Urgent Repair Requests Opened in January 2006 (34)
| School |
Description |
Open Date |
| Woodson High School |
FM-200517269 1/9/06 Woodson Room #210 Asbestos assessment required on line. Repair or replace rupture steam line in ceiling by window in room #210.. Can not be isolated Urgent !!!!! Asbestos Code B - on 01/09/06. Tidewater - Tony Marcolin - (RG 01/10/06) Asbestos Code A - Abated and cleared for repairs on 10/20/06 by Goel Construction (LM/02-08-07) Safety Office 202-576-8962 |
January 9, 2006 |
| Turner Elementary School |
FM-200517279 1/9/06 Second floor, Classrooms 203, 205 & 207. "Urgent" Scrape and Plaster entire classrooms to prepare for occupation. Note: This work needs to be done asap! Lead Code B Asbestos Code A - Clear for repairs on 01/09/06. SEE ASSESSMENTS Tidewater - Roger Small ( RG 01/12/06) |
January 9, 2006 |
| Young Elementary School |
FM-200517326 1/11/06 Very Urgent: Check and repair breaker to outside lights; breaker keep tripping and it's dark at front entrance at night. |
January 11, 2006 |
| Cardozo High School |
FM-200517341 1/11/06 Nurse's Suite. "Urgent" Need plumbers to assess and repair problem, there is no hot water in the nurse's suite. Note: This is a matter of urgency. |
January 11, 2006 |
| Young Elementary School |
FM-200517346 1/11/06 Outside-Large Ground By Gym Urgent Repair damaged brick wall on large playground Note: Wall was damage and there loose bricks on the wall |
January 11, 2006 |
| Terrell Mc ES |
FM-200517352 1/11/06 TERRELL, M.C. boiler room URGENT NO HEAT IN SCHOOL!!!!! ASBESTOS ASSESSTMENT REQUIRED Replace mud legs on boilers # 1 and 2 . School has NO HEAT URGENT Asbestos Code A - Clear for repairs on 01/11/06. Tidewater - Roger Small ( RG 01/12/06) |
January 11, 2006 |
| Woodson High School |
FM-200617385 1/12/06 Sixth floor, Teachers' Lounge Restroom. "Urgent" Repair or Replace restroom lock, staff are unable to unlock door to gain entry into the teachers" restroom. |
January 12, 2006 |
| Stuart-Hobson Middle School |
FM-200517364 1/12/06 Very Urgent: Repair the roof leak on the first floor in the hallway across from #3 stairwell on the first floor. |
January 12, 2006 |
| Aiton Elementary School |
FM-200617396 1/13/06 Outside-Parking Lot Urgent Repair the gate; it's off track and hard to pull |
January 13, 2006 |
| Birney Elementary School |
FM-200617408 1/13/06 Second Floor-Rm. 201 Very Urgent Investigate and repair electrical problem with wall outlets; they are not working and the box was checked and there was no respond. |
January 13, 2006 |
| Beers Elementary School |
FM-200617405 1/13/06 Very Urgent: Change outlets to fit the two printers that are being moved to the main office and the conference rooms on the first floor. (See Mr. Lancaster) |
January 13, 2006 |
| Marshall Educational Center |
FM-200617498 1/17/06 First Floor-Upper Gym Urgent Repair or replace the door to the upper gym; it is broken off and hanging. Asbestos Code A - Clear for repairs on 01/18/06. Tidewater - Thomas Johnson (RG 01/19/06) |
January 17, 2006 |
| Benning Elementary School |
FM-200617470 1/17/06 Urgent:Some lights on the outside of the building need to be replaced. |
January 17, 2006 |
| Benning Elementary School |
FM-200617471 1/17/06 Urgent: Second Floor-Girls Restroom Some lights are out |
January 17, 2006 |
| Benning Elementary School |
FM-200617467 1/17/06 Urgent: Lights out on in the note board in front of the building |
January 17, 2006 |
| Eaton Elementary School |
FM-200617552 1/18/06 Eaton Principal Office Room #101 Repair or replace univent that leaks very bad drip pan rusted out. Repair or replace univent motor in room #100 Main Office. Urgent !!!!! |
January 18, 2006 |
| Wilkinson ES |
