Urgent Closed Repair Requests
See Also: All Closed Repair Requests at Park View ES
Detailed Reports
| Description | Open Date | Close Date | Time Elapsed |
|---|---|---|---|
| FM-200117551 01 9/10/01 PARK VIEW EXTERIOR GROUNDS NEAR GYM ASBESTOS ASSESSMENT REQUIRED DRAIN NEEDS TO BE SNAKED / UNSTOP TH DRAIN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/16/01. SYLVIA GRIMES - SAFETY (202)576-5583 | |||
| FM-200118773 01 9/27/01 (PARKVIEW) BASEMENT/ CORRIDOR !!!!!!!!!URGENT!!!!!!!!!! CHECK LIVE ELECTRICAL WIRE INSIDE WALL OPENING NEAR STEAM PIPE. AREA PREVIOUSLY CODE A FOR REPAIRS. NEED WIRE EITHER CONNECTED OR CAPPED IN ORDER TO CLOSE WALL. | |||
| FM-200122294 /01 12/5/01 (PARKVIEW) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ SOUTHWEST-CORRIDOR DRINKING COOLER NEEDS TO BE FIXED ITS LEAKING WATER. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/30/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) | |||
| FM-200124691 /01 12/19/01 (PARK VIEW) **EMERGENCY** 2ND FLOOR/ROOM 223 &231 (COMPUTER ROOMS) LOCKS NOT ENGAGING AND DOORS IN BOTH ROOMS OPEN EASILY WHEN KNOB IS OR DOORS ARE PUSHED FROM OUTSIDE. SCHOOL ALREADY SUFFERING THEFTS FROM BOTH COMPUTER ROOMS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/07/01. RICHARD GIBSON - SAFETY (202)576-5584 (RG) | |||
| FM-200125768 /01 1/8/02 (PARK VIEW) ***EMERGENCY*** BASEMENT/AUDITORIUM STAGE LIGHTS WILL NOT COME ON (THERE HAS BEEN ASBESTOS ABATEMENT GOING ON IN THE BOILER ROOM & PERHAPS SOMEONE TOUCHED A SWITCH OR SOMETHING). WE NEED THE ELECTRICIAN TO CHECK THE PROBLEM & GET THE LIGHTS ON IN TIME FOR TOMORROWS XMAS PROGRAM SO WE CAN AVOID SAFETY ISSUES. | |||
| FM-200123941 /01 1/28/02 (PARK VIEW) ASBESTOS ASSESSMENT REQUIRED GROUND, RM 005/HEADSTART CLASSROOM REPAIR CLASSROOM DOOR, JAMS UP AND IS HARD TO OPEN. CREATES A SAFETY HAZARD. ASBESTOS CODE A-CLEAR FOR REPAIR 12/04/01 BY HORNE ENGINEER: SAM EBRAHIM | |||
| FM-200202699 02 2/14/02 PARKVIEW !!!! EMERGENCY !!!! EXIST DOOR TO LUNCH ROOM THE CYLINDER IS NOT LOCKING THE DOOR PROPERLY AND IT LOSE. DOOR CANNOT BE SECURE TO LOCK. SAFETY HAZARD. | |||
| FM-200126879 02 2/20/02 (PARKVIEW) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ PRINCIPALS OFFICE !! URGENT !! DOOR NEEDS TO BE REPAIRED OR REPLACED. PRINCIPALS THINGS NEED TO BE SECURED. ASBESTOS CODE A-CLEAR CLEAR FOR REPAIR ON 1/07/02 BY SAM EBRAHIM | |||
| FM-200204324 02 3/22/02 (Parkview) ***Very Urgent*** 2nd floor/Through-out the building: Shortage in panel box circuit breakers, affecting rooms through-out the building. | |||
| FM-200204355 02 3/27/02 Parkview !!!! Emergency !!!! Classroom #228 Closet ceiling water leaking from the roof. Ceiling tiles are falling down. Safety Hazard. Code A-clear for repair by Horne Egineer on ( Troy Wilcome ) 3/14/02 (CEB) | |||
| FM-200207614 02 5/20/02 (Parkview) Fire code violation: Page 1 of 1 Room #227: Defective lock on door. Instructed to change trade to locksmith. Asbestos Code A - Clear for repairs on 05/14/02. DCPS Safety - Ronald Edwards (RG 05/15/02) | |||
| FM-200207627 02 5/22/02 (Parkview) Fire code violation: Page 1 of 1 1. Asbestos assessment required. Ground Floor/Music Room: Music room door needs to be checked. Asbestos Code A - Clear for repairs on 05/14/02. DCPS Safety - Ronald Edwards (RG 05/15/02) | |||
| FM-200207621 02 5/22/02 (Parkview) Fire code violation: Page 1 of 1 1. Asbestos assessment required. 2nd Floor/next to room #236: Exit door not closing properly next to room #236. Asbestos Code A - Clear for repairs on 05/14/02. DCPS Safety - Ronald Edwards (RG 05/15/02) | |||
