Urgent Repair Requests Closed in February 2006 (458)
| School |
Description |
Open Date |
Close Date |
Time Elapsed |
| Plummer Elementary School |
FM-200510136 05 2/1/06 Plummer Fire Code Violation IFC 703.1 Third Floor - Across from 217 1) Ceiling tile is missing. Asbestos Code A - Clear for repairs on 08/12/05. DCPS Safety - Richard Gibson (RG) |
August 11, 2005 |
February 1, 2006 |
174 days |
| Slowe Elementary School |
FM-200452872 04 2/1/06 (Slowe) FIRE CODE VIOLATION: Basement/Exit Door from Library: Fix or repair door closer. Asbestos Code A - Clear for repairs on 08/27/04. DCPS Safety - Leroy Minton (RG 08/27/04) |
August 18, 2004 |
February 1, 2006 |
532 days |
| Barnard Elementary School |
FM-200336657 03 2/1/06 (Barnard) !!!VERY URGENT!!! 2nd Floor/Room #239: Air handler leaking, flooding room with water; teachers supplies are damaged from water leaking in her closet. Additional problem, 09, 08, 2003. 2nd Floor/Room #251: Drain in HVAC unit leaking water down to the 1st floor. |
September 2, 2003 |
February 1, 2006 |
883 days |
| Clark Elementary School |
FM-200617972 06 2/1/06 Third floor, Corridor & Custodial Closet. "Urgent" 1.) Repair or Replace leaking water cooler. 2.) Unclog custodial slop sink, there's a bad odor coming from the sink |
January 27, 2006 |
February 1, 2006 |
5 days |
| Wilson J. O. ES |
FM-200517306 06 2/2/06 Wilson, J.O. 1st Floor New Side of Building Repair or replace pneumatic from air handle unit in mechanical Room on 1 st floor of new side of building. No heat on that side. Urgent !!!!! |
January 10, 2006 |
February 2, 2006 |
23 days |
| Gibbs Elementary School |
FM-200227232 03 2/2/06 (Gibbs) !!!VERY URGENT!!! 1st Floor/Kitchen: Leaking under sink where dishes are washed. Unable to locate shut-off valve; water is flooding the floors. |
March 18, 2003 |
February 2, 2006 |
1,052 days |
| Tyler Elementary School |
FM-200516119 05 2/2/06 Tyler Boiler room URGENT Repair or replace domestic hot water circulation pump, pump is burnt out, no movement of hot water. |
December 7, 2005 |
February 2, 2006 |
57 days |
| Reed LC |
FM-200516027 05 2/2/06 Reed Boiler Room Unstop drain in boiler room between pump #2 and #3. Water on floor of boiler room. Urgent !!!!! |
December 4, 2005 |
February 2, 2006 |
60 days |
| Hart Middle School |
FM-200125101 /01 2/3/06 (HART) CORRIDOR/ THROUGH OUT BLDG. 1) REPAIR OR REPLACE STUDENT LOCKERS WITH JAGGED AND SHARP METAL PARTS. THIS IS A SECURITY AND SAFETY HAZARD TO STUDENT AND STAFF ESPECIALLY POTENTIAL DURING AND EMERGENCY EVACUTION WHILE PASSING. |
December 13, 2001 |
February 3, 2006 |
1,513 days |
| Hart Middle School |
FM-200125099 /01 2/3/06 (HART) ROOF PERIMETER 1) REPAIR OR MODIFY INADEQUATE SECURITY LIGHTING, FREQUENTLY SHUTS OFF. 2) INSTALL OR REPLACE FIXTURES OVER BOILER ROOM AND EGRESS DOORS VISIBILITY IS EXTREMLY POOR AT NIGHT AND EARLY MORNINGS, THIS A SAFETY HAZARD TO STAFF AND PTA, IS NOT LIMITED JUST TO BUILDING SECURITY. |
December 13, 2001 |
February 3, 2006 |
1,513 days |
| Hardy Middle School |
FM-200121901 /01 2/3/06 (HARDY) 1ST FLOOR/ ROOMS: 110, 115, 101, AND 112 CLASSROOMS NEED LIGHT COVERS ON CEILING LIGHTS. * THIS IS A SAFETY HAZARD FOR TEACHERS. LIGHTS FIXTURES ARE EXPOSED* |
October 18, 2001 |
February 3, 2006 |
1,569 days |
| Patricia R Harris Ed Center |
FM-200120727 01 2/3/06 (HARRIS, P.R.) ASBESTOS ASSESSMENT REQ. 2ND, 3RD FLOOR/ ASSISTANT PRINCIPALS OFFICE ELECTRIC OUTLETS ARE NEEDED TO BE REPAIRED BECAUSE THE ONES ON THE LEFT HAND SIDE OF THE ROOM DO NOT WORK. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG |
October 1, 2001 |
February 3, 2006 |
1,586 days |
| Patricia R Harris Ed Center |
FM-200202017 02 2/3/06 (HARRIS,P.R.) ***URGENT*** ASBESTOS ASSESSMENT REQUIRED MAIN OFFICE REPLACE KNOB LOCKS ON THREE (3) DOORS IN THE MAIN OFFICE (WHERE CONFIDENTIAL RECORDS ARE KEPT) WHICH CANNOT BE PROPERLY SECURED. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: SHERYLL JAMES |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Hart Middle School |
FM-200124489 01 2/3/06 (HART) ASBESTOS ASSESSMENT REQUIRED I CAN LEARN PROGRAM RENOVATE ROOM 232 FROM A HOME ECONOMICS CLASSROOM TO A COMPUTER LAB. ELECTRICAL OUTLET LOCATIONS MUST ADHERE TO THE ELECTRICAL SCHEMATICS. SEE ELECTRICAL REQUIREMENTS & SPECIFICATION. EQUIPMENT WILL ARRIVE 12/20/01. SEE ATTACHMENT CC: DANNY HUDSON CODE A -CLEAR FOR REPAIR, ASBESTOS ABATEMENT DATE 01-25-02. DCPS SAFETY-SHEILA R. HOWARD 01-29-02. |
December 4, 2001 |
February 3, 2006 |
1,522 days |
| Patricia R Harris Ed Center |
FM-200202021 02 2/3/06 (HARRIS,P.R.) ***URGENT*** ASBESTOS ASSESSMENT REQUIRED REPLACETHE LIGHTS IN THE AUDITORIUM CEILING WHERE THERE IS AN ELECTRICAL SHORT. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: SHERYLL JAMES |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Backus Middle School |
FM-200202031 02 2/3/06 (BACKUS) ***URGENT*** ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR MAIN HALLWAY AREA NEED TO DRILL 12 HOLES IN WALLS TO SUPPORT BRACKETS FOR DISPLAYING FIRE SAFETY PICTORIAL INSTRUCTIONS (WILL BE DONE IN-HOUSE BY MR. GROSS). THE PICTURES WERE PROVIDED BY DCPS & IT IS A FIRE CODE VIOLATION NOT TO HAVE THE PICTURES PROMINENTLY DISPLAYED AT EYE-LEVEL. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: EDWARD RODRIGUEZ |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Ronald H. Brown MS |
FM-200117184 01 2/3/06 BROWN, RON ROOM 523, GYM, 116&318 ASBESTOS ASSESSMENT REQUIRED REPAIR OF BROKEN GLASS , SAFETY GLASS ON CLASSROOM DOOR ROOM 523, BROKEN WINDOW GLASS ON HALL DOOR , BY GYM & EXTERIOR WINDOW GLASS IN CLASSROOM 116 & 318. ASBESTOS CODE A-CLEAR FOR REPAIR BY 11/02/01 HRONE ENGINEER: STEPHEN CALDWELL |
August 13, 2001 |
February 3, 2006 |
1,635 days |
| Backus Middle School |
FM-200202074 02 2/3/06 BACKUS !!!! EMERGENCY !!!! SECOND (2ND) FLOOR - ACTIVITY ROOM (WEIGHT AREA) SMELL OF SMOKE IS SMELL IN THE AREA, DONOT KNOW WHERE IT IS COMING FROM. SAFETY HAZARD. |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Coolidge High School |
FM-200118057 01 2/3/06 COOLIDGE THIRD (3RD) FLOOR 1) ASBESTOS ASSESSMENT REQUIRED. 2) ROOMS # 317, 319, 327 AND 329. PIPES ARE PROTRUDING THROUGH THE FLOOR MUST BE CUT OFF AND CAPPED. TRIPPING HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. RONALD EDWARDS - SAFETY (202)576-6693 |
August 21, 2001 |
February 3, 2006 |
1,627 days |
| Benjamin Banneker Academic HS |
FM-200122976 01 2/3/06 (BANNEKER) 1ST FLOOR/ AUDITORIUM AUDITORIUM UPPER LIGHTS NEEDS AN ELECTRICIAN IS NEEDED UP IN CAT WALK LIGHTS NEED TO BE LOOKED AT FOR ELECTRICAL SHORTAGE. (SAFETY HAZARD) |
November 6, 2001 |
February 3, 2006 |
1,550 days |
| Winston EC |
FM-200112761 01 2/3/06 WINSTON THIRD AND FOURTH FLOOR STAIRWELLS, LOBBY, AND COMMONS 1) PAINT THE FOLLOWING AREAS IN PREPARATION FOR GRADUATION: STAIRWELL 2 AND 3, FIRST FLOOR LOBBY DOORS, STAIRWELL #2 DOORS FOURTH FLOOR LOBBY, FOURTH FLOOR COMMONS AREA, THIRD FLOOR COMMONS AREA STAIRS, DOORS AND COMMON AREAS ARE CONFIRMED TO BE AREAS THAT CAN BE PAINTED. CODE-A CLEARED FOR REPAIRS (DCPS SAFETY) SRH 07-11-01. ***THE ELEVATOR AREA AND THE METAL RAILINGS ARE NOT TO BE DISTURBED, NO SCRAPING, SANDING, CHIPPING OR ANY SIMILIAR ACTIVITY. |
June 7, 2001 |
February 3, 2006 |
1,702 days |
| Coolidge High School |
FM-200119083 01 2/3/06 COOLIDGE 3RD FLOOR ROOMS#317,#323,#329,#319 1.ASBESTOS ASSESSMENT REQUIRED 2.REMOVE GAS AND DOMESTIC WATER LINES THAT ARE PASSING THROUGH THE FLOORS IN ROOMS: #317,323AND 329 ALL ROOMS ARE SCIENCE LAB. 3.SAFETY HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. RONALD EDWARDS - SAFETY (202)576-6693 (SAME AS WO# FM-200118057) |
September 4, 2001 |
February 3, 2006 |
1,613 days |
| Cook J.F. Elementary School |
FM-200124785 /01 2/3/06 (COOK, J.F.) ASBESTOS ASSESSMENT REQ. STORAGE ROOM- 1ST FLOOR PRINCIPALS OFFICE- 2ND FLOOR PRINCIPALS CONFERENCE ROOM - 2ND FLOOR. POC: CHARLES BUCHANAN 202-439-7840 ASBESTOS CODE A-CLEAR FOR REPIAR 12/10/01BY DCPS SAFETY CHARLES E. BUCHANAN |
December 10, 2001 |
February 3, 2006 |
1,516 days |
| Ronald H. Brown MS |
FM-200119620 01 2/3/06 (BROWN, RON) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ ROOM 325 DOOR GLASS IS BROKEN. SAFETY GLASS FOR HALL AND CLASSROOM NEED TO BE REPLACED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/18/01. LEROY MINTON - SAFETY (202)576-6691 |
September 11, 2001 |
February 3, 2006 |
1,606 days |
| Coolidge High School |
FM-200120032 01 2/3/06 COOLIDGE ROOM#328 ELECTRICAL WORK, UNIVENT IN CLASSROOM #328 WIRED WRONG ELECTRICTRI0N NEEDED TO PROVIDE COMMON LINE FOR UNIVENT MOTOR TO RUN FROM PANEL BOX. MOTOR COMMON LINE GROUNDED TO UNIVENT,POSSIBLE DANGER OF ELECTRICAL SHOCK. |
September 18, 2001 |
February 3, 2006 |
1,599 days |
| Wilkinson ES |
FM-200120438 01 2/3/06 (WILKINSON) !VERY URGENT!! 1. ASBESTOS ASSESSMENT REQUIRED. KITCHEN/CAFETERIA: BREAKER BOX FAILURE TO RESET GARBAGE DISPOSAL. ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 24, 2001 |
February 3, 2006 |
1,593 days |
| Coolidge High School |
FM-200120788 01 2/3/06 (COOLIDGE) ASBESTOS ASSESSMENT REQ. !!!! URGENT REQUEST !!!! BOYS RESTROOM (GROUND FLOOR) REPAIR CEILING IN BOYS RESTROOM NEAR THE AUDITORIUM THE PLASTER IS PEELING AND PART OF THE CEILING HAS FALLEN. ASBESTOS CODE A - CLEAR FOR REPAIR ON 10/03/01, BY BIPIN NANAVATY - HORNE ENGINEERING (RE-10/04/01) 03/26/2004: Staff (Mr. Collins) called in today with a concern as to when repairs are to be made; as indicated, this work is long over-due. |
October 1, 2001 |
February 3, 2006 |
1,586 days |
| Coolidge High School |