FM-200617507 1/18/06 Wilkinson Storage Area - (Inside of Boiler Room) Investigate concrete floor in back storage room. Floor is about to collapse. Safety Hazard !!!!! If assist. needed contract Mr. B. Shaw Cell #202-438-6537 Asbestos Code A - Clear for repairs on 01/18/06. Tidewater - Philp Connolly (RG 01/24/06) |
January 18, 2006 |
| Key Elementary School |
FM-200617551 1/18/06 Key Classroom #210 Repair or replace HV/AC with a new drip pan. Drip pan have a large hole inside of the pan, Causing flooding to the classroom area. A/C and Heating not working on all tear. Urgent !!!!! |
January 18, 2006 |
| Stoddert ES |
FM-200617579 1/19/06 Fill large pot hole in the drive way. Urgent |
January 19, 2006 |
| McKinley Technology High |
FM-200617574 74 1/19/06 C Wing- Outside Steps Very Urgent Repair the steps it's falling apart |
January 19, 2006 |
| Bowen Elementary School |
FM-200617614 1/19/06 "Urgent" Exterior Rear of building. Reinstall (1) security light in the rear of the builing, the light fell out of its location (on the roof). Also replace bulbs in the front of building Note: This is a issue of safety. |
January 19, 2006 |
| Brent Elementary School |
FM-200617648 1/20/06 Brent Boiler Room Repair or replace 4" drain line in Boiler Room. Water running down on Boiler room floor, from kitchen sink. Has odor. Urgent !!!! |
January 20, 2006 |
| Stuart-Hobson Middle School |
FM-200617698 1/23/06 Urgent Remove 6x3 plywood/carpet from side of dumpster, it smells of urine. Unsanitary |
January 23, 2006 |
| Walker-Jones EC |
FM-200617749 1/23/06 Exterior of Building/Parking Lot. "Urgent" Unstop storm drain on parking lot water is backing up and standing in large quantities. |
January 23, 2006 |
| Shaw JHS |
FM-200617992 1/25/06 Bandroom corridor: Inadequate light. Fixtures need to be updated very dim in band hallway. SAFETY HAZARD!!! 01/25/06 |
January 25, 2006 |
| Savoy Elementary School |
FM-200617823 0617823 1/25/06 Exterior of entire Building Urgent Investigate and repair problem with lighting, some lights are not functioning at all |
January 25, 2006 |
| Bruce-Monroe Elementary School |
FM-200617799 1/25/06 Bruce-Monroe Old Wing-Mech. Room-(Right Side) Asbestos assessment required Repair or replace leaking pneumatic valve on heating line. Unable to determine size, because of insulation. Urgent !!!! |
January 25, 2006 |
| Turner Elementary School |
FM-200617907 1/26/06 Turner 3rd Floor Room #302 Replace motor in univent. No heat in classroom. Urgent !!!!! |
January 26, 2006 |
| Eliot Junior High School |
FM-200617933 1/26/06 Second floor, Outside of room 212 Asbestos Assessment Required. Repair ceiling grid that was pulled away from wall, which is causing the ceiling tiles to fall. Note: This is a safety hazard. Asbestos Code A - Clear for repairs on 01/27/06. Tidewater - Roger Small (RG 01/30/06) |
January 26, 2006 |
| Key Elementary School |
FM-200617911 1/26/06 Key Room #208 Repair or replace two (2) bad motor that burn out on HVAC units. Type of motors G.E. HP 1/6 Volts 115 Amps 2.20 RPM 1075 HZ 60 PH 1 Come with a capacitor 370 Vac 50/60 HZ No heat or air. Urgent !!!!! |
January 26, 2006 |
| Terrell Mc ES |
FM-200617936 1/27/06 Health Suite - Several ceiling tiles show signs of water stain and should be replaced. Clifton C. Purks, III Code & Compliance Officer (202) 576-6049 Asbestos Code A - Clear for repairs on 01/27/06. DCPS Safety - Richard Gibson (RG) |
January 27, 2006 |
| Browne Junior High School |
FM-200617983 1/27/06 First floor, Room 131 & Second floor, Room231. "Urgent" Need electrician to do an assessment of electrical issue and repair. Half of the outlets in both classrooms have no juice. Note: The staff have already checked the breaker boxes. |
January 27, 2006 |
| Cardozo High School |
