Open Repair Requests in March 2004

Open Repairs Summary

  • Urgent Requests
    24
  • Routine Requests
    128
  • Total Requests
    152

Detailed Reports

Urgent Repair Requests Opened in March 2004 (24)
School Description Open Date
Birney Elementary School FM-200444655 3/2/04 Birney Boiler Room Repair or replace safety valve on domestic hot water heater. March 2, 2004
Ferebee-Hope Elementary School FM-200444856 3/5/04 Ferbee-Hope Boiler room Survey and replace circiut breaker for the # 2 condensate pump, the present breaker do not fit in the cabinet. ( safety Hazzard ) Asbestos Code A - Clear for repairs on 03/05/04. Horne Engineering - Sheryll James (RG 03/09/04) March 5, 2004
Coolidge High School FM-200444860 3/5/04 Coolidge Tunnel Area Repair or replace 1 1/2" busted steam supply line in tunnel. Pipe is leaking under electrical vault and several classrooms do not have heat. Urgent !!! March 5, 2004
Terrell Mc ES FM-200445119 3/8/04 (Terrell, M.C.) Asbestos Assessment Required. Main Entrance (electronic door) sticks and is very hard to open. Problem may be door hinge which will be a fire code violation if not repaired. Asbestos Code A - Clear for repairs on 03/24/04. DCPS Safety - Richard Gibson (RG) March 8, 2004
Turner Elementary School FM-200445032 3/9/04 (Turner) !!!VERY URGENT!!! Asbestos Assessment Required. 2nd & 3rd Floor/Rooms #203, &306: Replace classroom door with new security door too prevent vandals breaking in, and destroying property.. Asbestos Code A - Clear for repairs on 03/09/04. Horne Engineering - Bjame Smith (RG 03/11/04) March 9, 2004
Gibbs Elementary School FM-200445169 3/10/04 (Gibbs) !!!URGENT!!! Asbestos Assessment Required. Kitchen Storage Room: Replace entrance door to the kitchen storeroom Code A with condition - Do not disturb the insulation Horne Engineering - Philp Connolly (RG 03/10/04) March 10, 2004
Truesdell Elementary FM-200445155 3/10/04 (Truesdell) !!!URGENT!!! 1st Floor/Room #114: Repair wall that is separating from the joint of the wall. Asbestos Code A - Clear for repairs on 03/12/04. Horne Engineering - Bipin Nanavaty (RG 03/15/04) March 10, 2004
Patricia R Harris Ed Center FM-200445168 3/10/04 (Harris) !!!URGENT!!! Main Floor/Girls Locker Room: Two (2) toilets in girls restroom running over, snaking did not reolve the problem. March 10, 2004
Patricia R Harris Ed Center FM-200445338 3/12/04 Harris, P.R. Stairwell # 8 doors on the stairs The door jam is broken and the door just slams and has alreadt hurt one person. Asbestos Code A - Clear for repairs on 03/15/04. Horne Engineering - Philp Connolly (RG 03/17/04) March 12, 2004
Lafayette Elementary School FM-200445385 3/15/04 Lafayette Outside front Fabricate and install grate in front of building brside gas equipment. Grate size 18"x5 1/2" Asbestos Code A - Clear for repairs on 03/16/04. DCPS Safety - Leory Minton (RG 03/16/04) March 15, 2004
Seaton Elementary School FM-200445492 3/17/04 Seaton URGENT Second floor fire door to stairwell Upside - fire door is over lapping and hard to push ope. Asbestos Code A - Clear for repairs on 03/18/04. Horne Engineering - Tony Marcolin (RG 03/22/04) March 17, 2004
Seaton Elementary School FM-200445497 3/17/04 Seaton URGENT First floor outdoor lab Large hole in ground maybe a well. Area is used by children and teachers. March 17, 2004
Stanton Elementary School FM-200445488 3/17/04 Stanton Urgent !! Roof - Room - 308 1) Water is leaking from the ceiling. March 17, 2004
Seaton Elementary School FM-200445500 3/17/04 Seaton URGENT Second floor girls bathroom Replace partition to stall near window. partition is in house. Asbestos Code A - Clear for repairs on 03/18/04. Horne Engineering - Tony Marcolin (RG 03/22/04) March 17, 2004
Seaton Elementary School FM-200445496 3/17/04 Seaton URGENT Grounds parking lot Repair concrete wall, replace needed poles and repair fence and sliding gate. Can not secure gate-cars are being abandon, trash dumpster is being used. Parking lot is being used for a motel. March 17, 2004
Reed LC FM-200445585 3/19/04 Reed Ground exterior steps near basketball court Install two (2) gates so this area can be control by school staff. ASAP Safety and health March 19, 2004
Horace Mann Elementary School FM-200445593 3/19/04 Mann Urgent !!!! Entrance Door in the Back 1) Repair or replace door that is bent...Door can not be secured. Asbestos Code A - Clear for repairs on 03/22/04. Horne Engineering - Nanavaty Bipin (RG 03/24/04) March 19, 2004