FM-200120792 01 2/3/06 (COOLIDGE) ASBESTOS ASSESSMENT REQ. !!!! URGENT REQUEST !!!! NEW GYM REPAIR/ REPLACE MOTORS FOR BLEACHER, TOP BLEACHERS WILL NOT RETRACT AND LOWER BLEACHERS WILL NOT RETRACT. REPAIRS ARE NEEDED BEFORS SCHEDULED GAMES START. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/01/01. BIPIN NANAVATY - HORNE ENGINEERING (RG) |
October 1, 2001 |
February 3, 2006 |
1,586 days |
| Cook J.F. Elementary School |
FM-200122533 /01 2/3/06 (COOK, J.F.) 1. ASBESTOS ASSESSMENT REQUIRED. 2ND FLOOR: 1. WATER FOUNTAIN LEAKING ON THE LEFT SIDE OF THE HALL. 2. WATER FOUNTAIN LEAKING AND CONTINUES RUNNING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/08/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
October 29, 2001 |
February 3, 2006 |
1,558 days |
| Ronald H. Brown MS |
FM-200125839 /01 2/3/06 BROWN, RON SECOND (2ND) FLOOR - 2ND BLDG. CONNECTING HALLWAY CENTER STEP. ENTRANCEE DOOR FALLING OFF OF HINGES. SAFETY HAZARD/EMERGENCY |
December 20, 2001 |
February 3, 2006 |
1,506 days |
| Wilkinson ES |
FM-200116142 01 2/3/06 WILKINSON 2ND FLOOR - ROOM 218 CONFERENCE ROOM ASBESTOS ASSESSMENT REQUIRED CEILING TILE NEED REPLACED. (SIZE 29 1/4 x 59) ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
July 30, 2001 |
February 3, 2006 |
1,649 days |
| Cooke H.D. Elementary School |
FM-200119915 01 2/3/06 (COOKE, H.D.) ASBESTOS ASSESSMENT REQ. BASEMENT/ KITCHEN REMOVE SINGLE FACE BOWL AND INSTALL SLOP SINK. REQUEST IS FROM HEALTH CODE INSPECTORS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/17/01. LEROY MINTON - SAFETY (202)576-6691 |
September 17, 2001 |
February 3, 2006 |
1,600 days |
| Ronald H. Brown MS |
FM-200201785 02 2/3/06 BROWN RON BOILER ROOM EXTERIOR 1. ASBESTOS ASSESTMENT MAY BE REQUIRED FOR WALL. 2. FOR SAFETY AND SECURITY FURNISH AND INSTALL TWO(2) EXTERIOR LIGHTS OVER BOTH BOILER ROOM DOOR ENTRANCES. THERE ARE NO LIGHTS AT ENTRANCE OF BOILER ROOM. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/30/02 BY HORNE ENGINEER: TROY WILCOME |
January 25, 2002 |
February 3, 2006 |
1,470 days |
| Coolidge High School |
FM-200122808 01 2/3/06 (COOLIDGE) !!!URGENT REQUEST!!! GROUND FLOOR/ARMORY AREA STORAGE ROOM: REPAIR BUSTED SEWAGE LINE LEAKING THROUGH THE CEILING COMING FROM THE BOYS RESTROOM 2ND FLOOR. PERMIT DONE TO ISOLATE EMERGENCY!! ASBESTOS CODE A-CLEAR FOR REPAIR BY 11-07-01 HORNE ENGINEER : SHERYLL JAMES |
November 1, 2001 |
February 3, 2006 |
1,555 days |
| Coolidge High School |
FM-200124659 01 2/3/06 (COOLIDGE) ASBESTOS ASSESSMENT REQ. GROUND FLOOR/ 21-A-B-C DUE TO BREAKIN REPLACE EXISTING DOORS. ASSESSMENT NEEDED. (WOODEN DOORS) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/07/01. RICHARD GIBSON - SAFETY (202)576-5584 (RG) ASBESTOS CODE A-CLEAR FOR REPAIR ON 12-10-01 BY HORNE ENGINEER : SAM EBRAHIM |
December 7, 2001 |
February 3, 2006 |
1,519 days |
| Wilson J. O. ES |
FM-200116120 01 2/3/06 JO WILSON KITCHEN RESTORE REAR DOOR FRAME AND SCREEN FRAME IS CORRODED AT THE BOTTOM ON BOTH SIDES. Asbestos Code A - Cleared for repairs on 02-26-03 by Leroy Minton Jr (LN/03-30-04) Safety Office. 202-576-6691. |
July 30, 2001 |
February 3, 2006 |
1,649 days |
| Terrell Mc ES |
FM-200119138 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ KITCHEN REPLACE (1) DOUBLE SINK KITCHEN FAUCET (WALL MOUNTED TYPE) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119136 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. UPPER GROUND/ BOYS RESTROOM REPLACE VACUUM BREAKER ON TOILET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Coolidge High School |
FM-200125223 /01 2/3/06 (COOLIDGE) 2ND FLOOR/ LIBRARY !!! URGENT !!! REPAIR/ REPLACE BADLY DAMAGED DOOR TO LIBRARY. UNABLE TO PROPERLY SECURE DOOR. |
December 13, 2001 |
February 3, 2006 |
1,513 days |
| Terrell Mc ES |
FM-200119135 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ BOYS RESTROOM GYM REPLACE HANDLE ASSEMBLY ON (2) URINALS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119134 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ CUSTODIAN CLOSET REPLACE SERVICE SINK FAUCET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119126 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ GIRLS RESTROOM REPLACE (3) TOILET SEATS. REPAIR (2) BRADLEY BASIN AND RESTORE WATER TO RESTROOM. REPLACE (1) 1 1/2 SPUD AND WASHER ON TOILET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119122 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ OPEN SPACE REPLACE (2) DECK MOUNTED KITCHEN FAUCET ON (2) SINKS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119121 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ OPEN SPACE REPLACE OR REPAIR WALL HUNG DRINKING FOUNTAIN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Nalle Elementary School |
FM-200120358 01 2/3/06 NALLE BASEMENT LEVEL - BOYS RESTROOM - OLD WING 1) COMMODES ARE NOT WORKING. Asbestos Code A - Cleared for repairs on 05-08-03 by Leroy Minton Jr. (LM/05-08-03) Safety Office 202-576-8962. |
September 24, 2001 |
February 3, 2006 |
1,593 days |
| Nalle Elementary School |
FM-200120355 01 2/3/06 NALLE SECOND FLOOR - STAIRWELL (BASEMENT) 1) REPLACE LIGHTS,STAIRWELL LEADING TO BASEMENT. ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 24, 2001 |
February 3, 2006 |
1,593 days |
| Nalle Elementary School |
FM-200120346 01 2/3/06 NALLE ASBESTOS ASSESSMENT REQUIRED. SECOND FLOOR - NEXT TO ROOM 211 - OLD WING. 1) REMOVE WATER FOUNTAIN AND INSTALL NEW WATER COOLER. ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 24, 2001 |
February 3, 2006 |
1,593 days |
| Nalle Elementary School |
FM-200120340 01 2/3/06 NALLE ASBESTOS ASSESSMENT REQUIRED FIRST FLOOR-BOYS RESTROOM-OLD WING 1) REPAIR HOLE IN WALL UNDER SINK. ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 24, 2001 |
February 3, 2006 |
1,593 days |
| Gibbs Elementary School |
FM-200119832 01 2/3/06 (GIBBS) 1ST FLOOR/ GIRLS AND BOYS BATHROOM NEEDS LATCHES PUT ON BATHROOMS PARTITIONS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/14/01. LEROY MINTON - SAFETY (202)576-6691 |
September 14, 2001 |
February 3, 2006 |
1,603 days |
| Gibbs Elementary School |
FM-200449193 04 2/3/06 (Gibbs) !!!VERY URGENT!!! 2nd Floor/Girls Restroom: Toilet needs new handle assessmbly. |
June 10, 2004 |
February 3, 2006 |
603 days |
| Nalle Elementary School |
FM-200120529 01 2/3/06 (NALLE) 1. ASBESTOS ASSESSMENT REQUIRED. This request is a class project.I am requesting that the electrical capacity in the computer lab be upgraded. Account #: 288 Requester Phone: 202-645-7300 Web Form Location ID: computer lab 92 Requestor Phone: 202-645-7300 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/25/01. LEROY MINTON - SAFETY (202)576-6691 |
September 25, 2001 |
February 3, 2006 |
1,592 days |
| Hart Middle School |
FM-200201122 02 2/3/06 (HART) ASBESTOS ASSESSMENT REQUIRED THROUGHOUT 1ST & 2ND FLOORS REPLACE 180 BROKEN WINDOWS. HEAT IS GOING OUTSIDE IN ROOMS 227, 226, 230, 216, 218,214, 213, 220, 221, 224, 201 203, 207, 205, 212, 229, 231, 208, 225, LOUNGE TOILET, STAIRWELL #6, HALL BY STAIRWELL #6, 304, 305, 307, 311, 309, 306, 301, 124, HALL TO BOYS & GIRLS GYM, LOCKERROOMS, TOILETS 109, 105, 108, 127, 120, 126, 125, 122, 126, 121 & STAIRWELL #8. CODE A- CLEAR FOR REPAIR BY HORNE ENG. SHERYLL JAMES 01-16-02 DCPS SAFETY SHEILA R. HOWARD 01-16-02 |
January 15, 2002 |
February 3, 2006 |
1,480 days |
| Hart Middle School |
FM-200201113 02 2/3/06 (HART) ASBESTOS ASSESSMENT REQUIRED BASEMENT CORRIDOR BY ROOM B26 INVESTIGATE & EXPLORE LEAK FROM CONCRETE WALL. THIS PRESENTS A SAFETY HAZARD & MAY CAUSE INJURY DUE TO SLIPPING & FALLING (NO BLUEPRINTS). POC: MR. YOUMANS 645-9838 CODE A CLEAR FOR REPAIR-ASBESTOS ABATEMENT DATE 01-25-02. DCPS SAFETY-SHEILA R. HOWARD 01-29-02. |
January 15, 2002 |
February 3, 2006 |
1,480 days |
| Hart Middle School |
FM-200126503 02 2/3/06 HART BASMENT MECH. ROOM 1. REPLACE DOMESTIC HW TACO CIRC. PUMP LEAKING FROM HOUSING MOTOR G.E. HP 1/8, RMP 1725, VOLT 115, AMP3.0, PH 1, MOD. 5KH32EG129GX 2. REPAIR 1" COPPER SWEAT LINE TEE AND BUSHING TO SAFETY RELIEF VALVE. 3. No asbestos assessment needed. |
January 2, 2002 |
February 3, 2006 |
1,493 days |
| Green Elementary School |
FM-200116628 01 2/3/06 GREEN OUTSIDE RUN OFF DRAIN ASBESTOS ASSESSMENT REQUIRED OPEN OR UNSTOP DRAIN TO RUN OFF DITCH BEHIND PLAYGROUND & PARKING LOT AREA. THERE IS A LOT OF STANDING WATER. STAFF HAS REMOVED TRASH & DEBRIS. ASBESTOS CODE A-CLEAR FOR REPAIR BY 10/29/01 DCPS SAFETY : SRH |
August 3, 2001 |
February 3, 2006 |
1,645 days |
| Hardy Middle School |
FM-200112488 01 2/3/06 HARDY FIRST FLOOR CAFETERIA, HALLWAY ACROSS FROM GIRLS RESTROOM 1) FURNISH AND INSTALL TWO (2) WATER COOLERS ONE IN THE CAFETERIA AND ONE ON THE 34 TH ST. SIDE. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY CEB. 8/14/01. (CEB) ACROSS FROM GIRLS RESTROOM WATER LINES ARE PRESENT WATER COOLER ACROSS FROM THE FIRST FLOOR GIRLS RESTROOM NEEDS TO BE DESIGNED FOR AN EXPLORATORY. |
June 5, 2001 |
February 3, 2006 |
1,704 days |
| Shaw JHS |
FM-200122302 /01 2/3/06 (SHAW) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ COMMONS AREA EXIT LIGHTS NOT WORKING WHEN CLOSING SCHOOL. LIGHTS DONT WORK. PLEASE SEND HELP. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/14/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
October 24, 2001 |
February 3, 2006 |
1,563 days |
| Winston EC |
FM-200120703 01 2/3/06 (WINSTON) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ GYM REPLACE GYM FLOOR. SAFETY HAZARD, NEED SURVEY BE SURE TO CHECK UNDER THE WOOD. POC: KAREN WALLS, CUSTODIAL FOREMAN ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/15/01. HORNE ENGINEERING - TROY WILCOME |