FM-200617982 1/27/06 First floor, Room 144/Supply closet. "Urgent" Repair or Replace broken electrical light switch, wires are exposed.. |
January 27, 2006 |
| Ross Elementary School |
FM-200618100 1/31/06 "Urgent" Asbestos Assessment Required. Basement Level, Boiler room. Repair falling ceiling in boiler room asap! Need 1 piece of sheet rock 4' x 8'. Asbestos Code A - Clear for repairs on 02/01/06. Tidewater - Carlos Vera (RG 02/09/06) |
January 31, 2006 |
Routine Repair Requests Opened in January 2006 (105)
| School |
Description |
Open Date |
| Anacostia Senior High School |
FM-200517078 1/2/06 Roof leaking on west side of gym in two areas adjacent to windows. |
January 2, 2006 |
| Anacostia Senior High School |
FM-200517084 1/2/06 Repair hole in roof outside of girls lavatory, on first floor to stop slate from falling. |
January 2, 2006 |
| Randle-Highlands ES |
FM-200517079 1/3/06 Rm 2009 Ground fl. Repair broken window Asbestos Code A - Clear for repairs on 01/04/06. Tidewater - Tony Marcolin (RG 01/05/06) |
January 3, 2006 |
| Gage-Eckington ES |
FM-200517112 1/4/06 First floor, Room 115. Need electricians to assess and repair electrical issue. There are five lights in this room three of the lights are not working, the breaker that control these lights are not working. |
January 4, 2006 |
| Turner Elementary School |
FM-200517102 1/4/06 Repair the radiator in the girls restroom on the second floor (old side of the building) |
January 4, 2006 |
| Turner Elementary School |
FM-200517101 1/4/06 Repair the concrete wall that is deteriorating where the grate is connected to the fence leading to the outside of the cafeteria fence and entrance; and the curb along the fence line. |
January 4, 2006 |
| Hart Middle School |
FM-200517117 1/4/06 Girl's/boys Locker Rm. Shower head. Repair water leak |
January 4, 2006 |
| Spingarn High School |
FM-200517106 1/4/06 Custodian's office Replace 9x9 fl Tile. Asbestos Code D - on 01/10/06. Tidewater - Tony Marcolin ( RG 01/13/06) Code A asbestos was abated 01/18/06 by Motir Construction per Mr. Ringgold comfirmed.(RG 05/15/06) |
January 4, 2006 |
| Spingarn High School |
FM-200517105 1/4/06 Rm 211B Replace damaged fl. Tile Asbestos Code A - Clear for repairs on 01/06/06. Tidewater - Tony Marcolin - (RG 01/10/06) |
January 4, 2006 |
| Birney Elementary School |
FM-200517182 1/5/06 First floor, Breaker Box. Need electrician to assess and repair problem. Circuit breaker is continuously tripping. Note: This breaker (# 16) controls all the phones in the building. |
January 5, 2006 |
| Amidon Elementary School |
FM-200517155 1/5/06 Amidon Rooms 210, and 206 Replace burnt out univent motors in rooms 210 and 206, rooms are cold. Century Motors: RPM 750: Frame: G48Z: open Drip Proof Volts 115: 60 cyl. (4) each |
January 5, 2006 |
| Adams Elementary School |
FM-200517212 1/7/06 ADAMS 1st floor lobby Replace leaking 3/4 inch nipple on the steam supply line on the radiator by the front door in the lobby. Nipple is leaking due to F.W.&T. |
January 7, 2006 |
| Roosevelt High School |
FM-200517213 1/7/06 ROOSEVELT SHS Repair leaking heating coils in the following locations 1. Girls toilet 1st floor 2. Heating/cooling coil mech rm B26 3. Heating/cooling coil mech room 11-11B 4.Heating/cooling coil room 204 5. Heating coils mech room 152 - See Engineer |
January 7, 2006 |
| Marshall Educational Center |
FM-200517231 1/7/06 Asbestos Assessment Required. Repair or Replace library doors. Note: The doors will not open. Asbestos Code A - Clear for repairs on 01/10/06. Tidewater - Thomas Johnson ( RG 01/10/06) |
January 7, 2006 |
| Terrell Mc ES |
FM-200517214 1/7/06 Terrell, M.C. Boiler room Repair Boiler # 2 , Cuts off on flame failure. |
January 7, 2006 |
| Benjamin Banneker Academic HS |