Truesdell Elementary FM-200445762 3/24/04 Truesdell Room #301 Replace (2) traps for Herman Nelson univent (Trap is N2-17C ITT) in room #301 Note: Traps are 3/4". No heat. Urgent !!!! March 24, 2004
Hine JHS FM-200445937 3/26/04 Hine Fourth and third floor stairwell # 2 Replace fire safety glass to fire doors (2). March 26, 2004
Beers Elementary School FM-200446117 3/30/04 Beers URGENT DANGER Emergency Second floor bldg # 2 Room 208 ceiling need plaster and painting - paint dropping from the ceiling over the children desks. Parents and teachers are complaining. Asbestos Code A - Clear for repairs on 03/31/04. Horne Engineering - Edward Rodriguez (RG 04/06/04) March 30, 2004
Langdon Elementary School FM-200446125 3/30/04 Langdon ES Pressure wash all interior and exterior surfaces of the cooling tower Clean all spray nozzles and/or grommets. Replace all eliminators Inspect and properly adjust all floats Perform preventive maintenance on all auxiliary equipment (including but not limited to: greasing motors, replacing all belts, etc.) Clean all debris from jobsite Replace, as necessary, defective spray nozzle and/or grommet each Replace, as necessary, defective floats ach Poc - Jay Dolphin - 576-3364 Asbestos Code A - Clear for repairs on 03/31/04. DCPS Safety - Richard Gibson (RG) March 30, 2004
Shaw JHS FM-200446119 3/30/04 Shaw Pressure wash all interior and exterior surfaces of the cooling tower Clean all spray nozzles and/or grommets. Replace all eliminators Inspect and properly adjust all floats Perform preventive maintenance on all auxiliary equipment (including but not limited to: greasing motors, replacing all belts, etc.) Clean all debris from jobsite Replace, as necessary, defective spray nozzle and/or grommet each Replace, as necessary, defective floats each Poc - Jay Dolphin - 576-3364 Asbestos Code A - Clear for repairs on 03/31/04. DCPS Safety - Richard Gibson (RG) March 30, 2004
Young Elementary School FM-200446121 3/30/04 Charles Young ES Pressure wash all interior and exterior surfaces of the cooling tower Clean all spray nozzles and/or grommets. Replace all eliminators Inspect and properly adjust all floats Perform preventive maintenance on all auxiliary equipment (including but not limited to: greasing motors, replacing all belts, etc.) Clean all debris from jobsite Replace, as necessary, defective spray nozzle and/or grommet each Replace, as necessary, defective floats each Poc - Jay Dolphin - 576-3364 Asbestos Code A - Clear for repairs on 03/31/04. DCPS Safety - Richard Gibson (RG) March 30, 2004
Ludlow-Taylor ES FM-200446124 3/30/04 Ludlow-Taylor ES Pressure wash all interior and exterior surfaces of the cooling tower Clean all spray nozzles and/or grommets. Replace all eliminators Inspect and properly adjust all floats Perform preventive maintenance on all auxiliary equipment (including but not limited to: greasing motors, replacing all belts, etc.) Clean all debris from jobsite Replace, as necessary, defective spray nozzle and/or grommet each Replace, as necessary, defective floats each Poc - Jay Dolphin - 576-3364 Asbestos Code A - Clear for repairs on 03/31/04. DCPS Safety - Richard Gibson (RG) March 30, 2004

Routine Repair Requests Opened in March 2004 (128)
School Description Open Date
Garrison ES FM-200444641 41 3/1/04 (Garrison) 2nd Floor/Girls Restroom: Bradley basin will not shut off, shut-off valve not working. March 1, 2004
Hart Middle School FM-200444608 3/1/04 (Hart) 1st Floor/Room #123: Replace broken window. March 1, 2004
Thomas Elementary School FM-200444612 3/1/04 (Thomas) Asbestos Assessment Required. 1st Floor/Kitchen: Survey plaster, and paint ceiling over steam table. Lead & Asbestos Code A - Clear For Repairs On 03/02/04. Horne Enginering - Edward Rodriguez (03/03/04) March 1, 2004
Davis Elementary School FM-200444587 3/1/04 DAVIS fIRST FLOOR BOYS BATHROOM BY 117 iISTALL SINK BACK ON WALL AND REPLACE DAMAGE FAUCET, SINK KEEPS FALLING OFF WALL. Asbestos Code A- Clear for repairs on 03/01/04. Horne Engineering - Bipin Nanavaty (RG 03/02/04) March 1, 2004
Davis Elementary School FM-200444589 3/1/04 DAVIS Bathroom BOYS BATHROOM new wing Furnish and install a new sink, old broke the old sink off wall. Asbestos Code A- Clear for repairs on 03/01/04. Horne Engineering - Bipin Nanavaty (RG 03/02/04) March 1, 2004