| FM-200207617 02 5/23/02 (Parkview) Fire code violation: Page 1 of 1 1. Asbestos assessment required. Panic hardware broken on door in the exibit hall. Asbestos Code A - Clear for repairs on 05/14/02. DCPS Safety - Ronald Edwards (RG 05/15/02) | |||
| FM-200207618 02 6/5/02 (Parkview) Fire code violation: Page 1 of 1 1. Asbestos assessment required. Door closure broken on room #226. Asbestos Code A - Clear for repairs on 05/14/02. DCPS Safety - Ronald Edwards (RG 05/15/02) | |||
| FM-200221707 /02 11/26/02 (Parkview) !!!VERY URGENT!!! 1st Floor/Across from room #113: Girls bathroom stopped up and flooding the floors, engineers and staff are mopping up the water. This is a continuation of a previous problem. Also, the trap needs to be replaced on the sink in the Headstart room. | |||
| FM-200220113 /02 11/27/02 Parkview Hallway Rear Exit Door Above Cafeteria Exploratory Demo AMP - Ground Floor - Corridor 1 and 2 1. Asbestos assessment required. Repair/Replace steam leak pipe in the ceiling 3"inch black iron pipe. "Ceiling and wall is plastered and also tiled " Asbestos Code A - Abated and cleared for repairs on 11-01-02 (LM/11-19-02) per Leroy Minton confirmation. Safety Office 202-576-8962. | |||
| FM-200225146 03 2/6/03 "URGENT" Parkview Boiler Room Pump out flooded boilerroom | |||
| FM-200227243 03 3/18/03 (Parkview) !!!VERY URGENT!!! Across from Kindergarten: Water pouring out of slop sink, flooding the floors. | |||
| FM-200219451 /02 5/5/03 Park View Trintree on Otis Place side of the building, to allow more sun light. Which will elliminate accumilating mold on the building and to help stop pigeons/birds from landing on the building and leaving bird droppings on the building and causing a health and safety hazard. | |||
| FM-200101790 22/01 5/5/03 PARKVIEW GROUNDS REPLACE TWELVE FOOT BRIDGE ON PLAYGROUND AREA (METAL WITH PLASTIC COATING) NOTE: ORIGINAL BRIDGE WAS BROKEN AND WAS REMOVED FOR SAFETY. | |||
| FM-200331609 03 7/15/03 (Parkview) !!!VERY URGENT!!! 2nd Floor/Hallway: Electrical panel box has bad breaker, affecting all lights in that area. | |||
| FM-200336303 03 9/4/03 (Parkview) !!!VERY URGENT!!! 1st Floor/Outside Cafeteria: Electrical wiring exposed; children possible injured while walking to class. (Please see Principal, Mr. Hardin, for exact location) | |||
| FM-200337177 03 9/24/03 Park View !! Urgent !! First Floor 1. Repair or replace locks on the following doors: Reading room #232, Health suite, Science lab, Custodian office, gymnasium and the exterior door on the Newton street side of the building. | |||
| FM-200222415 /02 10/15/03 (Parkview) !!!VERY URGENT!!! Outside cafeteria: Drains stopped up, and backing up to the kitchen/cafeteria door. | |||
| FM-200443585 04 2/6/04 (Park View) !!!VERY URGENT!!! Basement Floor/Boys Restroom: Repair shut-off valve, water flooding the floors. If DCPS Plumper find suspected asbestos pipe insulation doing digging call : Environmental Compliance 202- 576-5562, 202-439-7840 Code A-clear for repair by DCPS Charles Buchanan on 2/4/04 02/04/2004 12:07 CXB - | |||
| FM-200342112 /03 2/11/04 (Parkview) !!!VERY URGENT!!! Teacher's Lounge: Check power, and put into operation, electrical service for range; electrical range is on-site. | |||
| FM-200456793 /04 10/13/04 (Park View) !!!VERY URGENT!!! Kitchen/Cafeteria: Repair pump under kitchen sink, water is pumping out on the floor. | |||
| FM-200456919 /04 10/19/04 (Parkview) !!!VERY URGENT!!! 1st Floor/Kitchen: Repair or replace leaking pipe in the kitchen. (Water is pouring out) | |||