FM-200517245 1/8/06 Banneker Boiler room Repair or replace condensate return pump # 3 unit is leaking from seals.( loosing returns) |
January 8, 2006 |
| Garfield ES |
FM-200517252 1/9/06 Garfield Boiler Room - Behind Boiler Ceiling Replace Bell & Gossett Centifugal pump, leaking continuously. Size: P.D.35S MZ Mod. # 105089 Ser. # 1124817 Motor- HP 1/2 RPM 1725 HZ 60 Volts 115/230 Amp 6.0/3.0 S.F. 125 S.F. Amp 7.0/3.5 C. Rating 40 F Thermal Protection M74791 Part # M80066 Pump is used to serve auditorium, music room, library and restroom near Boiler Room. |
January 9, 2006 |
| Hyde Elementary School |
FM-200517271 1/9/06 Basement & Second floor. Repair or Replace utility sink in basement area across from boilerroom, also Repair or Replace utility sink in custodial closet on second floor. |
January 9, 2006 |
| Tyler Elementary School |
FM-200517254 1/9/06 Tyler Boiler room Replace soleniond valve on condensate make up line, valve stuck open |
January 9, 2006 |
| Patterson ES |
FM-200517251 1/9/06 Patterson Exterior Driveway Entrance South Capitol Side Install prefabricated gate to lock to prevent illegal dumping in school trash dumpsters. Please install similar gate that is on the attached photo. |
January 9, 2006 |
| Benjamin Banneker Academic HS |
FM-200517274 1/9/06 Basement floor, Kitchen Area. Repair broken valve on hot water heater, in kitchen area. |
January 9, 2006 |
| Ketcham Elementary School |
FM-200517266 1/9/06 Ketcham Boiler Room Repair or replace air compressor, not working. |
January 9, 2006 |
| Patricia R Harris Ed Center |
FM-200517299 1/10/06 Second Floor-Kitchen Emergency Replace light fixtures inside walk in box. The fixture can't be repaired. |
January 10, 2006 |
| Hine JHS |
FM-200517348 1/11/06 Playground Area-Install traffic calming device on playground by entrance door. |
January 11, 2006 |
| Hine JHS |
FM-200517349 1/11/06 Exterior-Enhance exterior lighting around building |
January 11, 2006 |
| Ballou Senior High School |
FM-200617486 1/11/06 Asbestos Assessment Required. Survey, furnish and install materials for wall breach, to prevent male student access to female locker room Note: This is a (Fire code violation). Asbestos Code A - Clear for repairs on 01/20/06. Tidewater - Thomas Johnson (RG 01/24/06) |
January 11, 2006 |
| Jessie LaSalle Elementary |
FM-200617387 1/12/06 Exterior front of building near mechanical shop. Install wire mesh over light fixtures, to prevent bulbs from being broken out, |
January 12, 2006 |
| Dunbar High School |
FM-200517377 1/12/06 Dunbar ROTC Armory Repair or replace back of stabilizing bar on basketball hoop in ROTC Armory. |
January 12, 2006 |
| Beers Elementary School |
FM-200517357 1/12/06 Beers Room 104 Replace burnt out motor in room 104. Need Electrician Restore electrical service to univent. |
January 12, 2006 |
| Browne Junior High School |
FM-200517368 1/12/06 Emergency: Raised floor outlet is shorting out and shooting sparks; Repair or Remove there is a metal table right beside the outlet in the kitchen on the first floor. |
January 12, 2006 |
| John Burroughs ES |
FM-200617503 1/12/06 First floor, Room K73. Need electricians to assess and repair electrical problem, outlet does not work. |
January 12, 2006 |
| Randle-Highlands ES |
FM-200617403 1/13/06 Urgnet: Run a electrical line to the outdoor school sign on Penn. and R St. Side of the building Asbestos Code A - Clear for repairs on 01/17/06. Tidewater - Roger Small (RG 01/18/06) |
January 13, 2006 |
| Johnson JHS |
FM-200617394 1/13/06 Johnson Security Office Replace missing squirrel cage and coil in security office. |
January 13, 2006 |
| Brookland Elementary |
FM-200617397 1/13/06 Third Floor-Mr. Jones Class Urgnet Investigate and repair three outlets; they are not working. |
January 13, 2006 |
| Meyer Elementary School |