Gibbs Elementary School FM-200444583 3/1/04 Gibbs Outside Rails leading ro boy restroom outside from playground need repairing. March 1, 2004
Ferebee-Hope Elementary School FM-200444690 3/2/04 Ferebee-Hope Pool Locker Room (Mens) 1.Asbestos assessment required 2.Repair and replace ceiling in mens locker room 3.Repair shower drains in Womens shower area 4.Repair light fixture and check all related wiring Asbestos Code A - Clear for repairs on 03/04/04. Horne Engineering - Philp Connolly (RG 03/08/04) March 2, 2004
Duke Ellington School FM-200444667 3/2/04 Ellington South side of Building (Tunnel) Repair or replace 1" or 1 1/4" leaking steam line in tunnel of south side of Building, over water meter. March 2, 2004
Whittier Elementary School FM-200444709 3/2/04 (Whittier) 1st Floor/Cafeteria: Replace two (2) wire mesh glass in cafeteria door. March 2, 2004
Truesdell Elementary FM-200444686 3/2/04 (Truesdell) Asbestos Assessment Required. 1st Floor/Multipurpose Room: Floor damaged, buckled, and raised ten (10) inches high at exit door. Asbestos Code A - Clear for repairs on 03/03/04. Horne Engineering - Edward Rodriguez (RG 03/08/04) March 2, 2004
Benjamin Banneker Academic HS FM-200444786 3/3/04 Banneker First and second floor rooms 105 and 206 Room 105 need electrician to install more electrical outlets. Also floor outlets in 206 are inoperable, 104 electrical outlets sometimes malfunctions. Asbestos Code A - Clear for repairs on 03/04/04. Horne Engineering - Tony Marcolin (RG 03/08/04) March 3, 2004
Tubman Elementary School FM-200444783 3/3/04 Tubman Teachers lounge Repair / replace cabinets in kitchen. Asbestos Code A - Clear for repairs on 03/05/04. Horne Engineering - Bjame Smuth (RG 03/09/04) March 3, 2004
Browne Junior High School FM-200444752 3/3/04 Browne First floor room 127 Remove electrical plugs from floor. March 3, 2004
Browne Junior High School FM-200444751 3/3/04 Browne Outside roof Repair electrical lights over driveway. March 3, 2004
Browne Junior High School FM-200444748 3/3/04 Browne Throughout bldg. Repair or replace exit lights. Asbestos Code A - Clear for repairs on 03/03/04. Horne Engineering - Bipin Nanavaty (RG 03/08/04) March 3, 2004
Patricia R Harris Ed Center FM-200444785 3/3/04 Harris, P.R. First floor kitchen walk-in boxes Need electrician to restore power back to walkin boxes in kitchen and install flourescent lights, Walkin box #F-1 and box # R-2. Please look at numbers of the kitchen inspection sheet. 2nd request for repairs to be done. Asbestos Code A - Clear for repairs on 03/04/04. Horne Engineering - Sheryll James (RG 03/08/04) March 3, 2004
Coolidge High School FM-200444818 3/4/04 Coolidge Exterior of bldg. Install downspouts in courtyard area near auditorium. March 4, 2004
Gage-Eckington ES FM-200444881 3/5/04 Gage-Eckington Outside ramp leading to entrance Ramp to main entrance doorthe wood is weather beaten, splinters get in kids, visitors whom ever touch the rail. Need to be replace or refinished (wood rail). Ramp is crack up wear a hole has developed where someone will fall into. Cement ramp. Code A - clear for repairs as of /17/04 Sylvia Grimes March 5, 2004
Patricia R Harris Ed Center FM-200444973 3/8/04 Harris, P.R. Termites are bad. EMERGENCY March 8, 2004
Cardozo High School FM-200444959 3/8/04 (Cardozo) Asbestos Assessment Required. 3rd Floor/Room #320-A: Assess for lead in walls, and ceiling , request painting. Lead Code B Asbestos Code A - Clear for repairs on 03/09/04. Horne Engineering - Edward Rodriguez (RG 03/11/04) SEE LINKED DOCUMENTS March 8, 2004
Stoddert ES FM-200444964 3/8/04 Stoddert Attic Repair or replace building main exhaust fan. Asbestos Code A - Clear for repairs on 03/23/04. Horne Engineering - Bipin Nanavaty (RG 03/24/04) March 8, 2004
Backus Middle School FM-200444968 3/8/04 Backus Emergency !!!! Third Floor - 316 1) Window is out and hanging down. March 8, 2004
Turner Elementary School FM-200445082 3/9/04 Turner ( Maintenance T School Blitz ) Rooms - 100,109,201,202,203,204,205,305,307, and First Floor - Girls Bathroom . 1) Scrape and paint ceilings. Approx size - 34'x31' ) Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Bancroft Elementary School FM-200445078 3/9/04 Bancroft First floor auditorium Check the wall for loose plaster that felt and plaster. (FCV) Asbestos Code A - Clear for repairs on 03/17/04. Horne Engineering - Bipin Nanavaty (RG 03/17/04) March 9, 2004