| FM-200458000 04 11/18/04 Park View URGENT URGRNT Frist floor-Cafeteria/sink Repair or Replace leaking pipes under sink. water can not be stoped | |||
| FM-200454442 04 11/30/04 Park View Basement Repair plaster walls in head start room. Asbestos Code A - Clear for repairs on 09/16/04. DCPS Safety - Leroy Minton Jr. (RG 09/16/04) | |||
| FM-200454357 04 12/7/04 Park View Head Start Repair plaster walls in head start room. Asbestos Code A - Clear for repairs on 09/16/04. DCPS Safety - Leroy Minton Jr. (RG 09/16/04) | |||
| FM-200460023 /04 12/23/04 Parkview Boiler Room Repair or replace stack motor for boiler #4 and #5. Motor is over heating and going out in overload. Urgent !!!!! | |||
| FM-200500003 05 1/2/05 Park View Lunch Room (Cafeteria) Repair or replace cieling mounted heating unit. Board appears to be burnt out. Urgent !!!!! | |||
| FM-200503950 05 4/18/05 (Parkview) "Urgent" Kitchen Area. Repair leaking sink in kitchen area. | |||
| FM-200506228 05 6/3/05 (Parkview) "Urgent" First floor/Teachers' restroom. Repair busted pipe water is leaking and flooding area. Note: Custodian was able to isolate leak by shutting water supply off. | |||
| FM-200108091 01 7/22/05 PARKVIEW 1) TSI REMOVAL TUNNEL AREAS. # IT CORP. Code A - There was some materials removed during summer of 2002. This work order does not identify any specifics in any of the tunnels, so this work order will be cleared for confussion sake. (LM/01-13-04) Leroy Minton Jr, Safety Office. 202-576-8962. Note; Please ! Approasch any new work with extreme caution, notify Safety Office if there are any suspect materials observed. | |||
| FM-200106571 26/01 7/27/05 PARKVIEW TUNNEL AREA UNDER HALLWAY BY CAFETERIA 1. ASBESTOS ASSESSMENT REQUIRED 2. REPLACE 16 FT. OF 3/4 RUPTURED STEAM LINE IN TUNNEL AREA UNDER HALLWAY BY CAFETERIA. TUNNEL IS RESTRICTED. Asbestos Code A - Cleared for repairs and abated on 11-03-02 by Leroy Minton Jr (LM/01-13-04) Safety Office 202-576-8962. | |||
| FM-200456925 /04 8/1/05 (Park View) 1st Street/Newton Street Side: Repair or replace panic bar that locks entrance/exit door. This is very important. (Safety hazard) | |||
| FM-200456650 04 8/1/05 (Park View) !!!VERY URGENT!!! Kitchen/Cafeteria: Sink over-flowing with black, and oil looking substance. | |||
| FM-200515723 /05 12/22/05 Parkview Boiler Room Repair or replace burner on Boiler #3. On going problem, burner in stand-by mode continously. Urgent !!!! | |||
| FM-200456255 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Breach in the ceiling in the Library wall. Asbestos Code A - Clear for repairs on 09/30/04. DCPS Safety - Richard Gibson (RG) | |||
| FM-200456256 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Room #006: Breach in the ceiling. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456257 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Lower Level/Head Start: Breach in the ceiling. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456258 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Room #228 Breach in the ceiling. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456259 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Room #112: Breach in the ceiling. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456260 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Front entrance to school has breaches in ceiling and side wall. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456261 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Custodial foreman office: Breaches in the ceiling. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456262 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Room #232-B: Breaches in the wall. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456263 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Across from Room #233: Breaches in the wall. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200456264 04 12/27/05 (Parkview) FIRE CODE VIOLATION: Room #102: Breaches in the wall. Asbestos Code A - Clear for repairs on 10/06/03. DCPS Safety - Leroy Minton (RG 10/07/04) | |||
| FM-200115256 01 2/3/06 PARKVIEW 1) ASBESTOS ASSESSMENT REQUIRED. 2) INSTALLATION OF FLOOR TILES. CTSI (IT GROUP) 703-461-6848 Asbestos Code A - Cleared for repairs and abated on 06-26-03 by Leroy Minton Jr (LM/01-13-04) Safety Office 202-576-8962. | |||
| FM-200337755 03 2/22/06 Park View !! Urgent !! Exterior 1. Catcht- basin is back -up and need to be snaked out . | |||
| FM-200620140 06 4/29/06 Grease trap cover is rusted and have danger opening. Cover need to be replace and grease trap need to be clean. This have been sited by Health Inspector Account #: xxxx | |||
| FM-200515268 05 6/7/06 Install safety mats under playground equipment | |||
| FM-200205476 02 8/25/06 Park View Boiler Room 1.Asbestos assessment required 2.Repair/replace 2" steam supply line in mechanical room. NO HEAT !!! Asbestos Code A - Cleared for repairs and abated on 04-10-02 by Leroy Minton Jr (LM/01-13-04) Safety Office 202-576-8962. | |||
| FM-200618238 06 11/15/06 Parkview Boiler Room Correct the following problems with Boiler #1 a) Contenously filling up with water b) Gas smell around burner of Boilers #1,#4 and #5, need (3) three Boilers to properly heat. Urgent !!!!!! | |||
| FM-200448471 04 1/4/07 Parkview Boiler Room Repair or replace McDonnell a & Miller 150 pump centrol on Boiler #4. Note: Broken mercury bulb in control box. Urgent !!!! | |||
| FM-200617797 06 1/29/07 Parkview Boiler Room Unstop all floor drains (approx. 5) in this area. During period of heavy rains, this area recieves alot of water. Urgent !!!!! | |||
| FM-200339489 /03 2/1/07 (Parkview) install new molding on wall Asbestos Code A - Clear for repairs on 03/30/05. DCPS Safety - Leroy Minton Jr. (RG 03/30/05) | |||
| FM-200511784 05 2/1/07 Park View Very Urgent Second Floor-Stairway Landing Near Main Office Repair/Replace missing and loose floor tiles,parents and students are tripping and complaining. Safety Hazard. Asbestos Code C - on 09/06/05. Tidewater - Philp Connolly (RG 09/07/05) Code A - abeted by Contractors per Ricardo Eley comfrmed (RG 03/13/06) | |||
| FM-200330587 03 2/1/07 Parkview !! URGENT !! Basement - Boiler Room 1. Over panel boxes cover electric and fire equipment inside of boiler room to keep water from getting to electrical and fire alarm panel . | |||
| FM-200213379 02 2/1/07 Parkview Restoration 1) Installation of floor tile throughout school. Envirobate - Charles Crenshaw - 571-436-1150 Asbestos Code A - Cleared for repairs on 01-13-04 by Leroy Minton Jr (LM/01-13-04) Safety Office 202-576-8962. | |||
| FM-200210084 02 2/20/07 (Parkview) !!Urgent!! Rear of building: Replace door damaged beyond repair; door has been repaired three (3) times this school year. There is a major concern for this problem as there are abandoned properties behind the school used for negative activity. A teacher was attacked recently. Code A-clear for repair by Leroy Minton of DCPS Safety on 07/01/02 DCPS CE Buchanan |