 3/6/06 Very Urgent Second Floor-Main Bldg. (Near Room 222) Replace circuit breaker 10-12 in the panel box | |||
| FM-200456393 04 3/6/06 Bancroft Second floor open Space (boiler room) Replace circuit breaker # 5 , causing exterior lights not to come on. Asbestos Code A - Clear for repairrs on 10/04/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200512059 05 3/6/06 (Bancroft) "Emergency" Asbestos Assessment Required. Second floor, 124 Main bldg. Repair window that fell down from the top in danger of falling. Asbestos Code A - Clear for repairs on 09/09/05. Tidewater - Rodney Distance (RG 09/13/05) | |||
| FM-200512061 05 3/6/06 (Bancroft) "Emergency" Asbestos Assessment Required. Second floor, 124 Main bldg. Furnish and install safety glass in previously installed doors. Asbestos Code A - Clear for repairs on 09/09/05. Tidewater - Rodney Distance (RG 09/13/05) | |||
| FM-200512990 05 3/6/06 Bancroft Very Urgent Outside Playground (open space) Door is hanging off and may hurt somebody Asbestos Code A - Clear for repairs on 09/22/05. Tidewater - Tony Marcolin (RG 09/23/05) | |||
| FM-200455592 04 3/6/06 Bancroft Boiler room (overtop of open space) Replace circuit breaker # 5 that controls out side lights. Asbestos Code A - Clear for repairs on 09/24/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200511600 05 3/6/06 Bancroft Roof By Main Office Repair or replace cooling unit, servicing main office. Unit isn't cooling properly. Engineer has clean coils with negative results. Urgent !!!! | |||
| FM-200455591 04 3/6/06 Bancroft First floor room 210 (main bldg.) A/C unit keep on tripping circuit breaker, causing unit not to function. Asbestos Code A - Clear for repairs on 09/24/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200223415 /02 3/6/06 (Bancroft) INSTALLATION OF SINK IN CAFETERIA. Code A - Safety Saeed Rahimi (RG 04/23/03) | |||
| FM-200503393 05 3/6/06 (Bancroft) Repair or Replace door closer, the door is closing extremely fast . Note: Safety Hazzard. | |||
| FM-200458904 04 3/6/06 Bancroft Basement boiler room Replace electrical switch, fire sparking from socket. Please fix or either provide light switches. Asbestos Code A - Clear for repairs on 12/01/04. DCPS Safety - Richard Gibson (RG 12/01/04) | |||
| FM-200513780 /05 3/6/06 Bancroft Very Urgent Second Floor-Rm. 120 Main Bldg. Replace wall switch that controls the A/C unit. | |||
| FM-200506010 05 3/6/06 ( BANCROFT ) Main Office, Principals Office and Counselors Office 1) Asbestos Abatement of 9x9 in. floor tile, mastic and substrate leveling compound; carpet disposal. Replace with 12x12 in. vinyl floor tiles. Asbestos Code A - Abated and cleared for repairs on 03/05/06 per Goel confirmation (LM-09/29/06) Safety Office 202-576-8962. | |||
| FM-200459550 /04 3/6/06 Bancroft Steam Side of Building Replace approximately 100 faulty steam control valve and steam traps each. To radiators throughout steam side of Building. Current temperture control valves will not shutt off, causing steam side of building to get to hot. Urgent !!!!! | |||
| FM-200515149 05 4/14/06 Urgent: First Floor-Main Bldg. (next to counselors office): Repair steps where concrete has been missing (trip hazard) | |||
| FM-200513907 /05 6/2/06 Bancroft Urgent Outside Playground-Re-attach screws/bolts on swing equipment. | |||
| FM-200513908 /05 6/13/06 Bancroft Urgent Cafeteria (main bldg.) Repair water cooler due to compressor problem. | |||
