Open Repair Requests in May 2003

Open Repairs Summary

  • Urgent Requests
    10
  • Routine Requests
    65
  • Total Requests
    75

Detailed Reports

Urgent Repair Requests Opened in May 2003 (10)
School Description Open Date
Browne Junior High School FM-200329332 5/1/03 (Browne) !!!VERY URGENT!!! Outside Shed: Repair or replace door, door is damaged, and will not open. Asbestos Code A - Clear for repairs on 05/01/03. Horne Engineering - Troy Wilcome (RG 05/05/03) May 1, 2003
Benning Elementary School FM-200329434 5/2/03 (Benning) !!!URGENT!!! Main Floor/Cafeteria/Kitchen: All exit lights are out in this area. May 2, 2003
Lafayette Elementary School FM-200330101 101 5/13/03 LaFayette First Floor - Team #2 1. Replace ceiling tile that was damaged by univent leak . Asbestos Code A - Clear for repairs on 05/13/03. DCPS Safety - Richard Gibson (RG) May 13, 2003
West Elementary School FM-200330343 5/19/03 (West) !!!URGENT!!! Outside/6th grade classroom door: Light switch needs cover plate. May 19, 2003
Young Elementary School FM-200330326 5/19/03 Young Courtyard out side custodian's office by Gymnasium. 1) Install approximately 40 ' of expanded metal above existing 6' high wall to keep children from climbing the wall and going up on the roof. # Note - Kids play kickball and climb up on this wall to retrieve their kickball which is very dangerous. May 19, 2003
Wilson High School FM-200330417 5/20/03 (Wilson, W.) !!!VERY URGENT!!! Asbestos Assessment Required. 3rd Floor/Room #311: Badly damaged door, we are unable to secure. Valuable equipment in this room. Asbestos Code A - Clear for repairs on 05/21/03. Horne Engineering - Sharon Voss (RG 05/22/03) May 20, 2003
Garnet-Patterson MS FM-200330504 5/21/03 (Garnet-Patterson) !!!URGENT!!! 1st Floor/Boys bathroom:l Cold water stem broke completely off faucet; water leaking, (Engineer has shut the water off) May 21, 2003
Wilson High School FM-200330620 5/22/03 Wilson !! URGENT !! First Floor - Stairwell 1. Repair handrail in stairwell ( near room 143 ) leading down to the art room area . 1. Unstop drain in the courtyard and clean out sewer outside of the horseshoe door . Asbestos Code A - Clear for repairs on 05/23/03. Horne Engineering - Philp Connolly (RG 05/27/03) May 22, 2003
Turner Elementary School FM-200330636 5/23/03 Turner URGENT First Floor - classroom #100 1. Repair ceiling and wall where plaster is peeling and falling on children in classroom Lead & Asbestos Code A - Clear for repairs on 05/27/03. Horne Engineering - Edward Rodriguez (RG 05/28/03) May 23, 2003
Turner Elementary School FM-200330943 5/30/03 (Turner) !!!VERY URGENT!!! Main Floor/Principal's Office: Wooden door frame badly deteriorated; foundation completely gone. Asbestos Code A - Clear for repairs on 06/02/03. Horne Engineering - Tony Marcolin (RG 06/03/03) May 30, 2003

Routine Repair Requests Opened in May 2003 (65)
School Description Open Date
Wilson High School FM-200329314 5/1/03 Wilson, W Pool Filtration Room Furnish twelve (12) Pool De Filter Elements for main pool & two (2) pool de filter elements for small pool. Presently filter elements are torn and de is being circulated into pool water. NO ASBESTOS IN THIS AREA. May 1, 2003
Woodson High School FM-200329377 5/2/03 H.D Woodson Pool Room First Floor 1. Check on lights for replacement 1. Check all chemical level 2. Added chemcials 3. Added water 4. Adjust heat transfer 5. Fill out log 6. Back wash filter May 2, 2003
Takoma Educational Center FM-200329362 5/2/03 Takoma Second floor room 128 Repair breech in ceiling in girls bathroom. Asbestos Code A - Clear for repairs on 05/05/03. Horne Engineering - Tony Marcolin (RG 05/06/03 May 2, 2003
