Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Orr Elementary School
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200119477 01 10/2/01 (ORR) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ CUSTODIAN CLOSET UNSTOP DRAIN IN CUSTODIAN CLOSET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/13/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) | |||
| FM-200119479 01 10/2/01 (ORR) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ BOYS TOILET REHANG SINK IN BOYS TOILET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/13/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) | |||
| FM-200119478 01 10/30/01 (ORR) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ TEACHERS TOILET REALIGN TEACHERS BATHROOM DOOR. IT WONT CLOSE PROPERLY. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/13/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) | |||
| FM-200119476 01 12/10/01 (ORR) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ ALL PURPOSE ROOM CHECK CIRCUT BREAKER ON STAGE FOR LIGHTING IN ALL PURPOSE ROOM. THREE (3) ROWS OF LIGHTS ARE OUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/13/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) | |||
| FM-200126463 /01 1/3/02 ORR SCHOOL ASBESTOS ASSESTMENT REQUIRED BOILER ROOM REPLACE 2 INCH LEAKING TUBES IN NUMBER ONE BOILER CODE A- CLEAR FOR REPAIR BY HORNE ENGINEERING BY EDWARD RODRIGUEZ 12-31-01 (S.R. HOWARD- DCPS SAFETY12-31-01. | |||
| FM-200206850 02 4/30/02 4th Floor Reading Room Rehang window in 4th floor reading room. The window is off-track and could fall out at any time, possibly causing injury. | |||
| FM-200220117 /02 10/29/02 (Orr) !!!VERY URGENT!!! 1. Asbestos assessment required. Ground Floor/Main entrance doors: Due to break-in, door needs alignment, and door jamb repaired. Asbestos Code A - Clear for repairs on 10/28/02. Horne Engineering - Donald Maglienti (RG 10/28/02) | |||
| FM-200214653 02 3/12/03 Orr F-110.1 Fire Code Violation 1. Asbestos Assessment Reqd. 1st Floor Lobby Replace ceiling tiles in the front lobby. Asbestos Code A - Clear for repairs on 08/19/02. DCPS Safety - Leroy Minton Jr (RG 08/19/02) | |||
| FM-200220737 /02 3/21/03 (Orr) !!!VERY URGENT!!! 1. Asbestos assessment required. Main entrance / Front entry doors Doors are rotted out. Also, repair or replace silde bolts. Unable to secure door without slide bolt. Asbestos Code A - Clear for repairs on 10/28/02. Horne Engineering - Donald Maglienti (RG 10/28/02) | |||
| FM-200218808 02 3/26/03 Orr E.S Boiler Room Start up burners and test safety controls on specified boilers. | |||
| FM-200223731 03 3/26/03 ORR boiler room "URGENT" "NO HEAT THE ONLY ONE OF TWO BOILERS OPERATE" Resolve problem with boiler # 2 will not start out on flame failure. | |||
| FM-200110103 01 5/5/03 ORR REPAIR OR REPLACE PLAYGROUND EQUIPMENT. THERE ARE JAGGED EDGES AND MISSING PARTS. IT IS A SAFETY HAZARD. | |||
| FM-200329333 03 5/5/03 (Orr) !!!URGENT!!! 1st Floor/Cafeteria: Door was not secure through the night. Panic bar broken on door, unable to secure. | |||
| FM-200124234 /01 5/5/03 (ORR) GROUNDS/PLAYGROUND REGLUE SAFETY PADDING FOR PLAYGROUND EQUIPMENT | |||
| FM-200110927 01 5/5/03 ORR PLAYGROUND 1) REGLUE SAFETY PADDING FOR PLAYGROUND EQUIPMENT | |||
| FM-200329402 03 5/8/03 ORR boiler room EMERGENCY SAFETY HEALTH Problem Replace existing exhaust pipe on generator with 40 - 50 ft of additional piping to directing fumes away from inside of school. Or relocated existing generator to outside location. | |||
| FM-200225806 03 6/5/03 (Orr) !!!VERY URGENT!!! Cafeteria: Sparks and smoke coming from an electrical outlet; outlet is broken, and electrical wires are exposed. | |||
| FM-200213471 02 3/2/04 (Orr) ***Very Urgent*** 1. Asbestos assessment required. 4th Floor orange stairs/Learning center door: A hole was cut in the cage leading to the roof. Asbestos Code A - Clear for repairs on 08/05/02. DCPS Safety - Leroy Minton Jr. (RG 08/06/02) | |||
| FM-200335287 03 4/19/04 Orr F-519.0 FIRE CODE VIOLATION First floor Safety glass broken green side. | |||
| FM-200451148 04 8/11/04 Change the Computer Lab door locks. New equipment purchased, but too many keys exits and security of computers are in jeopardy of being stolen. Request change of door locks. Urgent due to the money value of computers. | |||
| FM-200451147 04 8/12/04 Need key for the wall Amplifier in auditorium stage replaced. The initial lock was loss. Cannot use auditorium system. Critical for opening school. Without this repair, school opening will be hampered. Thanks Asbestos Code A - Clear for repairs on 08/11/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200451670 04 10/13/04 Orr FIRE CODE First floor Entension cord used as permanent wiring (cafeteria) 2000 IFC 605.5 Code A - clear for repairs as of 8/24/04 safety Sylvia. | |||