| FM-200515198 05 6/13/06 Urgent: Re-attach faucets in the Main Office Bathroom on the First Floor. It turns 360 degrees around and is leaking water around supply line. | |||
| FM-200501056 05 6/13/06 Bancroft Main Building/Boy's Restroom Remount Urinal to wall. Asbestos Code A - Clear for repairs on 02/01/05. DCPS Safety - Leroy Minton (RG 02/01/05) | |||
| FM-200514793 /05 6/14/06 Bancroft Urgent Second Floor-(primary wing) Rm. 313 Replace spud/tail pipe on toilet; unable to remove nut. | |||
| FM-200625697 06 9/11/06 Bancroft Mechanical Room Asbestos assessment required Correct flow problem to air handler unit. Possible stoppage. Also replace supply and return valves. Urgent !!!!! Valves are approx. 2" Asbestos Code A - Clear for Repairs on 07/17/06. Tidewater - Shamika Parker (RG 07/21/06) | |||
| FM-200630881 /06 11/30/06 Interior wall in boys' restroom. Repair masonry wall so that sink can be reattached to to wall. Note: The students are unable to wash their hands. Asbestos Code A - Clear for repairs on 10/17/06. DCPS Safety - Richard Gibson (RG 10/17/06) | |||
| FM-200621329 06 1/4/07 First Floor-Hallway (primary wing)-Replace fire doors or replace wire mesh safety glass Asbestos Code A - Clear for repairs on 04/18/06. Tidewater - Thomas Johnson (RG 04/20/06) | |||
| FM-200630441 06 1/11/07 Girls Restroom- Replace partition door. Asbestos Code A - Clear for repairs on 10/04/06 DCPS Safety - Richard Gibson (RG) | |||
| FM-200513782 /05 1/16/07 Bancroft Very Urgent Ground Floor-Stairwell Leading To The First By Cafeteria Repair/Replace window guard, the latch is broken | |||
| FM-200331657 03 1/16/07 Bancroft !! URGENT !! First Floor - Classroom 1. Repair and or replace window in classroom #121- located in the 1921 orginal bldg . Asbestos Code A - Clear for repairs on 06/12/03 Horne Engeering - Philp Connolly (RG 06/16/03) | |||
| FM-200630951 /06 1/16/07 First Floor - Girl's Bathroom (main bldg.) - Re-attach sink to the wall #3, sharp edges a child may get hurt. Asbestos Code A - Clear for repairs on 10/20/06. Tidewater - Kenneth Belton (RG 10/24/06) | |||
| FM-200617827 06 1/16/07 Urgent: Second Floor-Rm. 310 (primary wing) Replace 2-3 ballast because the lights have a shortage in them | |||
| FM-200449242 04 1/16/07 Bancroft Basement music room bathroom First and third floor boys bathroom (main bldg) Replace 1 paper towel dispenser. Replace 1 toilet paper dispenser.(music room) Replace 2 broken toilet paper dispenser ( boys bathroom main bldg). Asbestos Code A - Clear for repairs on 06/14/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200618367 06 1/16/07 First Floor-Principals' Office Urgent Secure window from the top and the bottom; jammed and cannot be properly closed. Asbestos Code A - Clear for repairs on 02/08/06. Tidewater - Carlos Vera (RG 02/09/06) | |||
| FM-200446604 04 2/2/07 Bancroft Open Space Electric Boiler Room Replace leaking 3" normally open pneumatic control valve. A thirty-two gallon trash can has to be emptyed of water daily. Valve is on main line coming to boiler. P.S. Bobby Davis recommended that it be replace. Urgent!!!! | |||
| FM-200631101 /06 2/23/07 Bancroft Mechanical Room (Open Space) Correct problem that preventing heating water from flowing through pneumatic valves to heating this section of building. Urgent !!! | |||
| FM-200516337 /05 2/23/07 Bancroft Room #303 Repair or replace univent in room #303. Room is cold. Engineer has trouble shoot and still unit not heating. Urgent !!!! |