September 28, 2001 |
February 3, 2006 |
1,589 days |
| Winston EC |
FM-200120045 01 2/3/06 (WINSTON) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ STAIRWELL, GARAGE NEED ELECTRICIAN TO COME OUT AND REPLACE LIGHTS IN STAIRWELL BEHIND GYM. INSTALL OR REPLACE LIGHT AT ENTRANCE DOOR NEAR GARAGE. (AREA IS TO DARK) ASBEATOS CODE A - CLEAR FOR REPAIRS ON 9/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 18, 2001 |
February 3, 2006 |
1,599 days |
| Bruce-Monroe Elementary School |
FM-200112886 01 2/3/06 BRUCE-MONROE THIRD FLOOR ROOF 1) INSTALL AIR VENTILATORS PREVIOUS VENTILATORS NOT WORKING ASBESTOS CODE A - CLEAR FOR REPAIRS ON 01/07/02. RONALD EDWARDS - SAFETY (202)576-6691 |
June 8, 2001 |
February 3, 2006 |
1,701 days |
| Ballou Senior High School |
FM-200114105 01 2/3/06 BALLOU (STAY) SUB-BASEMENT ROOMS A-4 AND A-9 1) ELECTRICAL UPGRADE FOR COMPUTERS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/30/01. SYLVIA GRIMES - SAFETY (202)576-5583 (RG) |
June 26, 2001 |
February 3, 2006 |
1,683 days |
| Duke Ellington School |
FM-200122405 /01 2/3/06 (ELLINGTON) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ NEAR GIRLS BATHROOM HALLWAY SINK NEEDS NEW HARDWARE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/26/01. CHARLES BUCHANAN - SAFETY (202)576-5582 (RG) |
October 25, 2001 |
February 3, 2006 |
1,562 days |
| Duke Ellington School |
FM-200122407 /01 2/3/06 (ELLINGTON) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ GIRLS BATHROOM WATER PRESSURE CANT BE ADJUSTED. NEEDS A KIT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/26/01. CHARLES BUCHANAN - SAFETY (202)576-5582 (RG) |
October 25, 2001 |
February 3, 2006 |
1,562 days |
| Amidon Elementary School |
FM-200119990 01 2/3/06 (AMIDON) ASBESTOS ASSESSMENT REQ. 1,2 FLOORS/ HALLWAYS NEED SOME ONE TO COME OUT TO PAD THE CIRCUT BREAKER BOXES IN THE BUILDING THEY ARE STICKING TO FAR FROM THE WALLS AND CHILDREN ARE GETTING INJURED BECAUSE OF THIS SITUATION. MADE A REQUEST ON OR AROUND MARCH NO HAS RESPONDED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/17/01. LEROY MINTON - SAFETY (202)576-6691 |
September 17, 2001 |
February 3, 2006 |
1,600 days |
| Duke Ellington School |
FM-200123550 /01 2/3/06 (ELLINGTON) ASBESTOS ASSESSMENT REQUIRED SUB-BASEMENT/GYMNASIUM NEED 2 RIMS INSTALLED IN GYMNASIUM. (HAVE ONE RIM ON HAND) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/28/01 LEROY MINTON - SAFETY (202)576-6691 |
November 16, 2001 |
February 3, 2006 |
1,540 days |
| Young Elementary School |
FM-200202051 02 2/3/06 (YOUNG) ASBESTOS ASSESSMENT REQUIRED 1ST & 2ND FLOORS/GYM LOBBY & STAIRWAY #4 REPAIR OR REPLACE DOOR CLOSER ON DOORS TO THE 1ST FLOOR GYM & 2ND FLOOR STAIRWAY #4 Asbestos Code A - Clear for repairs on 7/15/02 DCPS Safety R. Edwards, (RE - 7/15/02) |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Bruce-Monroe Elementary School |
FM-200118162 01 2/3/06 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQD. THROUGHOUT REPAIR OR REPLACE HAND WASHING SINKS/FAUCETS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/28/01. RONALD EDWARDS - SAFETY (202)576-6693 |
August 22, 2001 |
February 3, 2006 |
1,626 days |
| Ballou Senior High School |
FM-200118037 01 2/3/06 (BALLOU) ASBESTOS ASSESSMENT REQD. SUB-BASEMENT FLOOR CORRIDOR PANEL BOX NEEDS TO BE SURVEYED BY ELECTRICIANS- INSPECTOR *DAVID BRYANT* HAS REQUESTED THIS SURVEY ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. RONALD EDWARDS - SAFETY (202)576-6693 |
August 21, 2001 |
February 3, 2006 |
1,627 days |
| Duke Ellington School |
FM-200124048 /01 2/3/06 ELLINGTON !!!! EMERGENCY !!!! KITCHEN/CAFETERIA GARAGE DISPOSAL IS SHOOTING OUT SPARKS. SAFETY HAZARD. |
November 29, 2001 |
February 3, 2006 |
1,527 days |
| Bruce-Monroe Elementary School |
FM-200122178 /01 2/3/06 (BRUCE-MONROE) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ OLD GYM STAIRWAY REPLACEMENT OF CEILING. CEILING HAS FALLEN IN DUE TO ROOF DAMAGE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/01/01. CHARLES BUCHANAN - SAFETY (202)576-5582(RG) |
October 23, 2001 |
February 3, 2006 |
1,564 days |
| Shaw JHS |
FM-200118215 01 2/3/06 (SHAW) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ REC. CEILING LEAKING EVERY TIME IT RAINS. SAFETY HAZARD. CODE A-CLEAR FOR REPAIRR BY HORNE ENG BIPIN NANAVAN 8/24/01. |
August 23, 2001 |
February 3, 2006 |
1,625 days |
| Wilkinson ES |
FM-200120539 01 2/3/06 (WILKINSON) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ GYM AREA #47 PROVIDE THREE (3) WIRE MESH GLASS FOR FIRE EXTINGUISHER CABINETS. MAINTENANCE STAFF WILL INSTALL. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG |
September 26, 2001 |
February 3, 2006 |
1,591 days |
| Woodson High School |
FM-200116396 01 2/3/06 WOODSON ,H.D. PLAZA - MAIN OFFICE CONFERENCE ROOM. ASBESTOS ASSESSMENT REQD. 1) REPLACE BROKEN WINDOW , DO TO BREAK IN SIZE: 131/4 X311/2, WINDOW ON GROUND LEVEL. (EMERGENCY) CODE A-CLEAR FOR REPAIR BY DCPS SAFETY (SG) 8/01/01. WORK WAS COMPLETED IN JULY 2001. |
August 1, 2001 |
February 3, 2006 |
1,647 days |
| Woodson High School |
FM-200112997 01 2/3/06 WOODSON, H.D. EXTERIOR PARKING ENTRANCE OUTSIDE AUDITORIUM 1) OUTSIDE DRAINS STOPPED UP ASBESTOS CODE A - CLEAR FOR REPARS ON 06/11/01. LEROY MINTON - SAFETY (202)576-6691 |
June 11, 2001 |
February 3, 2006 |
1,698 days |
| Houston Elementary School |
FM-200124947 /01 2/3/06 (HOUSTON) ASBESTOS ASSESSMENT REQUIRED Replace all floor tiles in the All Purpose Room. Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note : This work is done. |
November 27, 2001 |
February 3, 2006 |
1,529 days |
| Houston Elementary School |
FM-200121273 01 2/3/06 (HOUSTON) Install carpet and padding in room 206. Requester Phone: 724-4622 Requestor Phone: 724-4622 Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note: This work order is cleared through the safety office for the purpose of moving the work forward, however do not attempt to remove any carpet period without contacting the safety office, 202-576-8962. |
September 26, 2001 |
February 3, 2006 |
1,591 days |
| Bunker Hill Elementary School |
FM-200110919 01 2/3/06 BUNKER HILL FIRST FLOOR GIRLS RESTROOM - MIDDLE WING 1) REPAIR CEILING WHERE PLASTER IS LOOSE AND FALLING. AREA TO BE REPAIRED WAS INSPECTED BY INSPECTOR BUCHANAN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/30/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
May 24, 2001 |
February 3, 2006 |
1,716 days |
| Ferebee-Hope Elementary School |
FM-200110880 01 2/3/06 FEREBEE-HOPE FIRST FLOOR LOBBY, HALLWAY, AND MAIN OFFICE 1) INSPECT CEILING FOR ELECTRICAL WORK TO BE PERFORMED ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/24/01. MR. LEROY MINTON - (SAFETY) (202)576-6691 |
May 23, 2001 |
February 3, 2006 |
1,717 days |
| West Elementary School |
FM-200126450 /01 2/3/06 WEST BOILER ROOM FURNISH MATERIALS TO REPLACE BROKEN SEWER EJECTOR PUMP. NOTE: URGENT,FLOODING BOILER ROOM. |
December 31, 2001 |
February 3, 2006 |
1,495 days |
| Ferebee-Hope Elementary School |
FM-200117243 01 2/3/06 FEREBEE-HOPE (B) BLDG. MAINTENANCE STORAGE ROOM ASBESTOS ASSESSMENT REQUIRED PLUMBING: REPLACE 90 DEGREE ELBOW 3" DRAIN LINE THAT IS CRACKED. (ROOF DRAIN LINE) SAFETY HAZARD ASBESTOS CODE A-CLEAR FOR REPAIR ON 9/25/01BY HORNE ENGINEER: ROGER KAGER |
August 13, 2001 |
February 3, 2006 |
1,635 days |
| Walker-Jones EC |
FM-200123283 /01 2/3/06 (WALKER-JONES) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ OPEN SPACE ON THE LEFT BY ENTRANCE REPLACE WINDOWS. HOLE IN BIG WINDOW, TOP PART. (SAFETY HAZARD) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/15/01. HORNE ENGINEERING - ROYMOND AGNANT |
November 14, 2001 |
February 3, 2006 |
1,542 days |
| Walker-Jones EC |
FM-200121078 01 2/3/06 (WALKER-JONES) ASBESTOS ASSESSMENT REQ. 1ST AND 3RD FLOOR/ ROOMS 109 AND 305 REPAIR WINDOW. (CORRIDOR WINDOW CRACKED) (SAFETY HAZARD) ASBESTOS CODE A-CLEAR FOR REPAIR BY 10-22-01 HORNE ENGINEER : STEPHEN CALDWELL |
October 5, 2001 |
February 3, 2006 |
1,582 days |
| Bunker Hill Elementary School |
FM-200121516 /01 2/3/06 (BUNKER HILL) ASBESTOS ASSESSMENT REQ. OUTSIDE/ BEHIND HEALTH SUITE PLEASE REPLACE OUTSIDE DRAIN PIPE THAT HAS FALLEN DOWN, AND ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
October 12, 2001 |
February 3, 2006 |
1,575 days |
| Burrville Elementary School |
FM-200118489 01 2/3/06 BURRVILLE LEARNING CENTER - FIRST FLOOR AND SECOND FLOOR WET WINK AREA - 162,178, AND 78. 1) INSTALL SAFETY PLUGS IN THE ABOVE LOCATIONS. ASBESTOS CODE A-CLAER FOR REPAIR FOR BY 11-16-01 HORNE ENGINEER: ROGER KAGER |
August 27, 2001 |
February 3, 2006 |
1,621 days |
| Ferebee-Hope Elementary School |
FM-200124615 01 2/3/06 (FEREBEE-HOPE) OUTSIDE/ FRONT OF THE BUILDING ENTRANCE ELECTRICAL: REPLACE (3) LIGHTS IN FRONT OF BUILDING OVERHANG. (SAFETY HAZARD) |
December 6, 2001 |
February 3, 2006 |
1,520 days |
| Ferebee-Hope Elementary School |
FM-200124616 01 2/3/06 (FEREBEE-HOPE) GROUNDS/OUTSIDE LOADING DOCK BACK OF BUILDING ELECTRICAL: REPLACE (3) LIGHTS IN FRONT OF BUILDING OVERHANG. (SAFETY HAZARD) |
December 6, 2001 |
February 3, 2006 |
1,520 days |
| Bunker Hill Elementary School |
FM-200122547 /01 2/3/06 (BUNKER HILL) 1. ASBESTOS ASSESSMENT REQUIRED. GROUND FLOOR/BOYS RESTROOM: REPAIR LARGE HOLE IN WALL ON LEFT SIDE OF SINK; LEAK HAS BEEN REPAIRED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/02/01. RONALD EDWARDS - SAFETY (202)576-6693(RG) |
October 29, 2001 |
February 3, 2006 |
1,558 days |
| Bunker Hill Elementary School |