Takoma Educational Center FM-200329367 5/2/03 Takoma All staircases Lights on all staircases are in need of changing. This areas can not be reach and is impossible to be changed by staff. May 2, 2003
Thomas Elementary School FM-200329494 5/5/03 Thomas Kitchen 1) The following equipment needs to be disconnected. a) Oven - Travlsen b) Freezer - Glenco - 3510 c) Refrigerator - Glenco - 254 d) Refrigerator - Penn - 703C May 5, 2003
Powell Elementary School FM-200329551 5/5/03 Powell Kitchen 1) The following equipment needs to be disconnected. a) Steamer - Market Forge May 5, 2003
Moten Elementary School FM-200329530 5/5/03 Moten Ground floor B-14 Leak in ceiling. Asbestos Code A - Clear for repairs on 05/05/03. Horne Engineering - Edward Rodriguez (RG 05/06/03) May 5, 2003
Kramer Middle School FM-200329499 5/5/03 (Kramer Middle School) Asbestos Assessment Required. 1st Floor/Boys bathroom: Repair ceiling Due to previous leak, ceiling is still very moist, and very large portions have falling down on the bathroom urinals. Asbestos Code A - Clear for repairs on 05/05/03. Horne Engineering - Edward Rodriguez (RG 05/06/03) May 5, 2003
Barnard Elementary School FM-200329559 9 5/5/03 Barnard Kitchen 1) The following equipment needs to be disconnected. a) Refrigerator - Foster - DPC 3434 b) Freezer - Traulsen - 359 May 5, 2003
Hyde Elementary School FM-200329596 5/5/03 Hyde !!! EMERGENCY !!! Basement Level 1. provide electrical outlet for oven to be relocated from the basement to new location. Asbestos Code A - Clear for repairs on 05/05/03. Horne Engineering - Bipin Nanavaty (RG 05/07/03) May 5, 2003
Tubman Elementary School FM-200329540 5/5/03 Tubman Kitchen 1) The following equipment needs to be disconnected. a) Refrigerator - Norlake - 94080985 May 5, 2003
Truesdell Elementary FM-200329560 5/5/03 Truesdell Kitchen 1) The following equipment needs to be disconnected. a) Refrigerator - Norlake - 8302962 b) Dishmachine c) Warmer May 5, 2003
Takoma Educational Center FM-200329663 5/6/03 (Takoma) 3rd Floor/Room #222: Repair broken toilets, and urinals in the boys restrooms May 6, 2003
Benjamin Banneker Academic HS FM-200330007 5/6/03 Remove 4 existing window panels and window A/C units. 1 unit is located in the new basement level science lab preparation room, 2 units in the new basement level science lab proper and 1 in the lab adjacent chemical storage room. Replace window sash at all four windows, patch, prime and paint A/C opening in the window guards. Install 3 full-length window shades to complete window shade coverage in the first floor science lab and 6 full-length window shades in the basement science lab. DCPS to salvage three existing half-length window shades and four window air conditioners from the first floor and basement science labs. Asbestos & Lead Code A - Clear for repairs on 05/19/03. Horne Engineering - Edward Rodriguez (RG 05/20/03) May 6, 2003
Shepherd ES FM-200329683 5/6/03 (Shepherd) Asbestos Assessment Required. Replace / repair wood transition decks and touch up paint on the existing composite playground equipment. Repair / Replace existing protective surface located below the composite playground equipment. Asbestos & Lead Code A - Clear for repairs on 05/19/03. Horne Engineering - Edward Rodriguez (RG 05/20/03) May 6, 2003
Seaton Elementary School FM-200329699 5/7/03 Seaton Exterior Grounds 1) Paint exterior rear and front window guards, paint fence. 2) Paint map of world on ground. 3) Paint basketball lines and court. 4) Tire flower pot project. 5) Create kick ball field. Poc - City Year - Emily Cherniack - 202-742-7400 Lead & Asbestos Code A - Clear for repairs on 05/07/03. Horne Engineering - Edward Rodriguez (RG 05/08/03) May 7, 2003