FM-200617415 1/13/06 Repair the locks on the following classrooms: Second Floor-Rms. 205 and 207 First Floor-Rm. 116 Basement-Rm. 13 |
January 13, 2006 |
| Rudolph Elementary School |
FM-200617393 1/13/06 Rudollph Entrance to boiler room. Repair or replace light at the entrance to the boiler room, area is dark. |
January 13, 2006 |
| Browne Junior High School |
FM-200617455 1/17/06 Second Floor - Room 203 - Door hinges need to be adjusted and needs a door handle. Second Floor - Boys Restroom across from - Room 207- Door needs door closer and handle. Asbestos Code A - Clear for repairs on 01/17/06. Tidewater - Thomas Johnson (RG 01/19/06) |
January 17, 2006 |
| Jessie LaSalle Elementary |
FM-200617750 1/17/06 Repair blowers in the following classrooms (#32,#132and #207). |
January 17, 2006 |
| Park View ES |
FM-200617499 1/17/06 First Floor-Boys Restroom Urgnet Scrape and paint the ceiling Lead & Asbestos Code A - Clear for repairs on 01/19/06. Tidewater - Roger Small (RG 01/20/06) |
January 17, 2006 |
| Randle-Highlands ES |
FM-200617427 1/17/06 Randle Highland Boiler room Replace leaking relief valve on the # 5 boiler. Model # M3, 174 A, Size: 3/4, Set 80 lb., BTU/HR Rating 1,400,000 |
January 17, 2006 |
| Benning Elementary School |
FM-200617466 1/17/06 Flag pole need ropes and lock boxes at the front of the building. |
January 17, 2006 |
| Thomas Elementary School |
FM-200617430 1/17/06 Thomas N. Roof over cafeteria storeroom Replace defective dome style exhaust fan and motor. |
January 17, 2006 |
| Patterson ES |
FM-200617493 1/17/06 Loading Dock-Kitchen Door Replace broken glass cover for light |
January 17, 2006 |
| Winston EC |
FM-200617494 1/17/06 Second Floor-Rm. 233 Replace Ceiling (drywall) over exit sign near room 233 Asbestos Code A - Clear for repairs on 01/18/06. Tidewater - Roger Small (RG 01/19/06) |
January 17, 2006 |
| Barnard Elementary School |
FM-200617538 1/18/06 Restore electrical. power to the cafeteria electrical. panel. |
January 18, 2006 |
| Ferebee-Hope Elementary School |
FM-200617512 1/18/06 Ferebee-Hope Boiler room Provide parts and materials to repair burner on Boiler #1. |
January 18, 2006 |
| Ballou Senior High School |
FM-200617757 1/18/06 Survey:stairwell doors for replacement of glass at the bottom portion with plywood sheetmetal to eliminate-(vandalizum)breakage. Asbestos Code A - Clear for repairs on 01/27/06. Tidewater - Carlos Vera (RG 01/27/06) |
January 18, 2006 |
| Hine JHS |
FM-200617543 1/18/06 Hine Roof Repair or replace busted make-up water line to cooling tower |
January 18, 2006 |
| Key Elementary School |
FM-200617549 1/18/06 Key Classroom #208 Repair or replace two bad motors that burn out on HV/AC units. Type of motors GE HP 1/6 Volts 115 Amps 2.20 RPM 1075 HZ 60 PH 1 Comes with a capacitor 370 Vac 50/60 HZ. Hot !!!! |
January 18, 2006 |
| Kenilworth ES |
FM-200617508 1/18/06 Burrville Room #310 Asbestos assessment required on univent bearing. See sample. Asbestos Code A - Clear for repairs on 02/16/06. Tidewater - Carlos Vera (RG 02/17/06) |
January 18, 2006 |
| Truesdell Elementary |
FM-200617526 1/18/06 Ground-Kitchen (Storage Area) Emergency Water leaking through the ceiling causing a flood. Assess and isolate the emergency Asbestos Code A - Clear for repairs on 01/18/06. Tidewater - Shamika Parker (RG 01/20/06) |
January 18, 2006 |
| Merritt Middle School |
FM-200617562 1/18/06 Exterior-Back of School Unstop drain and replace cover |
January 18, 2006 |
| Meyer Elementary School |
FM-200617578 1/19/06 Flag Pole-Need new rope; the rope has been cut off the flag pole. |
January 19, 2006 |
| Beers Elementary School |
FM-200617594 1/19/06 Beers 108 - Building 2 Replace motor on univent, motor bad unit will not put out any heat. Stock #3134 HP 1/8 Volts 118 Amp 2.00 RPM 700 |