FM-200123695 /01 2/3/06 BUNKER HILL LIBRARY 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPAIR COUNSELOR COIL (HEATING). INSTALL CUT OFF VALVE. (URGENT) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/21/01. HORNE ENGINEERING - RICHARD BYRD (RG) |
November 21, 2001 |
February 3, 2006 |
1,535 days |
| Houston Elementary School |
FM-200121272 01 2/3/06 (HOUSTON) Install carpet and padding in room 208. Requester Phone: 724-4622 Requestor Phone: 724-4622 Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note: This work order is cleared through the safety office for the purpose of moving the work forward, however do not attempt to remove any carpet period without contacting the Safety Office, 202-576-8962. |
September 26, 2001 |
February 3, 2006 |
1,591 days |
| Houston Elementary School |
FM-200121095 01 2/3/06 (HOUSTON) 1. ASBESTOS ASSESSMENT REQUIRED. Installed new carpet and padding in room 157. Requester Phone: 724-4622 Requestor Phone: 724-4622 Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note: This work order is cleared through the safety office for the purpose of moving the work forward, however do not attempt to remove any carpet period without contacting the Safety Office, 202-576-8962. |
September 26, 2001 |
February 3, 2006 |
1,591 days |
| Houston Elementary School |
FM-200121081 01 2/3/06 (HOUSTON) 1. ASBESTOS ASSESSMENT REQUIRED. New carpet and padding installed in room 106. Requester Phone: 724-4622 Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note: This work order is cleared through the safety office for the purpose of moving the work forward, however do not attempt to remove any carpet period without contacting the Safety Office, 202-576-8962. |
September 26, 2001 |
February 3, 2006 |
1,591 days |
| Houston Elementary School |
FM-200120650 01 2/3/06 (HOUSTON) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ CAFETERIA REPAIR/ REPLACE PANIC BAR, AND REPLACE CYLINDER LOCK. KEYS WILL NOT FUNCTION IN CYLINDER. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 28, 2001 |
February 3, 2006 |
1,589 days |
| Houston Elementary School |
FM-200116131 01 2/3/06 HOUSTON REAR PARKING LOT CLEAN OUT CLOGGED STORM DRAIN. OVERFLOWS DURING RAIN AND LEAVES A BAD ODOR. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/04/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
July 30, 2001 |
February 3, 2006 |
1,649 days |
| Houston Elementary School |
FM-200114400 01 2/3/06 HOUSTON FIRST FLOOR ROOMS 103 AND 114 1) REPLACE CARPET IN CLASSROOM 103 AND 114 Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. Note: This work order is cleared through the safety office for the purpose of moving the work forward, however do not attempt to remove any carpet period without contacting the Safety Office, 202-576-8962. |
June 29, 2001 |
February 3, 2006 |
1,680 days |
| Houston Elementary School |
FM-200113256 01 2/3/06 HOUSTON SECOND FLOOR ROOM 202 1) REPLACE OR REPAIR DOOR DOOR DRAGS ON FLOOR MAIKNG IT DIFFICULT TO OPEN AND CLOSE Asbestos Code A - Cleared for repairs on 04-08-03 by Leroy Minton Jr. (LM/04-08-03) Safety Office 202-576-8962. |
June 13, 2001 |
February 3, 2006 |
1,696 days |
| Terrell Mc ES |
FM-200122452 /01 2/3/06 (TERRELL, M.C.) 1. ASBESTOS ASSESSMENT REQUIRED. Install circuit for computers on Level II (Second floor) Activity Center (stage). Install additional lighting for computer area. Requester Phone: 645-3740 Requestor Phone: 645-3740 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/26/01. CHARLES BUCHANAN - SAFETY (202)576-5582 (RG) |
October 23, 2001 |
February 3, 2006 |
1,564 days |
| Young Elementary School |
FM-200116669 01 2/3/06 YOUNG OUTSIDE - BASEMENT DOOR ACROSS FROM M. BROWN ASBESTOS ASSESSMENT REQUIRED SURVEY & REPLACE LARGE METAL DOOR LEADING INTO BASEMENT TUNNELS. DOOR IS VERY HARD TO OPEN DUE TO WEAR & TEAR. NEED A CROW BAR TO OPEN IT. URGENT ASBESTOS CODE B10/12/01 BY HORNE ENGINEER ROGER KAGER Asbestos Code A - Clear for repairs on 7/17/02 DCPS Safety - R. Edwards (RE - 7/17/02) |
August 3, 2001 |
February 3, 2006 |
1,645 days |
| Benning Elementary School |
FM-200113153 01 2/3/06 BENNING PLAYGROUND 1 & 2 1) BIG DRAIN CLOGGED UP ON PLAYGROUND ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/03/01. RICHARD GIBSON- SAFETY (202)576-5584(RG) |
June 12, 2001 |
February 3, 2006 |
1,697 days |
| Coolidge High School |
FM-200116990 01 2/3/06 COOLIDGE BASEMENT UNDER OLD GIRLS GYM 1) LOCKERS NEED TO BE REMOVED BEFORE CLEAN UP CAN BEGIN. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY LM 8/9/01. |
August 9, 2001 |
February 3, 2006 |
1,639 days |
| Shaw JHS |
FM-200112554 01 2/3/06 SHAW SHOWER ROOM BOYS LOCKER ROOM 1) REPAIR OR REPLACE LIGHT FIXTURE HANGING FROM CEILING IN LOCKER ROOM ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/04/02 SYLVIA GRIMES - SAFETY (202)576-5583 (RG)-01/24/02 |
June 6, 2001 |
February 3, 2006 |
1,703 days |
| Shaw JHS |
FM-200112112 01 2/3/06 SHAW 1) REPLACE (0) STAINED CEILING TILE (2X4) REPLACE (0) MISSING OR BROKEN (2X4) 2) REPLACE (0) STAINED CEILING TILE (12X12) REPLACE (330) MISSING OR BROKEN (12X12) 3) REPAIR OR REPLACE LIGHT FIXTURES AS NEEDED. (CEILING TILE REPLACEMENT PROJECT) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/17/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
June 4, 2001 |
February 3, 2006 |
1,705 days |
| Terrell Mc ES |
FM-200119152 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ KITCHEN 2 DEAK MOUNTED KITCHEN FAUCETS AND BOTH DRINKING FOUNTAINS HAVE LOW WATER PRESSURE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Shaed Elementary School |
FM-200202166 02 2/3/06 (SHAED) Asbestos Assessment Reqd. GROUND LEVEL EXTERIOR DOOR REALIGN DOORS, REPAIR THRESHOLD PLATE (DOOR WILL NOT CLOSE PROPERLY). Asbestos Code A - Clear for repairs, on 6/14/02 DCPS Safety - R. Edwards (RE - 6/14/02) |
January 30, 2002 |
February 3, 2006 |
1,465 days |
| Shaed Elementary School |
FM-200116667 01 2/3/06 SHAED HUMAN RESOURCE - GROUND FLOOR ASBESTOS ASSESSMENT REQUIRED BROKEN WINDOW NEDD REPLACING. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY LM 8/6/01 |
August 3, 2001 |
February 3, 2006 |
1,645 days |
| Thomas Elementary School |
FM-200123273 /01 2/3/06 THOMAS TEACHERS LOUNGE, PRINCIPALS AND BOYS RESTROOM - BASEMENT LEVEL 1) ASBESTOS ASSESSMENT REQUIRED. 2) CORRECT PLUMBING DEFICIENCIES IN RESTROOM. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/16/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
November 13, 2001 |
February 3, 2006 |
1,543 days |
| Seaton Elementary School |
FM-200116635 01 2/3/06 SEATON 1ST FLOOR - KITCHEN ASBESTOS ASSESSMENT REQUIRED NEED FLOOR RECEPTABLES REMOVED FROM KITCHEN. NO LONGER BEING USED. SAFETY HAZARD / BUCKETS OVER RECEPTABLES. |
August 3, 2001 |
February 3, 2006 |
1,645 days |
| Garfield ES |
FM-200119412 01 2/3/06 (GARFIELD) LEAD AND ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ 2-I & 1ST FLOOR #1E SCRAPE AND PAINT WALLS. PAINT IS PEELING. POC LEROY MINTON DCPS SAFETY 202 438-9097 CELL PHONE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/28/01. HORNE ENGINEERING - BILL CAMPION (RG) |
September 7, 2001 |
February 3, 2006 |
1,610 days |
| Seaton Elementary School |
FM-200115138 01 2/3/06 SEATON FIRST (1ST) FLOOR - ALL PURPOSE ROOM REPAIR OR REPLACE EMERGENCY LIGHT FIXTURES. POC: DANNY HUDSON 202 345-1566 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/27/01 LEROY MINTON - SAFETY (202)576-6691 (RG) |
July 11, 2001 |
February 3, 2006 |
1,668 days |
| Tubman Elementary School |
FM-200120992 01 2/3/06 (TUBMAN) ASBESTOS ASSESSMENT REQ. ENTIRE BUILDING RE-KEY ENTIRE BUILDING AND HAVE MASTER DOOR KEY FOR HEAD DAY CUSTODIAN AND HEAD NIGHT CUSTODIAN. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/23/01. LEROY MINTON - SAFETY (202)576-6691 (RG |
October 4, 2001 |
February 3, 2006 |
1,583 days |
| Amidon Elementary School |
FM-200125126 /01 2/3/06 (AMIDON) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ LOADING DOCK NEED SOMEONE TO COME OUT TO REPAIR OR REPLACE THE METAL PLATE ON THE LOADING DOCK. ITS A SAFETY HAZARD, SOMEONE HAS ALREADY TRIP OVER THE PLATE. Asbestos Code A - Clear for repairs on 02/21/02 DCPS Ronald Edwards (RE) |
December 13, 2001 |
February 3, 2006 |
1,513 days |
| Rudolph Elementary School |
FM-200120192 01 2/3/06 (RUDOLPH) ASBESTOS ASSESSMENT REQ. GROUND FLOOR/ BOYS AND GIRLS BATHROOM RE-KEY LOCKS ON DOORS TO RESTROOMS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/21/01. LEROY MINTON - SAFETY (202)576-6691 |
September 20, 2001 |
February 3, 2006 |
1,597 days |
| Benning Elementary School |
FM-200120476 01 2/3/06 (BENNING) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ KITCHEN REPLACE HEATING COIL IN DOUBLE SINK COMPARTMENT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/25/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 25, 2001 |
February 3, 2006 |
1,592 days |
| Ballou Senior High School |
FM-200120876 01 2/3/06 BALLOU 1ST FL. ASST. PRINCIPALS OFFICE 1. ASBESTOS ASSESSMENT IS REQUIRED. 2. REPLACE (1) WINDOW A/C UNIT. iNFO: AMANA MOD #S1082R, SER. # 022350773 V. 115, HZ 60, AMP 7.5, BTU 8200. ASBESTOS CODE A-CLEAR FOR REPAIR 12/03/01 BY DCPS SAFETY : RONALD EDWARDS 202 439 8094 REPAIR WAS COMPLETED AT TIME OF INSPECTION. |
October 2, 2001 |
February 3, 2006 |
1,585 days |
| Garfield ES |
FM-200202033 02 2/3/06 (GARFIELD) ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR, AREA 77/NEW WING REMOUNT INTERNET LINES--TWO-WAY TAPE IS NOT STICKING, NEED SHOT-GUN. WALLS ARE CINDER-BLOCK AND THERE IS NO ASBESTOS. ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/29/02 RICHARD GIBSON - SAFETY (202)576-5584 (RG)-01/29/02 |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| John Burroughs ES |