Davis Elementary School FM-200445095 3/9/04 Davis ( Maintenance T School Blitz ) Rooms - 100,101,105,106,108, Kindergardens and Pre-K. 1) Install Carpet. Asbestos Code A - Clear for repairs on 03/11/04. Horne Engineering - Tony Marcolin (RG 03/17/04) SEE LINKED DOCUMENTS March 9, 2004
Davis Elementary School FM-200445097 3/9/04 Davis ( Maintenance T School Blitz ) Kitchen 1) Supply and install double sinks. Asbestos Code A - Clear for repairs on 03/12/04. Horne Engineering - Tony Marcolin (RG 03/15/04) March 9, 2004
Eastern High School FM-200445025 3/9/04 Eastern ( Maintenance T School Blitz ) Through-out 1) Paint (10 ) Stairwells. Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Eastern High School FM-200445026 3/9/04 Eastern ( Maintenance T School Blitz ) Second and Third Floor Corridor 1) Repair or replace 2,500 Lockers. Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Sheryll James (RG 03/11/04) March 9, 2004
Eastern High School FM-200445027 3/9/04 Eastern ( Maintenance T School Blitz ) Guidance Suite 1) Remove carpet and replace with floor tile. Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Sheryll James (RG 03/11/04) March 9, 2004
Eastern High School FM-200445028 3/9/04 Eastern ( Maintenance T School Blitz ) Team Rooms 1) Paint (12 ) Team Rooms. Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Eastern High School FM-200445030 3/9/04 Eastern ( Maintenance T School Blitz ) Corridors 1) Paint ( 5 ) levels of corridor walls. Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Eastern High School FM-200445031 3/9/04 Eastern ( Maintenance T School Blitz ) Teams Rooms 1) Up grade lighting in Team Rooms. Asbestos Code A - Clear for repairs on 03/11/04. Horne Engineering - Sheryll James (RG 03/12/04) March 9, 2004
Patricia R Harris Ed Center FM-200445121 3/9/04 Harris, P.R. Repair or replace commercial disposal. March 9, 2004
Johnson JHS FM-200445029 3/9/04 Johnson First floor hallway near gym and library One large window wire mesh glass need to be replaced near gymand one exit door window wire mesh glass need to be replace near library. Student vandalized. March 9, 2004
Simon Elementary School FM-200445070 3/9/04 Simon ( Maintenance T School Blitz ) Roof 1) Repair roof on Auditorium. Asbestos Code A - Clear for repairs on 04/29/04. Horne Engineering - Ray Agnant (RG 04/29/04) March 9, 2004
Simon Elementary School FM-200445073 3/9/04 Simon ( Maintenance T School Blitz ) Third Floor ( Various locations) 1) Supply (8) window air conditioners and electric upgrade to accommodate the a/c units. Asbestos Code A - Clear for repairs on 05/03/04. Horne Engineering - Tony Marcolin (RG 05/04/04) March 9, 2004
Simon Elementary School FM-200445074 3/9/04 Simon ( Maintenance T School Blitz ) First Floor 1) Paint corridor walls. Lead & Asbestos Code A - Clear for repairs on 03/12/04. Horne Engineering - Edward Rodriguez (RG 03/15/04) March 9, 2004
Stanton Elementary School FM-200445103 3/9/04 Stanton ( Maintenance T School Blitz ) Through-out 1) Electrical upgrade to accommdate air conditioners. Asbestos Code A - Clear for repairs on 03/11/04. Horne Engineering - Bipin Nanavaty (RG 03/16/04) March 9, 2004
Stanton Elementary School FM-200445105 3/9/04 Stanton ( Maintenance T School Blitz ) Annex 1) Repair and paint corridor walls. Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Tubman Elementary School FM-200445057 3/9/04 Tubman Repair / replace window latches in the following locations: Main office, Rooms 115, 111, 108, 206, 308, 305, 311, 303, lobby door and room 108. March 9, 2004
Turner Elementary School FM-200445083 3/9/04 Turner ( Maintenance T School Blitz ) Stairwell - Main Building. 1) Paint (2) stairwells in the Main Building. Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Turner Elementary School FM-200445084 3/9/04 Turner ( Maintenance T School Blitz ) Room - 100 and 205 1) Repair and Paint walls . Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Turner Elementary School FM-200445086 3/9/04 Turner ( Maintenance T School Blitz ) Exterior - Boiler Room 1) Unstop outside drain by Boiler Room. March 9, 2004
Walker-Jones EC FM-200445058 3/9/04 Walker-Jones ( Maintenance T School Blitz ) Corridors and 108 1) Lay carpet . ( Carpet is on site ) Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Ray Agnant (RG 03/12/04) March 9, 2004
Walker-Jones EC FM-200445060 3/9/04 Walker-Jones ( Maintenance T School Blitz ) First, Second and Third Floor 1) Paint Corridors Lead & Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Edward Rodriguez (RG 03/12/04) March 9, 2004