Shaed Elementary School FM-200329734 5/7/03 (Shaed) 2nd Floor/L-2: Replace ceiling track, and tile that was removed due to broken pipe (Material on-site) Asbestos Code A - Clear for repairs on 05/08/03. Horne Engineering - Edward Rodriguez (RG 05/12/03) May 7, 2003
Wilson High School FM-200329757 5/8/03 Wilson, W S.H.S. Courtyard-Outside Armory Repair leak and replace freon in condenser unit for elevator. No asbestos in this area. May 8, 2003
Kimball Elementary School FM-200329823 3 5/8/03 (Kimball) Outside/Ely Place side: Repair handrails coming up from the sidewalk. May 8, 2003
Kenilworth ES FM-200329876 9876 5/9/03 Kenilworth Throughout building Room that need new installation of A/C units. Room 100, 108, 147, Teachers lounge (2), counselor office and library (2). May 9, 2003
Kenilworth ES FM-200329879 9879 5/9/03 Kenilworth Throughout building Replace spot coolers with A/C units in the following locations: Room 129, 211, 213, 301, 302, 312, 313 and health suite. May 9, 2003
Ferebee-Hope Elementary School FM-200329975 5/9/03 (Ferebee-Hope) Basement boiler room and Computer room: Drains backing up in the boiler room. Drains backing up in Lobby/C-building. May 9, 2003
Cook J.F. Elementary School FM-200329961 5/9/03 Cook, J.F. Room #203 Need electrician to check current to outlet. Repair or replace A/C window unit in room #203. Current unit has electrical shortage, 23,000 BTU's May 9, 2003
Smothers ES FM-200329896 5/9/03 Smothers Main office Install lexan glass in windows that currently have window A/C units in them. Once the window units have been removed. NOTE: A service order has been initiated for their removal. May 9, 2003
West Elementary School FM-200330028 5/12/03 West Air Handler Unit #7 Basement Repair or replace starter coil Name: Westing Huse AMP-45 Size-2 Cat#A200M2CAC Style-765A842GO V-200/230 Phase-3 H.P-200, Starter has pull in and will not release #7 Air Handler Unit cools the library May 12, 2003
Emery Elementary School FM-200330228 5/13/03 Replace screens in windows in room 203,teacherlounge,217,301,303,305A and B 315,317,319.Screen are on site. May 13, 2003
Bowen Elementary School FM-200330077 5/13/03 Bowen Boiler room - Floor Drains Unstop floor drains in the boiler room ,standing water. May 13, 2003
Benjamin Banneker Academic HS FM-200330151 5/14/03 Banneker Basement teacher cafeteria A hole in the wall behind the water fountain. It needs to be patched up. This is a fire code violation. Asbestos Code A - Clear for repairs on 05/14/03. Horne Engineering - Bipin Nanavaty (RG 05/15/03) May 14, 2003
Gage-Eckington ES FM-200330145 5/14/03 (Gage Eckington) 1st Floor/Pre-Kindergarten Classroom: Door will not close properly due to problem with door. (Door jam) Need s to be secured. Asbestos Code A - Clear for repairs on 05/14/03. Horne Engineering - Bipin Nanavaty (RG 05/15/03) May 14, 2003
Gage-Eckington ES FM-200330134 5/14/03 (Gage-Eckington) On top of roof drain: The drain on the roof need to be unstopped; water on roof is accumulating where rain is coming in-to the building. May 14, 2003
Cardozo High School FM-200330210 5/15/03 Cardozo Welder need to cut roof drain line fabricate. So plumber can snake out line. Note: Two waste line. May 15, 2003
Davis Elementary School FM-200330214 5/15/03 (Davis) Basement, lunchroom, and Maintenance office: Doors need alignment, they drag floor when you open and close. Asbestos Code A - Clear for repairs on 05/16/03. Horne Engineering - Sharo Voss (RG 05/19/03) May 15, 2003
Ross Elementary School FM-200330212 5/15/03 Ross Plaster need to plaster wall on third floor by principal office. May 15, 2003