FM-200120677 01 2/3/06 (BURROUGHS) ASBESTOS ASSESSMENT REQ. 1ST CORRIDOR (WEST) COMPLETE INSTALLATION OF CEILING TILE. NO TILE IN AREA. PROJECT WAS STARTED BY CONTRACTOR AND STOPPED BECAUSE OF IMPROPER PROCEDURES. POC: JOHN RIDGLEY - 202-889-8400 HRGM CORP ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/23/01. RONALD EDWARDS - SAFETY (202)576-6691 (RG) |
September 28, 2001 |
February 3, 2006 |
1,589 days |
| Garfield ES |
FM-200202037 02 2/3/06 (GARFIELD) ASBESTOS ASSESSMENT REQUIRED AREA 38/INSIDE FRONT ENTRANCE LIGHTS ON STAIRWELL NEED TO BE REPLACED (DO NOT HAVE A LADDER CAPABLE OF REACHING THIS AREA FOR IN-HOUSE STAFF TO ACCOMPLISH THE REPLACEMENT) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/26/02. DCPS- SAFETY RICHARD GIBSON (202)576-5584 (RG 03/0102) |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Garfield ES |
FM-200202040 02 2/3/06 (GARFIELD) Asbestos Assessment Reqd. AREA 31 OUTSIDE CLOSET THE OUTSIDE STORAGE AREA DOOR IS EXTREMELY HARD TO OPEN & NEEDS TO BE REPAIRED OR REPLACED. Asbestos Code A - Clear for repairs on 6/13/02 DCPS Safety - R. Edwards (RE- 6/13/02) |
January 29, 2002 |
February 3, 2006 |
1,466 days |
| Savoy Elementary School |
FM-200114951 01 2/3/06 SAVOY FIRST FLOOR BETWEEN GIRLS RESTROOM AND CUSTODIANS OFFICE 1) TERRIBLE AND SERIOUS LEAK BETWEEN GIRLS RESTROOM AND CUSTODIANS OFFICE ON FIRST FLOOR COMING FROM OUTSIDE ROOF CEILING TILE WET AND IN DANGER OF FALLING ASBESTOS CODE A-CLEAR FOR REPAIR BY 11/02/01 HRONE ENGINEER: BIPIN NANAVARY |
July 9, 2001 |
February 3, 2006 |
1,670 days |
| John Burroughs ES |
FM-200202105 02 2/3/06 BURROUGHS LIBRARY ASBESTOS ASSESSMENT REQUIRED 1) PAINT CEILING IN THE LIBRARY. CODE A CLEAR FOR REPAIR-01-21-02 SAMPLES COLLECTED BY RONALD EDWARDS OF DCPS SAFETY 01-18-02. AMA CHAIN OF CUSTODY #91057/DCPS SAFETY-SHEILA R. HOWARD 01-31-02. SAMPLE RESULTS GIVEN TO GREGORY WILLIAMS OF USACE AND MARGO MONROE BSM, DIVISION#3 SAME AS FM-2002014118 ASBESTOS CODE A-CLEAR FOR REPAIR ON 2/05/02 BY HORNE ENGINEER: EDWARD RODRIGUEZ |
January 30, 2002 |
February 3, 2006 |
1,465 days |
| Turner Elementary School |
FM-200113086 01 2/3/06 TURNER FIRST AND THIRD FLOOR NEW SIDE STAIRS 1) REPLACE FLOOR TILE IN AREAS THAT IT GROUP REMOVED Code A Clear for Repair the asbestos abatement is completed the floor tile can be replaced DCPS Safety- Sheila R. Howard 06-28-02. |
June 11, 2001 |
February 3, 2006 |
1,698 days |
| Hine JHS |
FM-200124563 01 2/3/06 HINE BOILER ROOM 1. ASBESTOS ASSESSMENT REQUIRED. 2. REPAIR/REPLACE 4 SAFETY RELIEF VALVES ON DOMESTIC HOT WATER STORAGE TANK. DATA HAS BEEN PAINTED OVER. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/05/01. HORNE ENGINEERING - STEPHEN CALDWELL (RG) |
December 5, 2001 |
February 3, 2006 |
1,521 days |
| Garnet-Patterson MS |
FM-200114130 01 2/3/06 GARNETT PATERSON MAIN OFFICE 1. ASBESTOS ASSESSMENT REQUIRED. 2. FURNISH AND INSTALL 24,000 BTU WINDOW A/C UNIT THAT IS BEYOND REPAIR. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY LM 8/2/01. |
June 27, 2001 |
February 3, 2006 |
1,682 days |
| Garnet-Patterson MS |
FM-200116991 01 2/3/06 (GARNETT-PATTERSON) 1. ASBESTOS ASSESSMENT REQUIRED. Garbage disposal in cafertia kitchen is not working Requester Phone: 202-576-7400 Web Form Location ID: 0410 Requestor Phone: 202-576-7400 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/04/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
August 7, 2001 |
February 3, 2006 |
1,641 days |
| Turner Elementary School |
FM-200120223 01 2/3/06 (TURNER) ASBESTOS ASSESSMENT REQ. 1ST AND 2ND FLOOR/ FIRE DOORS SURVEY AND PAINT NEW INSTALLED METAL FIRE DOORS AND METAL FRAMES. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/21/01. LEROY MINTON - SAFETY (202)576-6691 |
September 20, 2001 |
February 3, 2006 |
1,597 days |
| John Burroughs ES |
FM-200123580 /01 2/3/06 (BURROUGHS) ASBESTOS ASSESSMENT REQUIRED REPLACE/REPAIR BROKEN DOOR, WHICH CREATES A SAFETY HAZARD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/19/01. HORNE ENGINEERING - SHARON VOSS (RG) |
November 19, 2001 |
February 3, 2006 |
1,537 days |
| John Burroughs ES |
FM-200122044 01 2/3/06 (BURROUGHS) 1. ASBESTOS ASSESSMENT REQUIRED. I have 6 restrooms that have concrete floors and they are breakin up. I need them changed to tile floors: Main Building: Men & Women 1st floor, Boys & Girls 1st floor, Boys & Girls basement restrooms. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/04/01. LEROY MINTON - SAFETY (202)576-6691 |
October 5, 2001 |
February 3, 2006 |
1,582 days |
| Turner Elementary School |
FM-200120245 01 2/3/06 (TURNER) ASBESTOS ASSESSMENT REQ. ROOF OLD SIDE REPLACE OUTSIDE ROOF LIGHTS THAT HAVE BEEN SHOT OUT. (2) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/21/01. LEROY MINTON - SAFETY (202)576-6691 |
September 21, 2001 |
February 3, 2006 |
1,596 days |
| Hine JHS |
FM-200119016 01 2/3/06 (HINE) 1. ASBESTOS ASSESSMENT REQUIRED. Rm 308- Unstop drain line to science lab table. Requester Phone: 202 698-3330 Requestor Phone: 202 698-3330 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/07/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
August 22, 2001 |
February 3, 2006 |
1,626 days |
| Hine JHS |
FM-200116084 01 2/3/06 (HINE) 1. ASBESTOS ASSESSMENT REQUIRED. Replace fire safety glass. Requester Phone: 202 698-3330 Requestor Phone: 202 698-3330 ASBESTOS CODE A-CLEAR FOR REPAIR 10/11/01BY HORNE ENGINEER RAY AGNANT |
July 26, 2001 |
February 3, 2006 |
1,653 days |
| Hendley Elementary School |
FM-200123166 01 2/3/06 HRNDLEY MAIN ENTRANCE EXTERIOR LIGHTS ARE NOT WORKING PROPERLY. PRINCIPAL WANTS THE LIGHTS REPAIR OR REPLACE. EXTERIOR LIGHTING ARE NEED AT NIGHT TIME DO TO STUDENT AND STAFF LEAVING OR COMING. SAFETY HAZARD. ISOLATE EMERGENCY!!! |
November 9, 2001 |
February 3, 2006 |
1,547 days |
| Hendley Elementary School |
FM-200118520 01 2/3/06 (HENDLEY) ASBESTOS ASSESSMENT REQ, THE TUNNEL OF THE ANNEX, THE WALL HAS PLASTIC AND A PIECE OF WIRE EXPOSED. (SAFETY HAZARD). ASBESTOS CODE A-CLEAR FOR REPAIR ON 9/25/01BY HORNE ENGINEER: ROGER KAGER |
August 27, 2001 |
February 3, 2006 |
1,621 days |
| Turner Elementary School |
FM-200122606 /01 2/3/06 TURNER FIRST (1) FLOOR - BOYS RESTROOM 1. ASBESTOS ASSESSMENT REQUIRED. 2. BRICK UP WALL WHERE URINALS NEEDS TO BE HUNG; ALSO NEEDS CERAMIC TILE WORK. ASBESTOS CODE A - CLEARED FOR REPAIRS ON 10-04-01 (LM) SAFETY OFFICE:202-576-8962. ASBESTOS CODE A-CLEAR FOR REPAIR BY 11/02/01 HORNE ENGINEER: SHARON VOSS |
October 30, 2001 |
February 3, 2006 |
1,557 days |
| Nalle Elementary School |
FM-200119047 01 2/3/06 NALLE ROOM #225 NEW WING REPLACE 25,000 BTU WINDOW A/C UNIT. OLD UNIT CONTINUES TO TRIP CIRCUIT BREAKER AFTER RUNNING ABOUT 15 MINUTES. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/04/01. CHARLES BUCHANAN - SAFETY (202)576-5582 (RG) |
September 4, 2001 |
February 3, 2006 |
1,613 days |
| Cook J.F. Elementary School |
FM-200118640 01 2/3/06 (COOK,J.F) ASBESTOS ASSESSMENT REQD. 1ST FLOOR CUSTODIAN OFFICE 108 TILE OR CARPET OFFICE REPLACE CARPET IN BOTH CLASSROOMS PRE-K AND ROOM 102. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/24/01. LEROY MINTON - SAFETY (202)576-6691 |
August 28, 2001 |
February 3, 2006 |
1,620 days |
| Wilson J. O. ES |
FM-200120104 01 2/3/06 (WILSON, J.O.) ASBESTOS ASSESSMENT REQ. ROOF/ OPEN SPACE ASSESS, ABATE, AND RESTORE ROOF TOP. NOTE: ROOF TOP LEAKS AND HAS MANY SAGGING AND SOFT SPOTS PRESENT. ASBESTOS D BY 11/01/01 - HORNE ENGINEER: BIPIN NANAVARY ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/13/02 AFTER DCPS - SAFETY RONALD EDWARDS RESITED THE SITE WITH GARY RUCKER AND DETERMINED THAT THE NEGATIVE CEILING TILE WAS THE ONLY MATERIAL TO BE REMOVED FROM INSIDE THE BUILDING, NO NEED TO ENTER THE ROOF AT ALL. DCPS- SAFETY - S R HOWARD 02/14/02 (202)576-9862 (RG 02/14/02) |
September 18, 2001 |
February 3, 2006 |
1,599 days |
| Terrell Mc ES |
FM-200119154 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ GIRLS BATHROOM 1 COMMODE FLUSH VALVE. 1 BRADLEY BASIN NEEDS TO BE REPAIRED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Nalle Elementary School |
FM-200117875 01 2/3/06 (NALLE) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ DATA ENTRY CLERK OFFICE INSTALL A/C UNIT. ASBESTOS CODE B ON 10/19/01 BY HORNE ENGINEER : EDWARD RODRIGUEZ Asbestos Code A - Cleared for repairs on 05-1303 by Leroy Minton Jr. (LM/05-08-03) Safety Office 202-576-8962. |
August 20, 2001 |
February 3, 2006 |
1,628 days |
| Terrell Mc ES |
FM-200119155 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ MENS BATHROOM REPLACE COMMODE AND FITTINGS. COMMODE IS ON SITE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119159 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ PRE-K REPLACE (2) SINK TRAPS ON (2) KITCHEN SINKS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119160 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ 2ND FLOOR CORRIDOR NO WATER SUPPLY TO DRINKING FOUNTAIN. 2 DRINKING FOUNTAINS NEED TO BE REPAIRED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Brent Elementary School |
FM-200122962 01 2/3/06 (BRENT) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ KITCHEN SECURE ELECTRICAL PANEL BOXES BY INSTALLING LOCKING DEVICES. SCHOOL WATCH ACTION TEAM INSPECTION. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/08/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
November 6, 2001 |
February 3, 2006 |
1,550 days |
| Takoma Educational Center |