Walker-Jones EC FM-200445061 3/9/04 Walker-Jones ( Maintenance T School Blitz ) Through-out 1) Replace ceiling tile through-out the building. Asbestos Code A - Clear for repairs on 03/10/04. Horne Engineering - Ray Agnant (RG 04/23/04) SEE LINKED DOCUMENTS March 9, 2004
Wilkinson ES FM-200445090 3/9/04 Wilkinson ( Maintenance T School Blitz ) Gym 1) Repair Gym floor. Asbestos Code A - Clear for repairs on 03/11/04. Horne Engineering - Philp Connolly (RG 03/29/04) March 9, 2004
Wilkinson ES FM-200445093 3/9/04 Wilkinson ( Maintenance T School Blitz ) Through out 1) Repair (100) light fixtures. Asbestos Code A - Clear for repairs on 03/25/04. Horne Engineering - Philp Connolly (RG 04/02/04) March 9, 2004
Wilkinson ES FM-200445094 3/9/04 Wilkinson ( Maintenance T School Blitz ) 1) Repair Security Gates. ( 3 sets) March 9, 2004
Patricia R Harris Ed Center FM-200445167 3/10/04 (Harris) Big Gym: Toilet urinal out of order, and will not flush. March 10, 2004
Brookland Elementary FM-200445158 3/10/04 Brookland Roof Top / Exhaust Fan Repair or replace three burnt out exhaust fan motors. Name - Baldor Class - A Cy-60 Model -35G8-546 Frame - 56/513M HP- 1/2 Amps -1.8 RPM - 1725 PH-3 March 10, 2004
Patricia R Harris Ed Center FM-200445331 3/12/04 Harris, P.R. Kitchen Emergency justification because this area has not pass inspection because of a walkin freezer that is broken and need to be removed and tile along the basboard thar=t need to be fixed because it has come away from the wall. Asbestos Code A - Clear for repairs on 03/15/04. Horne Engineering - Philp Connolly (RG 03/17/04) March 12, 2004
Patricia R Harris Ed Center FM-200445333 3/12/04 (Harris,P.R.) Stairwell #3/On right side of stairs: No electrical power to light fixtures; stairwell is dark. March 12, 2004
Brookland Elementary FM-200445320 3/12/04 Brookland Roof Top Repair or replace exhaust fan for boys restroom, exhaust fan motor is burnt out. Name - Power line Volts - 120 PH-1 R.P.M. - 1300 Model - 90DE8X HP-110 CFM - 250 March 12, 2004
Oyster Elementary School FM-200445321 3/12/04 Oyster First floor cafeteria One broken double window pane need to be replaced. March 12, 2004
Patricia R Harris Ed Center FM-200445336 3/12/04 Harris, P.R. Restrooms and stairwell landings # 7 top floor area student restroom need ballances changed # 6 main floor student restroom also. # 7 restroom for students # 1 restroom need ballances changed. Asbestos Code A - Clear for repairs on 03/15/04. Horne Engineering - Philp Connolly (RG 03/17/04) March 12, 2004
Oyster Elementary School FM-200445328 3/12/04 Oyster first floor exit door Loading dock latch on exit door is broken. It need to be replace. Asbestos Code A - Clear for repairs on 03/16/04. Horne Engineering - Bjame Smith (RG 03/17/04) March 12, 2004
Patricia R Harris Ed Center FM-200445337 3/12/04 Harris, P.R. Each and every classroom that have electrical cords all over the floor Poles need to be putin each room to get the electrical cords uo off the floor. There needs to be some kind of electrical pole put up to get all of these cords up off the floor. Asbestos Code A - Clear for repairs on 03/15/04. Horne Engineering - Philp Connolly (RG 03/17/04) March 12, 2004
Benjamin Banneker Academic HS FM-200445311 3/12/04 Banneker Room #312 Replace stop valve on heating unit in room #312. Valve is not working. March 12, 2004
Benjamin Banneker Academic HS FM-200445309 3/12/04 Banneker Hallway Replace steam trap in hallway on heating unit by room #311. March 12, 2004
Patricia R Harris Ed Center FM-200445330 3/12/04 (Harris,P.R.) Asbestos Assessment Required. Restroom #7/Top Floor: Power outage due to broken tube, and bad ballast. Asbestos Code A - Clear for repairs on 03/15/04. Horne Engineering - Philp Connolly (RG 03/17/04) March 12, 2004
Coolidge High School FM-200445389 3/15/04 Coolidge Steps There are eight steps with cracks on them. Track meet is on Saturday. March 15, 2004
Patricia R Harris Ed Center FM-200445381 3/15/04 Harris, P.R. Main office back of school bldg. Electri plug do not work on one side of the room. Asbestos Code A - Clear for repairs on 03/17/04. Horne Engineering - Sheryll James (RG 03/19/04) March 15, 2004
Turner Elementary School FM-200445379 3/15/04 Turner Grounds Replace netting around windows where birds are nesting. March 15, 2004