January 19, 2006 |
| McKinley Technology High |
FM-200617575 75 1/19/06 Repair or replace three water fountains on the second floor and one on the lower level by gym-they are not working. |
January 19, 2006 |
| Bruce-Monroe Elementary School |
FM-200617591 1/19/06 Bruce-Monroe Old side Auditorium Repair or replace air handler unit. Broken shaft. Hot !!!! |
January 19, 2006 |
| Stoddert ES |
FM-200617657 1/20/06 Exterior of the building Repair Exterior (siding) |
January 20, 2006 |
| Woodson High School |
FM-200617618 1/20/06 Woodson Swimming Pools On going Pool maintenance Chemical treatment, backwash of filter system and pump PM, Vacuum pools and check all related equipment. |
January 20, 2006 |
| Marshall Educational Center |
FM-200617617 1/20/06 Marshall Swimming Pools On going Pool maintenance Chemical treatment, backwash of filter system and pump PM, Vacuum pools and check all related equipment. |
January 20, 2006 |
| Ferebee-Hope Elementary School |
FM-200617616 1/20/06 Ferebee-Hope Swimming Pools On going Pool maintenance Chemical treatment, backwash of filter system and pump PM, Vacuum pools and check all related equipment. |
January 20, 2006 |
| Brent Elementary School |
FM-200617647 1/20/06 Brent Classrooms #108;#204 and #305 Repair or replace motors in the following classrooms: #108; #204 and #305 GE Motor Model #5K4390N942AT HP 1/3-1/9 HZ 60 Volts 115 PH 1 RPM 1725/1140 Frame 48 SF 1.00 Cod R 2) Replace squirrel cage bearing on univent # 1 in room 108. 3) Secure vent louver on top of univets in room 108. |
January 20, 2006 |
| Eliot Junior High School |
FM-200617679 1/22/06 Eliot Library Repair or replace univent motor in the Library. The Holtzer Cabet Electric Co. #875752 Frame RWC6417 Volts 110/220 Amp 1.8/.9 Phase 1 HP 1/15 RMP 825 Cycle 60 Time BTM1 |
January 22, 2006 |
| Roosevelt High School |
FM-200617666 1/22/06 Roosevelt Mechanical Room #15 Replace backflow preventer to make up feed water valve, |
January 22, 2006 |
| Hart Middle School |
FM-200617725 1/23/06 Emergency No Lights Rooms: 216, 224, 117, and 226 |
January 23, 2006 |
| Wilkinson ES |
FM-200617739 1/23/06 First floor, Room K-18 Kindergarden/General Storage Area. Remove old insullation thats falling and replace insullation on duct work. Asbestos Code A - Clear for repairs on 01/24/06. Tidewater - Tony Marcolin(RG 01/27/06) |
January 23, 2006 |
| Turner Elementary School |
FM-200617743 1/23/06 Turner Classroom #115,#207, #205 and #317 Repair or replace (2) two motors for room #115,#205,#207 and #317 Type of motor GE Motor STK #4319 HP-1/3 - 1/8 Volts 115 5KH39QN9429AT |
January 23, 2006 |
| Burrville Elementary School |
FM-200617693 1/23/06 Burrville Boiler room Replace Pneumatic controls on both Heat Exchangers and calbrate to work inconjuntion with outside air temperture controls to resolve the over heating of hot water heating system. |
January 23, 2006 |
| Kimball Elementary School |
FM-200617756 1/23/06 Urgnet Classroom 204-Broken Window Pane-Entrance Door Asbestos Code A - Clear for repairs on 01/24/06. Tidewater - Tony Marcolin(RG 01/27/06) |
January 23, 2006 |
| Ludlow-Taylor ES |
FM-200617734 1/23/06 Second Floor-Rm. 218: Need a key made Third Floor-Rm. 305: Repair damaged lock |
January 23, 2006 |
| Ludlow-Taylor ES |
FM-200617747 1/23/06 Ludlow-Taylor Boiler Room Repair or replace I,D, Fan for Boiler #1, bad motor. |
January 23, 2006 |
| Deal Junior High School |
FM-200617796 1/24/06 Insulate the following exposed steam lines to prevent students from getting burnt: The Main Office and classrooms, 209, 211, 213, 215, 217, 203, 205A, 205B, 207, 201, 200, 202, 204, 206, 208, 210B, 210A, 212, 214, 216, 109, 115, 105, 107, 107B 102, 104, 108, 110, 112, 116, 124B. Asbestos Code A - Clear for repairs on 01/30/06. Tidewater - Carlos Vera (RG 01/31/06) |