FM-200122686 /01 2/3/06 (TAKOMA) EXTERIOR REPAIR/ REPLACE LAMP POLE NEAR MAIN ENTRANCE, BROKEN BOLTS ON POLE. THE POLE CAN BE SHAKEN AND IS A SAFETY HAZARD. IT IS THE 1ST POLE ON THE LEFT. |
October 31, 2001 |
February 3, 2006 |
1,556 days |
| Takoma Educational Center |
FM-200121489 /01 2/3/06 (TAKOMA) 2ND FLOOR/ GIRLS BATHROOM !!! EMERGENCY !!! REPAIR CEILING IN RESTROOM DUE TO DAMAGE FROM THE TOLIET UPSTAIRS, DEBRIS IS DROPPING FROM CEILING AREA. ASBESTOS CODE A-CLEAR FOR REPAIR 10/12/01 BY DCPS SAFETY CHARLES E. BUCHANAN ASBESTOS CODE A-CLEAR FOR REPAIR 10/12/01 BY HORNE ENGINEER DAMIIEL GARRIPOLI |
October 12, 2001 |
February 3, 2006 |
1,575 days |
| Takoma Educational Center |
FM-200117408 01 2/3/06 TAKOMA EXTERIOR ASBESTOS ASSESSMENT REQUIRED PAINTING OF ALL EXTERIOR HANDRAILS & SAFETY RAILS AT THE ENTRANCE OF THE EXITS & STEPS AROUND THE BLDG. PREPARING FOR OPENING OF SCHOOL. ASBESTOS CODE A-CLEAR FOR REPAIR 10/12/01 BY HORNE ENGINEER STEPHEN CALDWELL |
August 14, 2001 |
February 3, 2006 |
1,634 days |
| Takoma Educational Center |
FM-200116634 01 2/3/06 TAKOMA 2ND & 3RD FLOOR - ROOM 167 & 235 ASBESTOS ASSESSMENT REQUIRED REPLACE LOCKS ON WALL MOUNTED SHOWCASE DISPLAY. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY SG 8/7/01. |
August 3, 2001 |
February 3, 2006 |
1,645 days |
| Takoma Educational Center |
FM-200113386 01 2/3/06 TAKOMA 1) REPAIR THE METAL CHIMNEY THAT IS DEFECTIVE AND RUSTED OUT. THE GAS COMPANY HAS SHUT DOWN THE GAS EQUIPMENT UNTIL REPAIR IS COMPLETED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 06/15/01. LEROY MINTON - SAFETY (202)576-6691 |
June 15, 2001 |
February 3, 2006 |
1,694 days |
| Takoma Educational Center |
FM-200112090 01 2/3/06 TAKOMA 1) REPLACE (10) STAINED CEILING TILE (2X4) 2) REPLACE (10) 12X12 CEILING TILE. 3) MISSING 0, BROKEN 0 4) REPAIR OR REPLACE LIGHT FIXTURES AS NEEDED. After asking Margo Monroe for locations on 06-27-02 we were told the areas are the theater, room #217C, room #190 and room #232. will be assessed in house now. (CEILING TILE REPLACEMENT PROJECT) Linda Bacote is the Head Custodian Code A-clear for repair by DCPS Safety Leroy Minton on 07/01/02 DCPS CE Buchanan |
June 4, 2001 |
February 3, 2006 |
1,705 days |
| Cooke H.D. Elementary School |
FM-200124227 /01 2/3/06 (COOKE, H.D.) ASBESTOS ASSESSMENT REQUIRED 3RD & 2ND FLOOR 1) NEWLY HUNG DOORS IN BACK OF CLASSROOM 307; PUT GLASS PANES IN 2) COATROOM (2ND FLOOR-RM 200) NEEDS GLASS PANE PLACED IN NEWLY HUNG DOOR @ FRONT ENTRANCE ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/04/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
November 30, 2001 |
February 3, 2006 |
1,526 days |
| Draper Elementary School |
FM-200110938 01 2/3/06 DRAPER BASEMENT HALLWAY PRINCIPALS OFFICE 1) TOUCH UP PAINTING REQUIRED ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/24/01. MR. RICHARD GIBSON - SAFETY (202)576-5584 |
May 24, 2001 |
February 3, 2006 |
1,716 days |
| Draper Elementary School |
FM-200111443 01 2/3/06 DRAPER THROUGHOUT BUILDING 1) FABRICATE AND CONSTRUCT NON-ACCESS PANEL BOXES UNDERNEATH INSTALLED ELECTRICAL BOXES IN VARIOUS AREAS OF BUILDING WHERE NEEDED FOR SAFETY Asbestos Code A - Clear For Repairs On 03/26/02. Horne Engineering - Philp Connnolly (RG 03/27/02) |
May 29, 2001 |
February 3, 2006 |
1,711 days |
| Takoma Educational Center |
FM-200111154 01 2/3/06 TAKOMA FIRST FLOOR ROOM 73 1) REPLACE AND PROVIDE STAIR STREADS ON STEPS TO PREVENT INJURIES ASBESTOS CODE A -CLEAR FOR REPAIRS ON 05/25/01. |
May 25, 2001 |
February 3, 2006 |
1,715 days |
| Takoma Educational Center |
FM-200111152 01 2/3/06 TAKOMA SECOND FLOOR ROOM 170 1) PROVIDE AND REPLACE STAIR STREADS ON STEPS TO PREVENT INJURIES ASBESTOS CODE A -CLEAR FOR REPAIRS ON 05/29/01. |
May 25, 2001 |
February 3, 2006 |
1,715 days |
| Draper Elementary School |
FM-200120486 01 2/3/06 (DRAPER) 1. ASBESTOS ASSESSMENT REQUIRED. REWIRE ELECTRICAL OFF/ON SWITCH TO DOMESTIC HOT WATER HEATER. REASON: NO HOT. (ELECTRICIAN) Requester Phone: 698-1750 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/25/01. LEROY MINTON - SAFETY (202)576-6691 |
September 20, 2001 |
February 3, 2006 |
1,597 days |
| Nalle Elementary School |
FM-200122184 /01 2/3/06 (NALLE) ASBESTOS ASSESSMENT REQ. KITCHEN GREASE TRAP- BACK UP AND NEEDS TO BE SNAKED OUT. WASH SINK- WATER PRESSURE IS LOW AT FULL BLAST THE WATER IS ONLY DROPPING. HAND SINK- WATER WONT STOP DROPPING. ASBESTOS CODE A - CLEARED FOR REPAIRS 10-24-01. (LM) SAFETY OFFICE 202-576-8962. |
October 23, 2001 |
February 3, 2006 |
1,564 days |
| Reed LC |
FM-200124583 01 2/3/06 MARIE REED SWIMMING POOL AREA ASBESTOS ASSESSMENT REQUIRED 1) REPLACE LIGHT FIXTURES IN POOL AREA. POC: PROSPERITY CONTRACTORS DERRICK HOWARD - 301-203-2804 FM-200124578 ASBESTOS CODE A-CLEAR FOR REPAIR ON 12/6/01 BY DCPS SAFETY CHARLES E. BUCHANAN WORK ORDER FM-200124578 IS A CODE A. |
December 6, 2001 |
February 3, 2006 |
1,520 days |
| Terrell Mc ES |
FM-200119151 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ GIRLS BATHROOM 1 COMMODE FLUSH VALVE 2 TOILET SEALS 1 HANDLE ASSEMBLY 2 BRADLEY BASINS NEED REPAIRING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119150 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ BOYS RESTROOM 2 FLUSH VALVE ASSEMBILIES FOR COMMODE. 1 FLUSH VALVE ASSEMBLE FOR URINAL. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Reed LC |
FM-200124578 01 2/3/06 REED, MARIE SWIMMING POOL AREA AND MEZANNENE INSTALL LIGHT FIXTURES AROUND POOL AND UPPER MEZANNENE AREA. CONTRACTOR: DERRICK HOWARD 301-203-2804 FM-200124583 ASBESTOS CODE A-CLEAR FOR REPAIR ON 12/6/01 BY DCPS SAFETY CHARLES E. BUCHANAN WORK ORDER FM-200124583 IS A CODE A. |
December 5, 2001 |
February 3, 2006 |
1,521 days |
| Nalle Elementary School |
FM-200122653 /01 2/3/06 (NALLE) 1. ASBESTOS ASSESSMENT REQUIRED. Replace lock on auditorium door. Repair started in September; however, the work needs to be completed. Account #: 288 Requester Phone: 202-645-7300 Web Form Location ID: 83 Requestor Phone: 202-645-7300 ASBESTOS CODE A-CLEAR FOR REPAIR BY 11/01/01 DCPS SAFETY : CEB |
October 26, 2001 |
February 3, 2006 |
1,561 days |
| Brent Elementary School |
FM-200122961 01 2/3/06 (BRENT) ASBESTOS ASSESSMENT REQ. 1, 2, AND 3RD FLOORS/ CORRIDORS SECURE ELECTRICAL PANEL BOXES BY INSTALLING LOCKING DEVICES. SCHOOL WATCH ACTION TEAM INSPECTION. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/08/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
November 6, 2001 |
February 3, 2006 |
1,550 days |
| Reed LC |
FM-200121130 01 2/3/06 REED SWIMMING POOL DECK SAND AND FINISH BENCHES AROUND THE POOL DECK PERIMETER. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/18/01. SHEILA HOWARD - SAFETY (202) 576-8962 (RG) |
October 5, 2001 |
February 3, 2006 |
1,582 days |
| Clark Elementary School |
FM-200116418 01 2/3/06 CLARK ROOF THIRD REQUEST FOR THE LIGHT ON ROOF TO BE FIX. NEED A B CAN NOT REACH. ITS VERY DARK ON GROUNDS WHEN LEAVING AT NIGHT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. CHARLES BUCHANAN - SAFETY (202)576-5582 |
August 1, 2001 |
February 3, 2006 |
1,647 days |
| Clark Elementary School |
FM-200112689 01 2/3/06 CLARK 1ST FLOOR CHECK FOR ASBESTOS . REPAIR PLASTER CEILING OUTSIDE OVER HANG BY 1ST FLOOR PRE-K. ROOM. CODE A CLEAR FOR REPAIR- 01-11-02 DCPS SAFETY SHEILA R. HOWARD HORNE ENGINEERING-SAM EBRAHIM 01-11-02. RESUBMITTED TO HORNE 01-11-02 |
June 7, 2001 |
February 3, 2006 |
1,702 days |
| Orr Elementary School |
FM-200111646 01 2/3/06 ORR FIRST FLOOR ROOM 12 AND HEALTH SUITE 1) REPAIR LEAK IN CEILING IN BUSINESS MANAGERS OFFICE IN LIGHT FIXTURE 2) REPAIR LEAK IN HEALTH SUITE CEILING ASBESTOS CODE A - CLEARED FOR REPAIRS ON 07-31-01. LEROY MINTON JR SAFETY OFFICE ( 202-576-8962 ) SAME AS WO# 200106950, LEAK CORRECTED |
May 30, 2001 |
February 3, 2006 |
1,710 days |
| Orr Elementary School |
FM-200124239 /01 2/3/06 (ORR) ASBESTOS ASSESSMENT REQUIRED 2ND & 4TH FLOORS REPLACE DOOR KNOBS ON STAIRWELL DOORS ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/11/01 RONALD EDWARDS - SAFETY (202)576-6691 |
November 30, 2001 |
February 3, 2006 |
1,526 days |
| Reed LC |
FM-200121004 01 2/3/06 (REED) ASBESTOS ASSESSMENT REQ. 1ST AND GROUND FLOOR/ EARLY CHILDHOOD BOYS RESTROOM,STAIRS #5 EXIT DOOR IN EARLY CHILDHOOD WILL NOT OPEN AND EXIT DOOR ON STAIRWAY #5 IS HARD TO CLOSE. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG |
October 4, 2001 |
February 3, 2006 |
1,583 days |
| Reed LC |
FM-200113268 01 2/3/06 REED OUTSIDE GROUNDS FLAMMABLE TOOL SHED 1) SUPPLY AND INSTALL GATE VALVE WATER CONTINUES TO RUN SIZE UNKNOWN DUE TO PIPE INSULATION ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/04/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
June 13, 2001 |
February 3, 2006 |
1,696 days |
| Drew Elementary School |
FM-200114432 01 2/3/06 DREW FIRST (1ST) FLOOR - CAFETERIA 1) ASBESTOS ASSESSMENT REQUIRED. 2) REPAIR AND REPLACE LIGHTS AND BALLAST THROUGH-OUT ENTIRE AREAS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/13/02. RONALD EDWARDS - SAFETY (202)576-6693 (RG 02/14/02) |
June 29, 2001 |
February 3, 2006 |
1,680 days |
| Drew Elementary School |
FM-200124623 01 2/3/06 (DREW) ASBESTOS ASSESSMENT REQ. 2ND FLOOR/ BOYS TOILET REPAIR HOLE IN THE CEILING FALLING PLASTER. APPROX. 2" X 4". LEAK ABOVE RESTROOM HAS BEEN REPAIRED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/13/02. RONALD EDWARDS - SAFETY (202)576-6693 (RG 02/14/02) |
December 6, 2001 |
February 3, 2006 |
1,520 days |
| Macfarland Middle School |
FM-200517192 06 2/3/06 Urgent-First Floor-By Principal Office Snake out sink |
January 6, 2006 |
February 3, 2006 |