Gibbs Elementary School FM-200445373 3/15/04 Gibbs Boys and Girls restroom Replace heating units that are not working and has been urinated on and rotton out and motors are inoperable. March 15, 2004
Patricia R Harris Ed Center FM-200445383 3/15/04 Harris, P.R. Pree-K area ground floor in front of bldg. Bad ballances in the light fixtures. Asbestos Code A - Clear for repairs on 03/18/04. Horne Engineering - Sheryll James (RG 03/19/04) March 15, 2004
Ferebee-Hope Elementary School FM-200445377 3/15/04 Ferebee-Hope First floor cafeteria Install proper lights inside the cafeteria. It is too dark for children to be eating in this area. Asbestos Code A - Clear for repairs on 03/17/04. Horne Engineering - Tony Marcolin (RG 03/18/04) March 15, 2004
Gibbs Elementary School FM-200445438 3/16/04 Gibbs Over Cafertia 1) Restore electrical service to exhaust fan motors on roof that service the cafertia two units fan are inoperable. March 16, 2004
Rudolph Elementary School FM-200445459 3/16/04 Rudolph Hallway across from room 200B Need roof repairing were roof is leaking. Asbestos Code A - Clear for repairs on 03/17/04. Horne Engineering - Philp Connolly (RG 03/19/04) March 16, 2004
Gibbs Elementary School FM-200445447 3/16/04 Gibbs Roof Over 1) Restore electrical service to two exhaust fan motors on the main roof of the building.One for room 215 and vice principal office. March 16, 2004
Coolidge High School FM-200445398 3/16/04 Coolidge Boiler Room Repair or replace defected burner, Boiler not working. Has only 1 out of 3 Boilers working. March 16, 2004
Gibbs Elementary School FM-200445445 3/16/04 Gibbs Main Building Replace Bearing to shaft. For exhaust fan motors Girls and Boys restroom. Main Building top bottom bearings. March 16, 2004
Wilkinson ES FM-200445391 3/16/04 Wilkinson Roof drains for the cooling tower Unstop roof drains for the cooling tower, dains need to be clear in order to clean the tower March 16, 2004
Gibbs Elementary School FM-200445444 3/16/04 Gibbs Lower Roof Rooms: 101; 102; kitchen and main office. 1) Restore electrical service to exhaust fan motors. March 16, 2004
Gibbs Elementary School FM-200445439 3/16/04 Gibbs Over Kitchen 1) Restore electrical service for kitchen hood inoperable. March 16, 2004
Meyer Elementary School FM-200445392 3/16/04 MEYER ES Replace LWCO on boilers # 1 and 2. (McDonnell # 63) Burners will not shut off under low water condition!!!!!!!! March 16, 2004
Benjamin Banneker Academic HS FM-200445484 3/17/04 Banneker Second floor boys restroom Electrician is needed for light fixture. Lights will not come on, fixtures were tested for proper voltage. Looked to have all its power. March 17, 2004
West Elementary School FM-200445473 3/17/04 West Boiler room Repair or replace Domestic hot water circulating pump, pump is down no hot water to the building. March 17, 2004
Hine JHS FM-200445470 3/17/04 Hine Roof cooling tower water supply line Repair or replace 8' feet of cooling tower water supply line 1 1/4", couplings and elbows . March 17, 2004
Slowe Elementary School FM-200445478 3/17/04 Slowe Throughout building Replace radiatior covers. 114-115-116-117-122-124-210-211-214 March 17, 2004
Backus Middle School FM-200445474 3/17/04 Backus Boiler room Replace the relief valve on the #1 storage DHW tank, Size 1" set 150 210 psi March 17, 2004
Shaed Elementary School FM-200445508 3/17/04 Shead Library/Stairwell Replace motor in univents in Library and stairwell. Model: #2PJDCARACWG-50111-000 Volts 120; AMP 4.0; PH 1; Control #484873 Stairwell no information on motor Basement floor no information on motor March 17, 2004
Ludlow-Taylor ES FM-200445524 3/17/04 (Ludlow-Taylor) Asbestos Assessment Required. 1st Floor/Multipurpose room: Roof leaking through ceiling in the above room. Asbestos Code A - Clear for repairs on 03/22/04. Horne Engineering - Bjarne Smith (RG 04/13/04) SEE LINKED DOCUMENTS March 17, 2004
Stanton Elementary School FM-200445567 3/18/04 (Stanton) 3rd Floor: Asbestos Assessment Required. Install air conditioners in the following rooms: Rooms #301, 304, 306, 308, & 313. Asbestos Code A - Clear for repairs on 03/23/04. Horne Engineering - Sheryll James (RG 03/25/04) March 18, 2004
Gibbs Elementary School FM-200445556 3/18/04 Gibbs Boiler Room Boiler #1 leaking tubes. March 18, 2004
Turner Elementary School FM-200445553 3/18/04 (Turner) Asbestos Assessment Required. 3rd Floor/Old Side: Water fountains need new filters installed, fountains are not pumping enough water out to drink. March 18, 2004