January 24, 2006 |
| Patricia R Harris Ed Center |
FM-200617782 1/24/06 Harris, P.R. Auditorium Repair air handler unit for Auditorium. |
January 24, 2006 |
| Patricia R Harris Ed Center |
FM-200617777 1/24/06 Replace blown ballasts in the following areas: (277 rapid start) 1.) Restroom in big gym (girls) 2.) Restroom nest to stairwell # 8, 1st floor (girls). 3.) Restroom teachers' 3rd floor. Note: Ballasts are on job site. |
January 24, 2006 |
| Shepherd ES |
FM-200617792 1/24/06 Exterior rear of building near cafeteria. Install drain in airway near cafeteria. |
January 24, 2006 |
| Shaed Elementary School |
FM-200617807 1/25/06 Ground Floor/First Floor Replace 1x1 tiles that are damaged due to "pipe burst". See Mr. Wilson Asbestos Code A - Clear for repairs on 01/27/06. Tidewater - Tony Marcolin (RG 01/30/06) |
January 25, 2006 |
| Savoy Elementary School |
FM-200617820 0617820 1/25/06 First Floor-Multipurpose Room Replace all broken electrical outlets. (total of 8) |
January 25, 2006 |
| Turner Elementary School |
FM-200617817 1/25/06 Second Floor-Rm. 201 Install electrical outlet for washer and dryer (upgrade) Asbestos Code A - Clear for repairs on 01/27/06. Tidewater - Carlos Vera (RG 01/30/06) |
January 25, 2006 |
| Walker-Jones EC |
FM-200617815 1/25/06 Outside-Parking Lot Urgnet Unclog drain on the parking lot there is standing water |
January 25, 2006 |
| Whittier Elementary School |
FM-200617818 1/25/06 Replace water spout From the roof, it broke off due to heavy rain. When it rains the water leaks inside the auditorium. |
January 25, 2006 |
| Maury Elementary School |
FM-200617804 1/25/06 New Building-Security doors need pad locks |
January 25, 2006 |
| Shaw JHS |
FM-200617990 1/25/06 Replace soundproof glass on music room door 01/25/06 |
January 25, 2006 |
| Shaed Elementary School |
FM-200617811 1/25/06 First Floor-Special ED Office Repair Duet to heat and air vent due to "pipe burst". |
January 25, 2006 |
| Bowen Elementary School |
FM-200617931 1/26/06 First, Second, and Third floors/Entire Interior. Asbestos Assessment Required. Scrape and paint entire interior of building. Lead Code A - Clear for repairs on 02/02/07. Tidewater - Roger Small (RG 02/05/07) |
January 26, 2006 |
| Cook J.F. Elementary School |
FM-200617996 1/26/06 The air conditioner window units in room 301 are not working. The units are not blowing out cool air. |
January 26, 2006 |
| Johnson JHS |
FM-200617872 1/26/06 Johnson JHS Health Suite - Electrical floor outlet has cover missing and one section protruding causing a trip hazard. Clifton C. Purks, III Code & Compliance Officer (202) 576-6049 |
January 26, 2006 |
| Johnson JHS |
FM-200617871 1/26/06 Johnson JHS Health Suite - Resting room had ceiling tile missing and several show signs of water damage. Clifton C. Purks, III Code & Compliance Officer (202) 576-6049 Asbestos Code A - Clear for repairs on 01/27/06. Tidewater - Carlos Vera (RG 01/30/06) |
January 26, 2006 |
| Brookland Elementary |
FM-200617914 1/26/06 Brookland Outside Lightening Repair or replace outside lights in rear of building. Area is very dark and unsafe. |
January 26, 2006 |
| Johnson JHS |
FM-200617915 1/26/06 Johnson Heat Start Check room #200 (Head Start) No heat in classroom. Note: Electricians are needed to rewire motor.No neutral wire to motor |
January 26, 2006 |
| Whittier Elementary School |
FM-200617975 1/27/06 WHITTIER boiler room Repair circulating pump # 1 located in boiler pump room. Pump will not start-up. Note: Both pumps are needed to properly heat building (new side). |
January 27, 2006 |
| Ballou Senior High School |