28 days |
| Brent Elementary School |
FM-200122941 01 2/3/06 (BRENT) 1. ASBESTOS ASSESSMENT REQUIRED. 1ST FLOOR/LOBBY: REPLACE EXISTING SMOKE LEXAN WITH FIRE RATED GLASS OR CLEAR LEXAN. (SCHOOL WATCH ACTION TEAM INSPECTION) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/08/01 RONALD EDWARDS - SAFETY (202)576-6693(RG) |
November 6, 2001 |
February 3, 2006 |
1,550 days |
| Wilson J. O. ES |
FM-200122860 01 2/3/06 (WILSON, J.O.) ASBESTOS ASSESSMENT REQ. 1, 2, AND 3 FLOORS/ CEILING IN ALL OPEN SPACE AREAS ASSESS, ABATE, AND RESTORE 3x5 CEILING TILE WITH 2x4x3/4" TILE. NOTE: CURRENT CEING TILES ARE POSSIBLE SAFETY HAZARD DISTURBED OR REMOVED. ALSO TILE MAY CONTAIN ASBESTOS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/05/01. HORNE ENGINEERING - BIPIN NANAVATY (RG) |
November 2, 2001 |
February 3, 2006 |
1,554 days |
| Stuart-Hobson Middle School |
FM-200124694 /01 2/3/06 STUART-HOBSON BOILER ROOM STEPS 1. ASBESTOS ASSESSMENT REQUIRED. REPLACE HANDRAILING ONSTEPS LEADING TO BOILER ROOM AND REPAIR OR REPLACE METAL LANDING. (SAFETY HAZARD). Requester Phone: 698-1750 Requestor Phone: 698-1750 Asbestos Code A - Cleared for repairs on 04-21-03 by Leroy Minton Jr. (LM/04-08-03) the Safety Office 202-576-8962. |
November 21, 2001 |
February 3, 2006 |
1,535 days |
| Stevens Elementary School |
FM-200118723 01 2/3/06 (STEVENS) ASBESTOS ASSESSMENT REQ. REAR 1ST FLOOR WINDOWS COMPLETE GRATES FOR REMAINING WINDOWS. (ONE WINDOW IN THE PRE-K IS DANGEROUS, CHILDREN CAN CLIMB UP ON BOTTOM LEDGE IN CLASSROOM) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/24/01. HORNE ENGINEERING - RAYMOND AGNANT (RG) |
August 29, 2001 |
February 3, 2006 |
1,619 days |
| Wilson J. O. ES |
FM-200124266 /01 2/3/06 (WILSON, J.O.) ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR/NW CORRIDOR REPLACE WIRE MESH TRANSOM GLASS. ASBESTOS CODE A-CLEAR FOR REPAIR 12/04/01 BY DCPS SAFETY CE BUCHANAN 202 439 7840 |
November 30, 2001 |
February 3, 2006 |
1,526 days |
| Terrell Mc ES |
FM-200119164 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. UPPER GROUND/ GIRLS RESTROOM REPAIR BRADLEY BASIN AND RESTORE WATER TO RESTROOM. REPLACE (3) 1 1/2 SPUD AND WASHER ON TOILET (1) HANDLE ASSEMBLY KIT ON TOILETS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Terrell Mc ES |
FM-200119166 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ BOYS BATHROOM REPLACE (1) TOILET SEAT AND REPAIR (1) FLUSH VALVE ON URINAL. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Bowen Elementary School |
FM-200508969 05 2/3/06 Bowen Fire Code Violation - 2003 D.C. Supp IFC - 110.1.1 Second Floor - Storage Room 1) Vertical Penetration. Code A - clear for repairs as of 8/3/05 by Tidewater. Sylvia Grimes safety office. |
July 28, 2005 |
February 3, 2006 |
190 days |
| Terrell Mc ES |
FM-200121500 /01 2/3/06 (TERRELL, M.C.) REPLACE COVERS FOR 2 (TWO) DRAINS !!! EMERGENCY !!! ON PLAYGROUND THE OPENINGS ARE VERY DEEP AND DANGEROUS. (SAFETY HAZARD) |
October 12, 2001 |
February 3, 2006 |
1,575 days |
| Wilson J. O. ES |
FM-200124573 01 2/3/06 (WILSON, J.O.) ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR MUSIC ROOM & 2ND FLOOR LIBRARY AREA NEED RESTORATION OF LIGHT FIXTURES IN POORLY LIT AREAS DUE TO BAD BALLASTS--GETTING MANY COMPLAINTS FROM STAFF ABOUT LIGHTING DEFICIENCIES. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/11/01 RONALD EDWARDS - SAFETY (202)576-6691 |
December 5, 2001 |
February 3, 2006 |
1,521 days |
| Bowen Elementary School |
FM-200126888 02 2/3/06 (BOWEN) OUTSIDE/PLAYGROUND THE LIGHTS ON THE BLDG LIGHTING THE PLAYGROUND ARE CONSISTENTLY BEING BROKEN BY CHILDREN THROWING BRICKS. REPLACE ALL BROKEN LIGHTS (WHICH ARE NOW BROKEN SHARDS HANGING OVER PLAYGROUND & COULD FALL ONTO THE CHILDREN CAUSING SERIOUS INJURY) & INSTALL PROTECTIVE CAGES OVER THE REPLACEMENT LIGHTS & ALL OTHER REMAINING LIGHTS (PREVENTING BREAKAGE) ON THE OUTSIDE OF THE BLDG & THE PLAYGROUND. |
January 7, 2002 |
February 3, 2006 |
1,488 days |
| Wilson J. O. ES |
FM-200126118 /01 2/3/06 (WILSON, J.O.) ASBESTOS ASSESSMENT REQUIRED 3RD FLOOR ROOM 303 REPLACE CRUMBLING FLOOR TILES, DAMAGED FROM FAULTY BLEEDER VALVE LEAK. ***URGENT*** Asbestos Code A - Abated and cleared for repairs on 07/09/03 by Leroy Minton Jr (LM/03-30-04) Safety Office. 202-576-6691. |
December 27, 2001 |
February 3, 2006 |
1,499 days |
| Bowen Elementary School |
FM-200124473 01 2/3/06 (BOWEN) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ CAFETERIA REPAIR PLASTER CEILING-DAMAGE FROM OLD ROOF. PIECES ARE FALLING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/06/01. HORNE ENGINEERING - SHERYLL JAMES (RG) NOTE: This plastering/painting job can not proceed until the roofing problem causing the falling plaster is resolved [Ref: FM-200208742]. At that time, please update this to a very urgent status, as the plaster is falling in ever larger pieces. |
December 4, 2001 |
February 3, 2006 |
1,522 days |
| Murch Elementary School |
FM-200201567 02 2/3/06 (MURCH) ASBESTOS ASSESSMENT REQ. FRONT-ENTRY DOOR TO MULLION IS RUSTED AND ROTTED. DOOR DOES NOT LOCK, DOOR IS NOT REPAIRABLE, AND DOOR NEEDS TO BE REPLACED. Asbestos Code A - Clear for repairs on 06/07/02. DCPS Safety - Ronald Edwards (RG 06/10/02) |
January 23, 2002 |
February 3, 2006 |
1,472 days |
| Wilson J. O. ES |
FM-200201508 02 2/3/06 (WILSON, J.O.) !URGENT! 1. ASBESTOS ASSESSMENT REQUIRED. NORTH NEW SIDE-PRE-K/ROOM #148: REPAIR OR REPLACE METAL FIRE DOOR; RODENTS ARE ENTERING THE BUILDING. DOOR HAS BEEN DAMAGED BY THE RODENTS EATING THEIR WAY INTO THE BUILDING. PEST CONTROL IS ON THE GROUNDS TODAY. (ENTRY DOOR) ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/24/02 HORNE ENGINEERING - SHERYLL JAMES (RG)-01/24/02 |
January 23, 2002 |
February 3, 2006 |
1,472 days |
| Eastern High School |
FM-200112360 01 2/3/06 EASTERN GROUND FLOOR 1) ASBESTOS ASSESSMENT REQUIRED 2) INSTALL ELECTRIC CIRCUIT THRU EXISTING PIPE TO ROOF. POC: KEN KATZ WORK TO BE DONE BY E.L.S. CONTRACTOR. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 06/04/01. RICHARD GIBSON - SAFETY 202 576-5584 |
June 4, 2001 |
February 3, 2006 |
1,705 days |
| Spingarn High School |
FM-200127268 02 2/3/06 (SPINGARN) ASBESTOS ASSESSMENT REQUIRED ARMORY REPLACE CEILING TILE DAMAGED BECAUSE OF A LEAKING TOILET IN RESTROOM ABOVE. ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/17/02 SYLVIA GRIMES - SAFETY (202)576-5583 (RG) |
January 11, 2002 |
February 3, 2006 |
1,484 days |
| Eastern High School |
FM-200115322 01 2/3/06 (EASTERN) "VERY URGENT" 1. ASBESTOS ASSESSMENT REQUIRED. 1ST FLOOR/ROOM #149: THIS IS A NEW CLASSROOM; NEED OUTLETS FOR USE OF COMPUTERS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 07/17/01. |
July 17, 2001 |
February 3, 2006 |
1,662 days |
| Spingarn High School |
FM-200120003 01 2/3/06 (SPINGARN) ASBESTOS ASSESSMENT REQ. !!!! URGENT !!!!! 306, 326, NURSES OFFICE THESE ROOMS ARE UNSAFE AND NEED PLASTER AND PAINT. THE CEILINGS IN THESE ROOMS ARE DAMAGED BADLY. ASBESTOS CODE A-CLEAN FOR REPAIR ON 9/19/01 BY HORNE ENGINEER RICHARD BYRD |
September 17, 2001 |
February 3, 2006 |
1,600 days |
| Spingarn High School |
FM-200118666 01 2/3/06 (SPINGARN) ASBESTOS ASSESSMENT REQ. REPAIR OR REPLACE LEAKING FAUCETS OR NON WORKING FAUCETS FOR THE FOLLOWING ROOMS: 115, 119, 218, 219, 307, AND 310. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 |
August 28, 2001 |
February 3, 2006 |
1,620 days |
| Spingarn High School |
FM-200118464 01 2/3/06 SPINGARN OUTSIDE - GROUNDS PROFESSIONALLY TOUCH-UP YELLOW PAINTING DONE BY THE FOOTBALL TEAM ASBESTOS CODE A - CLEAR FOR REPAIR ON 08/30/01. SYLVIA GRIMES - SAFETY (202)576-5583 |
August 27, 2001 |
February 3, 2006 |
1,621 days |
| Eastern High School |
FM-200118510 01 2/3/06 (EASTERN) ASBESTOS ASSESSMENT REQ. BUILDNG EXTERIOR REPLACE (12) HOSE BIBS ON OUTSIDE OF BUILDING. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/29/01. LEROY MINTON - SAFETY (202)576-6691 |
August 27, 2001 |
February 3, 2006 |
1,621 days |
| Terrell Mc ES |
FM-200119145 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. GYM RESTORE HOT WATER TO SHOWERS. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Bowen Elementary School |
FM-200122318 /01 2/3/06 (BOWEN) 1. ASBESTOS ASSESSMENT REQUIRED. K27 is no longer the Custodians Office it is now the Counselors Office locate on the first floor. The wall is very badly damage. It has a very large split and material are falling out. Not sure if the materials falling out is of a dangerous nature. Also the base boards ar coming away from the wall. Requester Phone: 202 724-4871 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/26/01. HORNE ENGINEERING - SHERYLL JAMES (RG) |
October 18, 2001 |
February 3, 2006 |
1,569 days |
| Eastern High School |
FM-200122807 01 2/3/06 (EASTERN) ENTIRE SCHOOL: WALL POCKET LIGHT: BUGS NEED TO BE CLEANED OUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/01/01. CHARLES BUCHANAN - SAFETY (202)576-5584 (RG) |
November 1, 2001 |
February 3, 2006 |
1,555 days |
| Eastern High School |
FM-200122835 01 2/3/06 (EASTERN) ASBESTOS ASSESSMENT REQ. FOOTBALL FIELD/ STADIUM REPAIR OR REPLACE (4) FOUNTAINS ON FIELD. NONE OF THE FOUNTAINS OPERATE AT THIS TIME. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/05/01 LEROY MINTON - SAFETY (202)576-6691(RG) |
November 2, 2001 |
February 3, 2006 |
1,554 days |
| Sousa Middle School |
FM-200112451 01 2/3/06 SOUSA BASEMENT GYM 1) REPAIR EXIT LIGHTS FLUSH TO CEILING 2) FURNISH RIM TO LIGHT FIXTURE SO IT WONT FALL DOWN TO FLOOR ASBESTOS CODE A - CLEAR FOR REPAIRS ON 02/28/02. DCPS- SAFETY RONALD EDWARDS (202)576-6693 (RG 03/0102) |