| FM-200451665 04 10/13/04 Orr FIRE CODE First floor Entension cord used as permanent wiring (boys and girls club office) 2000 IFC 605.5 Code A - clear for repairs as of 8/24/04 safety Sylvia. | |||
| FM-200451672 04 4/5/05 Orr FIRE CODE First floor Broken door (exit) (main front door) 2000 IFC 110.1.1 Code A -clear for repairs as of 8/24/04 safety Sylvia. | |||
| FM-200451673 04 4/5/05 Orr FIRE CODE First floor Unsafe condition w/door (main front door) 2000 IFC 110.3 Code A -clear for repairs as of 8/24/04 safety Sylvia. | |||
| FM-200450517 04 10/19/05 Orr URGENT Lunchroom Six tables broken, principal request that they be remove. | |||
| FM-200450516 04 10/19/05 Orr URGENT Third floor exit door Exit door on the orage stairway is not locking properly. | |||
| FM-200450438 04 10/19/05 (Orr) !!!URGENT!!! Asbestos Assessment Required. Exit door does not work. This could be a safety hazard. Please correct and repair as soon as possible. Asbestos Code A - Clear for repairs on 07/20/04. DCPS Safety - Leroy Minton Jr. (RG 07/20/04) | |||
| FM-200209606 02 10/19/05 Orr ****Very Urgent**** Roof Area Over Front Lobby Area Roof drain needs to be checked for blockage----water is coming through the ceiling into the front lobby area at the entrance, especially when there is rain. [Roof drain was cleared, however water still coming through when it rains. Ceiling tile holding moisture and appear ready to fall--severely sagging.] | |||
| FM-200452680 04 10/19/05 Safety Hazard. Several of the ceiling tiles in the multipurpose room need to be replaced. Children utilize the space constantly. Asbestos Code A - Clear for repairs on 08/16/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200206844 02 10/19/05 1. Asbestos Assessment Reqd. 1st Floor All-Purpose Room 2. Readjust ceiling tiles in the all-purpose room [10 ceiling tiles need to be replaced]. Asbestos Code A - Clear for repairs on 04/30/02. DCPS Safety - Leroy Minton Jr. (RG 04/30/02) | |||
| FM-200454929 04 10/19/05 (Orr) Electrical problem in four computer lab rooms which causes teachers to be electrically shocked when using computers. SAFETY HAZARD FOR STUDENTS AND STAFF. SEE MS. PHILLIPS, COMPUTER TEACHER, FOR DETAILS. Rooms of Cruz, Bouser, Hurlbert, and Jefferson. URGENT MATTER. | |||
| FM-200451654 04 12/27/05 Orr FIRE CODE Fourth floor Electrical panel inaccessible (Storage room rear) 2000 IFC 605.6 Code A - clear for repairs as of 8/24/04 safety Sylvia. | |||
| FM-200111646 01 2/3/06 ORR FIRST FLOOR ROOM 12 AND HEALTH SUITE 1) REPAIR LEAK IN CEILING IN BUSINESS MANAGERS OFFICE IN LIGHT FIXTURE 2) REPAIR LEAK IN HEALTH SUITE CEILING ASBESTOS CODE A - CLEARED FOR REPAIRS ON 07-31-01. LEROY MINTON JR SAFETY OFFICE ( 202-576-8962 ) SAME AS WO# 200106950, LEAK CORRECTED | |||
| FM-200124239 /01 2/3/06 (ORR) ASBESTOS ASSESSMENT REQUIRED 2ND & 4TH FLOORS REPLACE DOOR KNOBS ON STAIRWELL DOORS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/11/01 RONALD EDWARDS - SAFETY (202)576-6691 | |||
| FM-200443183 04 2/8/06 Orr Urgent!!! Second Floor - Green Stairwell 1) Repair broken handrail, bolts are out and the peice is on Custodian Foremans desk. Wall is cinder block. | |||
| FM-200620007 06 5/13/06 Very Urgent First Floor-Multi Purpose Rm. Need a cherry picker to put bulbs in, the ceiling is too high-there is about 36 light fixtures out and about 4 to each light fixture. | |||
| FM-200516453 /05 8/11/06 Orr Boiler Room Repair or replace domestic hot water heater. Polit lite continously going out. No Hot Water in Building. Urgent !!!!! | |||
| FM-200624846 06 8/18/06 Orr Chiller Check and repair chiller, low refrig. pressure and check cooling fan controls. Summer School site. Urgent !!!! | |||
| FM-200228590 03 12/26/06 ORR First Floor - Cafeteria 1. Repair hole in cinder block wall . Asbestos Code A - Clear for repairs on 03/10/03. DCPS Safety - Richard Gibson (RG) | |||
| FM-200213468 02 1/17/07 (Orr) 1. Asbestos assessment required. 1st Floor Gym/Multipurpose room: Light fixture damaged. Asbestos Code A - Clear for repairs on 08/05/02. DCPS Safety - Leroy Minton Jr. (RG 08/06/02) | |||
| FM-200516456 /05 1/17/07 Urgent: Start the hot water heater in the boiler room on the first floor. | |||
| FM-200516454 /05 2/9/07 Orr Boiler Room Repair or replace air handle unit that services the Multi purpose area. Bad motoer. No Heat in Area. Urgent !!!!! | |||
| FM-200450862 04 2/13/07 Orr 20 ceiling tiles need replacement in cafeteria, it is a fire code violation. Asbestos Code A - Clear for repairs on 07/28/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200450515 04 2/13/07 Orr URGENT First floor front entrance door Not closing properly, children are coming in. Asbestos Code A - Clear for repairs on 07/20/04. DCPS Safety - Richard Gibson (RG) |