Patricia R Harris Ed Center FM-200445589 3/19/04 Harris. P.R. Ground large gym Repair or replace doors leading into large gym. In House has made all repairs that they can, and door does not lock from inside. Slide bolt is bent due to vandalism. See attachment Asbestos Code A - Clear for repairs on 02/24/04. Horne Engineering - Bjarne Smith (RG 05/03/04) SEE LINKED DOCUMENTS March 19, 2004
Stanton Elementary School FM-200445596 3/19/04 Stanton First, second and third floor Rooms 103, 106, 107, 108 need repairing. rooms on 2nd floor rooms 212, 210, 206, 204, 203 213, 205, 209, 211, 207 and 208. March 19, 2004
Reed LC FM-200445586 3/19/04 Reed Ground exterior lights Repair or replace twenty four (24) pole lights and twenty (20) other exterior lights. A lift will be needed. March 19, 2004
Gage-Eckington ES FM-200445587 3/19/04 Gage-Eckington First floor Ms. Williams room Panal bar on exit door needs replace (broken). Needed for security reasons. Asbestos Code A - Clear for repairs on 03/22/04. Horne Engineering - Bipin Nanavaty (RG 03/23/04) March 19, 2004
Ludlow-Taylor ES FM-200445618 3/19/04 Ludlow-Taylor Stairwell # 1 on Third floor landing Reinstall thermostat. March 19, 2004
Brent Elementary School FM-200445664 3/22/04 Brent Boiler Room Boiler #2 has leaking tubes. March 22, 2004
Bancroft Elementary School FM-200445631 3/22/04 Bancroft Ground bookroom main bldg. Repair / replace ventilator fan, it is not turning. March 22, 2004
Gibbs Elementary School FM-200445637 3/22/04 Gibbs Second floor room 205 First floor room 101 Class room door glass is shaddard need replacing in room 205. Replace window pane in room 101. March 22, 2004
Shaed Elementary School FM-200445686 3/23/04 Shead Boiler Room Replace (2) 5" OS&Y Valve on condenser side of Chiller. This is to prevent hot water from going into Chiller. March 23, 2004
Ludlow-Taylor ES FM-200445676 3/23/04 Ludlow-Taylor Hallway by North Stairwell Replace thermostat on the wall which was remove by unknown person, Thermostat. is not on site. March 23, 2004
Gibbs Elementary School FM-200445677 3/23/04 Gibbs Boiler room Replace bad spring coupling on the #1 Domestic hot water heat . March 23, 2004
Patricia R Harris Ed Center FM-200445764 3/24/04 (Harris, P.R.) !!EMERGENCY!!! !!!VANDALISM!!! VANDALISM Asbestos Assessment Required. Ground Floor/Outside at #6: Replace storage room doors at stairway #6, back of stairs, leading to the outside of the building, doors were vandalized previously. (Vandals will have easy access to the building if doors are not repaired. Asbestos Code A - Clear for repairs on 03/24/04. Horne Engineering - Bjarne Smith (RG 04/22/04) March 24, 2004
Seaton Elementary School FM-200445793 3/24/04 Seaton Second floor boys bathroom Repair or replace partition to stall near window. Asbestos Code A - Clear for repairs on 03/25/04. Horne Engineering - Tony Marcolin (RG 03/26/04) March 24, 2004
Turner Elementary School FM-200445757 3/24/04 (Turner) Asbestos Assessment Required. Outside Grounds: Please install new lights for school sign. March 24, 2004
Stanton Elementary School FM-200445792 3/24/04 Stanton Tree in garden need to be cut down it is a hazard!!!! March 24, 2004
Bunker Hill Elementary School FM-200445784 3/24/04 Bunker Hill Incinerator Room Repair steam leak on radiator pipe in incinerator. March 24, 2004
Woodson High School FM-200445816 3/24/04 Woodson Outside Overhinge by Main Office Repair busted pipe in overhinge by main office March 24, 2004
Gibbs Elementary School FM-200445749 3/24/04 Gibbs Boiler room Furnish (1) B& G series 110 pump for DHW. March 24, 2004
Garnet-Patterson MS FM-200445814 3/25/04 Garnet-Patterson boiler room Boiler #4 repair 2" leaking pipe. Pipe is approximately 12 feet high. March 25, 2004
Ludlow-Taylor ES FM-200445829 3/25/04 Ludlow-Taylor Basement boiler room Need two (2) cinder blocks to level off duplex oil strainer to stop oil leak. March 25, 2004
Kenilworth ES FM-200445813 3/25/04 Kenilworth All classrooms Repair or replace pneumatic controls on all Herman- Nelson univents outside air & Hot water temperture controls in all classrooms March 25, 2004
Johnson JHS FM-200445825 3/25/04 Johnson JHS Head Start Main Office 1) Replace existing carpet due to age and flooding. Asbestos Code A - Clear for repairs on 03/25/04. Horne Engineering - Roger Kager (RG 03/25/04) SEE LINKED DOCUMENTS March 25, 2004