June 5, 2001 |
February 3, 2006 |
1,704 days |
| Smothers ES |
FM-200121994 /01 2/3/06 (SMOTHERS) !!VERY URGENT!! 1. ASBESTOS ASSESSMENT REQUIRED. 2ND FLOOR/ROOM #202: FLOOR IS BUCKLING UP DUE TO WATER DAMAGE IN ROOM #202. PLYBOARD AND TILE IS DAMAGED VERY BADLY. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/19/01. HORNE ENGINEERING - EDWARD RODRIGUEZ (RG) |
October 19, 2001 |
February 3, 2006 |
1,568 days |
| Smothers ES |
FM-200116424 01 2/3/06 SMOTHER ROOF ASBESTOS ASSESSMENT REQUIRED UNCLOG DOWN SPOUT DRAIN AT FRONT, WEST WING OF THE BLDG. UNCLOG GROUND DRAINS ON EAST AND NORTH SIDE OF BLDG. CODE A-CLEAR FOR REPAIR BY DCPS SAFETY SG 8/2/01. |
August 1, 2001 |
February 3, 2006 |
1,647 days |
| Bowen Elementary School |
FM-200117746 01 2/3/06 (BOWEN) 1. ASBESTOS ASSESSMENT REQUIRED. OUTSIDE/BUILDING FLOOD LIGHTS: FLOOD LIGHTS WERE DAMAGED BY VANDALS; REPLACE LIGHTS WITH PROTECTIVE SHIELDS. (LIGHTS HAVE BEEN OUT FOR A WEEK) CODE A-CLEAR FOR REPAIR BY DCPS SAFETY RONALD EDWARD. CEB |
August 17, 2001 |
February 3, 2006 |
1,631 days |
| Eastern High School |
FM-200124508 01 2/3/06 (EASTERN) **EMERGENCY** BASEMENT/MAIN ENTRANCE LOBBY REPAIR HOLES IN WALL IN CORRIDOR ACROSS FROM RM B-70; HOLES IN CORNER OF LOW CEILING AREA NEED TO BE REPAIRED, & AT THE RIGHT OF RM B-37 CEILING HOLES NEED TO BE REPAIRED. THE STUDENTS HAVE A TENDENCY TO FILL THESE HOLES WITH PAPER WHICH THEY THEN SET ON FIRE CREATING A HAZARD. ## NO WORK PERMIT ISSUED## J. EGGLESTON Asbestos Code A - Cleared on 03-17-04 by Leroy Minton Jr (LM) Safety Office 202-576-8962. |
December 4, 2001 |
February 3, 2006 |
1,522 days |
| Smothers ES |
FM-200110937 01 2/3/06 SMOTHERS ROOMS 102 - 106 1) TOUCH UP PAINTING REQUIRED ASBESTOS CODE A - CLEAR FOR REPAIRS ON 05/24/01. MR. RICHARD GIBSON - SAFETY (202)576-5584 |
May 24, 2001 |
February 3, 2006 |
1,716 days |
| Eastern High School |
FM-200127269 02 2/3/06 (EASTERN) ASBESTOS ASSESSMENT REQUIRED ARMORY ROOF REPLACE 20 FT OF DOWN-SPOUT DUE TO VANDALISM ASBESTOS CODE - A - CLEAR FOR REPAIRS ON 01/17/02 SYLVIA GRIMES - SAFETY (202)576-5583 (RG) |
January 11, 2002 |
February 3, 2006 |
1,484 days |
| Cardozo High School |
FM-200119567 01 2/3/06 (CARDOZO) ASBESTOS ASSESSMENT REQ. !!!!!!!! URGENT !!!!!! BASEMENT/ B-7 WOODSHOP INSTALL ELECTRIC SERVICE FOR COMPUTERS, 115 VOLTS AND MOUNT POWER STRIPS AS WELL AS WALL OUTLETS. WORK WAS STARTED BUT NEVER FINISHED. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/16/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 10, 2001 |
February 3, 2006 |
1,607 days |
| Moten Elementary School |
FM-200124082 /01 2/3/06 (MOTEN) ASBESTOS ASSESSMENT REQUIRED ROOM 306 INSTALL AN 1/2-INCH STOP VALVE ON HOT & COLD WATER LINE. NO INSULATION ON LINE. ASBESTOS CODE A-CLEAR FOR REPAIR 12/05/01 BY DCPS SAFETY RONALD EDWARD 202 439 8094 |
November 29, 2001 |
February 3, 2006 |
1,527 days |
| Moten Elementary School |
FM-200121795 /01 2/3/06 (MOTEN) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ FIRE DOOR 16TH ST SIDE HINGE NEEDS TO BE REPLACED (OLD SIDE). ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/19/01. RONALD EDWARDS - SAFETY (202)576-6691 |
October 16, 2001 |
February 3, 2006 |
1,571 days |
| Eaton Elementary School |
FM-200111391 01 2/3/06 EATON DR. WILLIE MCELROY PTA COMMUNITY GROUP MULTI-PURPOSE ROOM 1) CEILING TILES IN MULTI-PURPOSE NEEDED 12 INCHES X 12 INCHES CEILING HA032 NAD CEB SAFETY OFFICE Asbestos Code A-Clear For Repairs |
May 29, 2001 |
February 3, 2006 |
1,711 days |
| Eaton Elementary School |
FM-200116794 01 2/3/06 EATON BOILER ROOM ASBESTOS ASSESSMENT REQUIRED ENGINEER NEED TO GAIN ACCESS TO BOILER ROOM. BOILER ROOM DOOR HAS NO KEY. RE-KEY FALCOM LOCK TO ACCOMMADATE ACCESS. URGENT CODE A-CLEAR FOR REPAIR BY DCPS SAFETY LM 8/9/01. |
August 6, 2001 |
February 3, 2006 |
1,642 days |
| Terrell Mc ES |
FM-200119140 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ MAIN OFFICE REPLACE HANDLE KIT ASSEMBLY ON TOILET. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Slowe Elementary School |
FM-200122651 /01 2/3/06 (SLOWE) ASBESTOS ASSESSMENT REQ. 1ST FLOOR/ NEAR CAFETERIA (EXTERIOR) DOOR IS BROKE DUE TO VANDALISM. REPAIR OR REPLACE. ASBESTOS CODE A-CLEAR FOR REPAIR BY 11-13-01 DCPS SAFETY : CEB 11-13-01 POC: THOMPSON ALFONZO 202-576-6075 |
October 30, 2001 |
February 3, 2006 |
1,557 days |
| Slowe Elementary School |
FM-200118113 01 2/3/06 SLOWE ROOM 100, 102 ASBESTOS ASSESSMENT REQUIRED REPLACE (2)NEWLY INSTALLED 25,000 BTU WINDOW A/C UNITS. POSSIBILITY COMPRESSOR MOTOR IS BURNED OUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 12/08/01 RICHARD GIBSON - SAFETY (202)576-5584 |
August 22, 2001 |
February 3, 2006 |
1,626 days |
| Eliot Junior High School |
FM-200114408 01 2/3/06 ELIOT GYM 1) REMOVE CLIMBING ROPES AND CHAINS FROM GYM CEILING STUDENTS SWINGING AND GETTING HURT ROPES ARE NOT IN USE |
June 29, 2001 |
February 3, 2006 |
1,680 days |
| Slowe Elementary School |
FM-200111929 01 2/3/06 SLOWE 1) REPLACE (105) STAINED CEILING TILE (2X4) 2) MISSING 0, BROKEN 6 3) REPAIR OR REPLACE LIGHT FIXTURES AS NEEDED. (CEILING TILE REPLACEMENT PROJECT) WORK HAS BEEN COMPLETED ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/13/01. CHARLES BUCHANAN - SAFETY (202)576-5582 (RG) |
June 1, 2001 |
February 3, 2006 |
1,708 days |
| Shepherd ES |
FM-200119076 01 2/3/06 SHEPHERD ROOM#201 1. ASBESTOS ASSESSMENT REQUIRED 2. SURVEY ELECTRICAL CAPACITY TO DETERMINE WHETHER THE INSTALLATION OF REPLACEMENT UNITS. 3. INSTALL A/C WINDOW UNIT-14,000 BTU ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/04/01. LEROY MINTON - SAFETY (202)576-6691 (RG) |
September 4, 2001 |
February 3, 2006 |
1,613 days |
| Bowen Elementary School |
FM-200112459 01 2/3/06 BOWEN THIRD FLOOR HALLWAY 1) REPLACE WASH SINK ON THIRD FLOOR HALLWAY SINK LEAKS WATER INTO CLASSROOMS AND ONTO OFFICE FLOOR ASBESTOS CODE A - CLEAR FOR REPAIRS ON 11/30/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
June 5, 2001 |
February 3, 2006 |
1,704 days |
| Whittier Elementary School |
FM-200117762 01 2/3/06 WHITTIER ASST. PRINCIPAL OFFICE - 1ST FLOOR ASBESTOS ASSESSMENT REQUIRED WINDOW WILL NOT SHUT. NEEDS ADJUSTMENT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 08/27/01. RONALD EDWARDS - SAFETY (202)576-6693 |
August 17, 2001 |
February 3, 2006 |
1,631 days |
| Whittier Elementary School |
FM-200116919 01 2/3/06 WHITTIER THROUGHOUT ASBESTOS ASSESSMENT REQUIRED REPAIR / REPLACE WATER FOUNTAINS ON: 1ST FLOOR NEW WING 2 COOLERS NOT WORKING 2ND FLOOR 1 COOLER NOT WORKING 1 HOT WATER 3RD FLOOR 2 NOT WORKING BASEMENT OLD WING: 1 FOUNTAIN NEED REPLACING FROM FIRE. 1ST FLOOR OLD WING: 1 FOUNTAIN NEED REPAIR 2ND FLOOR OLD WING: 1 COOLER NEED KNOBS CODE A - CLEARED FOR REPAIRS 8-31-01 (LM) SAFETY OFFICE 202-576-8962 |
August 8, 2001 |
February 3, 2006 |
1,640 days |
| Terrell Mc ES |
FM-200119139 01 2/3/06 (TERRELL, M.C.) ASBESTOS ASSESSMENT REQ. UPPER GROUND/ CUSTODIAN CLOSET REPLACE (1) SERVICE SINK FAUCET (WALL MOUNTED TYPE) ASBESTOS CODE A - CLEAR FOR REPAIRS ON 09/05/01. RONALD EDWARDS - SAFETY (202)576-6693 (RG) |
September 5, 2001 |
February 3, 2006 |
1,612 days |
| Eliot Junior High School |
FM-200121894 /01 2/3/06 (ELIOT) ASBESTOS ASSESSMENT REQ. 3RD FLOOR/ HALLWAY REPLACE BURNED OUT CIRCUT (#22) BREAKER MAIN HALLWAY 3RD FLOOR CIRCUT BREAKER WILL NOT RESET. HALF OF THE HALLWAY LIGHTS ARE OUT. ALSO CIRCUT BREAKER GIRLS GYM HAS BURNED OPUT. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/22/01. LEROY MINTON - SAFETY (202)576-6691 (RG |
October 18, 2001 |
February 3, 2006 |
1,569 days |
| Cardozo High School |
FM-200115692 01 2/3/06 CARDOZO PAINT SCOREBOARD URGENT !!! LEAD BASE PAINT IS CODE A-CLEAR FOR REPAIR BY CEB 7/27/01 |
July 23, 2001 |
February 3, 2006 |
1,656 days |
| Backus Middle School |
FM-200118868 01 2/3/06 (BACKUS) 3RD FLOOR/ ALL OF THE FLOOR NEED 390 DEFUSER COVERS FOR EGGSHELL CRATE LIGHTS. (SAFETY HAZARD) ISOLATE EMERGENCY!!! |
August 30, 2001 |
February 3, 2006 |
1,618 days |
| Terrell Mc ES |
FM-200122126 /01 2/3/06 (TERRELL, M.C.) 1. ASBESTOS ASSESSMENT REQUIRED. URGENT! REPAIR OR REPLACE GYM FLOOR. IT IS A SAFETY HAZARD. EXISTING FLOOR IS WOOD. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/23/01. HORNE ENGINEERING - SHERON VOSS (RG) |
October 10, 2001 |
February 3, 2006 |
1,577 days |
| Eliot Junior High School |
FM-200201939 02 2/3/06 (ELIOT) ***EMERGENCY*** ASBESTOS ASSESSMENT REQUIRED 1ST FLOOR--CLASSROOM 107 REPLACE PLASTER CEILING TILES (6) WHICH HAVE FALLEN THIS MORNING OVER THE TEACHERS DESK. THE TILES ARE PLASTER & HEAVY (COULD CAUSE SERIOUS INJURY). OTHER SPACES CAN BE SEEN WHERE TILES HAVE FALLEN IN THE PAST. ASBESTOS CODE A-CLEAR FOR REPAIR ON 1/29/02 BY HORNE ENGINEER: RAY AGNANT LEAD BASE PAINT CODE A-CLEAR FOR REPAIR ON 1/29/02 BY HORNE ENGINEER: RAY AGNANT DO NOT SCRAPE CHIP OR PEEL ANY OF THIS PAINT SURFACE RE-PAINT OVER ONLY |
January 28, 2002 |
February 3, 2006 |
1,467 days |
| Moten Elementary School |
FM-200120651 01 2/3/06 (MOTEN) ASBESTOS ASSESSMENT REQ. 4TH FLOOR/ ROOM 405 CHECK FOR ELETRICAL SHORTAGE/ OVERLOAD. BREAKER TRIPS WHEN CLASSROOM LIGHTS ARE TURNED ON. ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/03/01. LEROY MINTON - SAFETY (202)576-6691 |
September 28, 2001 |
February 3, 2006 |
1,589 days |
| Ronald H. Brown MS |
FM-200112400 01 2/3/06 BROWN, RON ROOF 1) PUMP WATER FROM ROOF OVER THE FOLLOWING AREAS: ROOMS 312, 329, 317, STAIRWELL #9 ASBESTOS CODE A - CLEAR FOR REPAIRS ON 10/01/01. LEROY MINTON - SAFETY (202)576-6691 |
June 5, 2001 |
February 3, 2006 |