FM-200617943 1/27/06 Health Suite - Restroom hole in plaster wall from plumbing repairs, repair hole. Clifton C. Purks, III Code & Compliance Officer (202) 576-6049 HA 018 Wall board white drywall No Asbestos Code A-clear for repair by DCPS Charles Buchanan on 3/23/06 |
January 27, 2006 |
| Gibbs Elementary School |
FM-200617949 1/27/06 Replace roofs of all overhangs to prevent any further water penetration. Replace ceilings of all overhangs. Have a Structural Engineer access the condition of all overhangs. The underside of the roof or ceiling area is composed of wire mesh that has been covered with brown coat stucco. Due to water leaks the wire mesh has deteriorated. Clifton C. Purks, III Code & Compliance Officer (202) 576-6049 Asbestos Code A - Clear for repairs on 01/27/06 Tidewater - Philp Connolly (RG 02/08/06) |
January 27, 2006 |
| Plummer Elementary School |
FM-200617986 1/27/06 Roof, Top of Cafeteria outside. Replace (3) broken light fixtures. |
January 27, 2006 |
| Peabody Elementary School |
FM-200617998 1/29/06 Peabody Boiler room Check and make adjustments on the pump controls,and condensate return pumps, pumps are not putting returns back in boilers. |
January 29, 2006 |
| Ross Elementary School |
FM-200618003 1/30/06 Basement - Cafeteria Area - No lights ( checked all switches. ) |
January 30, 2006 |
| Woodson High School |
FM-200618035 1/30/06 Emergency! Ground Floor-Bandroom doors are unsecure and all equipment is in the room, door can't be locked. Repair or replace locks on the door. See Mr. Jones |
January 30, 2006 |
| Anacostia Senior High School |
FM-200618192 1/30/06 Asbestos Assessment Required. The following rooms have severe plaster damage do to roof leaks:boys bathroom 3rd fl.,301,312,307,306,201,239,202,209,231,121,222,126,cafeteria,1st&2nd fl. inner walls,and 3rd fl. hall ceiling Lead & Asbestos Code A - Clear for repairs on 03/08/06 Tidewater - Roger Small (RG 03/10/06) |
January 30, 2006 |
| Whittier Elementary School |
FM-200618002 1/30/06 Whitter Boiler Room Repair condensate ,and circulating pump in the boiler room. |
January 30, 2006 |
| Eliot Junior High School |
FM-200618083 1/31/06 Eliot Room #110, 111, 214,201 and 212 Replace univent motors (Burnt out) A.O. Smith Serial #40T8 Model #HF4H009 HZ 60 Volts 115 RPM 700 SP PH 1 CAP HP 118 AMPS 2.5 Stock 0547 |
January 31, 2006 |
| Reed LC |
FM-200618096 1/31/06 Exterior Walls - Remove graffiti from the exterior walls of the building. |
January 31, 2006 |
| Ferebee-Hope Elementary School |
FM-200618085 1/31/06 Unclog drain in Computer Lab and Outside sewer by Kitchen parking lot and outside storm drain. Poc - Charles Buchanan - 576-5560 Code A-clear for repair by DCPS Charles Buchanan on 1/31/06 |
January 31, 2006 |
| McKinley Technology High |
FM-200618068 1/31/06 DSTV @ Mckinley (South Campus) Replace sliding doors on all of the edit suites on both floors. Sound proof glass and conventional open doors with power shut is needed with Writings or inscriptions on the glass (the station emblem engraved in the glass doors to the edit suites). |
January 31, 2006 |
| Dunbar High School |
FM-200618063 1/31/06 Dunbar Boiler Room Sump pump not working. Need electrician. Emergency !!!!!!! |
January 31, 2006 |
| Eliot Junior High School |
FM-200618078 1/31/06 Eliot Rooms #104, #106 Replace Bad univent motor (burned out) A.O. Smith Serial 407B Volts 115 RPM 700 Mod. HF4H005 HZ 60 SP PH 1 CAP HP 118 AMPS 2.5 sTOCK 0547 |
January 31, 2006 |
| Eliot Junior High School |
FM-200618082 1/31/06 Eliot Room #103 Replace univent motors (Burnt out) The Holtzer Cabot Electric Co. NO875961 Frame RWC6417 Volts 110/220 Amps 1.8/1.9 Phase 1 RPM 825 Cycles 60 |
January 31, 2006 |
| Webb Elementary School |
FM-200618080 1/31/06 "Emergency" Roof, First floor/Vice Principal's Office. Repair roof leak, water is coming through light fixtures into Vice Principal's office. |
January 31, 2006 |