Shaw JHS FM-200445849 3/25/04 Shaw Jr High Health clinic area Asbestos assessment required Install door louver's in the doors in the old health clinic area,as per Mr Rahimi's request. louver size 13 1/2" X 13 1/2" to assure proper air flow through-out. Asbestos Code A - Clear for repairs on 03/25/04. Horne Engineering - Edward (RG 03/26/04) March 25, 2004
Ferebee-Hope Elementary School FM-200445845 3/25/04 Ferebee-Hope Family Center Repair leaking univent in family center room. March 25, 2004
Ballou Senior High School FM-200445815 3/25/04 Ballou Kitchen,storeroom ceiling Replace broken AHU shaft assembly ,including shaft bearings,unit is needed for heat and ventilation. March 25, 2004
Spingarn High School FM-200445911 3/26/04 Spingarn Basement cafeteria Requesting an electrician to add extra outlets for soda machine along side that has an existing outlet. Asbestos Code A - Clear for repairs on 03/29/04. Horne Engineering - Bipin Nanavaty (RG 03/30/04) March 26, 2004
Patricia R Harris Ed Center FM-200445953 3/26/04 (Harris, P.R.) 1st Floor/Back of Building: Smoke coming from light fixtures across from wood shop. (Very strong burning smell) March 26, 2004
Horace Mann Elementary School FM-200445890 3/26/04 Mann Outside/New Wing: Brick wall has fallen down. March 26, 2004
Hine JHS FM-200445939 3/26/04 Hine Third floor gym by stairwell # 6 Exit light not working. March 26, 2004
Ferebee-Hope Elementary School FM-200446034 3/29/04 03/29/2004 12:01 EJ - !!!VANDALISM!!! (Ferebee-Hope) 1st Floor/Room #103: Screws were taken out of frame, and strips removed, vandals are responsible, and it appears that they will return again soon. March 29, 2004
Woodson High School FM-200445993 3/29/04 Woodson SHS Health Suite 1) Plastering is needed for walls, ceiling in the restrooms,bed/sleeping area. Plaster is falling . Lead & Asbestos Code A - Clear for repairs on 03/29/04. Horne Engineering - Edward Rodriguez (RG 03/30/04) March 29, 2004
Ross Elementary School FM-200445989 3/29/04 Ross 1) Furnish and install frames and screens for the following areas: a) Principal Office - 2 screens b) First Floor - Pre K - 3 screens and 2 frames c) First Floor - Ms. Hoo Room - 2 screens d) Second Floor - Mr. Ucles Room - 3 screens March 29, 2004
Cardozo High School FM-200446021 3/29/04 Cardozo EMERGENCY!!!!! Interior of bldg. Clear drains in all working water fountains for water testing. March 29, 2004
Reed LC FM-200446077 3/30/04 Reed Outside exterior walls and other surface Remove graffitti from school walls and other areas on the grounds. March 30, 2004
Spingarn High School FM-200446111 3/30/04 Spingarn VANDALISM Secondt floor stairway # 5 Requesting a glaze person to measure and replace wire mess glass door, that was broken by student. March 30, 2004
Patricia R Harris Ed Center FM-200446075 3/30/04 Harris, P.R. Room 323 Door handle broken off need replacing. Asbestos Code A - Clear for repairs on 04/05/04. Horne Engineering - Bipin Nanavaty (RG 04/07/04) March 30, 2004
Reed LC FM-200446113 3/30/04 Reed Pool area Repair or replace motor for swimming pool. March 30, 2004
Wilson High School FM-200446102 3/30/04 Wlison, W. First floor below library Repair or replace classroom door can not be secured properly. Asbestos Code A - Clear for repairs on 03/31/04. Horne Engineering - Bipin Nanavaty (RG 04/05/04) March 30, 2004
Garfield ES FM-200446079 3/30/04 Garfield D-wing Repair railing in the demanables. plastering in need to do the repairs. Asbestos Code A - Clear for repairs on 03/31/04. Horne Engineering - Bjame Smith (RG 04/02/04) March 30, 2004
Patricia R Harris Ed Center FM-200446076 3/30/04 Harris, P.R. Room 329 Door still split and about to break in half. Please respond ASAP. Second time putting this in for repairs. Asbestos Code A - Clear for repairs on 04/09/04. Horne Engineering - Sheryll James (RG 04/13/04) March 30, 2004
Browne Junior High School FM-200446108 3/30/04 Brown Center Third floor hallway Furnish and install (11) eleven flourescent lamp ballasts, (special ed). Asbestos Code A - Clear for repairs on 03/31/04. Horne Engineering - Philp Connolly (RG 04/06/04) March 30, 2004
Young Elementary School FM-200446174 3/31/04 YOUNG Tunnel Asbestos assessment may be neccessary for pipe insulation. Repair rupture 4" heating hot water supply line that can not be isolated. Asbestos Code A - Clear for repairs on 04/01/04. Horne Engineering - Tony Marcolin (RG 04/06/04) March 31, 2004