Browne Junior High School FM-200330264 5/16/03 Browne Basement stairwell new side near new gym Replace metal thread on step. Missing meat thread creating a tripping hazard. Asbestos Code A - Clear for repairs on 05/16/03. Horne Engineering - Sheryll James (RG 05/19/03) May 16, 2003
Browne Junior High School FM-200330266 5/16/03 Browne Basement new side across from new gym Brench in wall. Wall and tiles need to be repair / replace. Asbestos Code A - Clear for repairs on 05/16/03. Horne Engineering - Sheryll James (RG 05/19/03) May 16, 2003
Nalle Elementary School FM-200330242 5/16/03 Nalle !! EMERGENCY !! First Floor - Classroom #118 1. Repair major roof leak in classroom . May 16, 2003
Slowe Elementary School FM-200330249 5/16/03 Slowe !! EMERGENCY !! Second Floor - Hallway ( New Bldg. ) 1. Repair roof leak in the hallway in front of classroom # 211 . May 16, 2003
Meyer Elementary School FM-200330318 5/19/03 Meyer Couselors office first floor Window was broken over week end in front of the building. Need to be repair ASAP. May 19, 2003
Gage-Eckington ES FM-200330331 5/19/03 Gage-Eckington Boiler Room Check condenser pump in boiler room. Pump is making loud noise. B&G Pump # 1510 Ser.# 2094399 ID.# 1BAO85 Model # 4BC95 BF RPM 540 GP 65 feet HP 15 PSI 175 May 19, 2003
Young Elementary School FM-200330333 5/19/03 Young Outside east of building Replace vertical drain pipe that has burst open, from west tear. P.S. this pipe that the down spout drains into. May 19, 2003
Bunker Hill Elementary School FM-200330306 5/19/03 Bunker Hill Second floor west wing outside Middle wing outside Repair gutter. Water pours over side of building when it rains. Water runs down side od buildind when it rains hard , seeping through wall causing leaks in ceiling in room 111. May 19, 2003
Eastern High School FM-200330312 5/19/03 Eastern Wood shop - armory and gym Repair roof leaks wood shop leaking from skylight. May 19, 2003
Garnet-Patterson MS FM-200330505 5/21/03 (Garnet-Patterson) 1st Floor/Room #107: Window shattered, please replace. May 21, 2003
Takoma Educational Center FM-200330632 5/22/03 Takoma Third floor room 184 We are requesting a temporary partition 1/2 wall to be removed from class area to enlarge class area. This project needs to be completed ASAP due to summer cleaning is about to be in session. Lead & Asbestos Code A - Clear for repairs on 02/23/03. Horne Engineering - Edward Rodriguez (RG 05/27/03) May 22, 2003
Patricia R Harris Ed Center FM-200330583 5/22/03 Harris, P.R. / Patterson Third floor boys room stairwell 4 Repair partition broke loose from floor tiles. Asbestos Code A - Clear for repairs on 02/22/03. Horne Engineering - Sharon Voss (RG 05/27/03) May 22, 2003
Eliot Junior High School FM-200330621 5/22/03 Eliot Library Replace bad bearing on the air handler for the split system in the library, bearing are non-lubricating type. 3/4" shaft. Asbestos Code A - Clear for repairs on 03/18/04. Horne Engineering - Bjame Smith (RG 03/19/04) May 22, 2003
Coolidge High School FM-200330585 5/22/03 Coolidge Third Floor - Rear Corridor 1) Ceiling needs to be plasterd and painted. Damage came from roof and drain repairs. Lead & Asbestos Code A - Clear for repairs on 05/22/03. Horne Engineering - Edward Rodriguez (RG05/23/03) May 22, 2003
Benning Elementary School FM-200330656 5/23/03 Benning Main Roof Repair or replace exhaust fan #4 MFR: Greenheck - MOD-CEE104 Motor MFR: General Electric - HP- 1/4; V-115 RPM-1725 A; 4.7 Cy 60 Fr: 48 PH-1 Belt 3L210 May 23, 2003
Benning Elementary School FM-200330655 5/23/03 Benning Main Roof Repair or replace exhaust fan #3 MFR: Greenheck - MOD-CE96 Motor MFR: Fasco - HP- 1/20; V-115 RPM-1050 A; 2.0 Cy 60 PH-1 Direct Drive May 23, 2003
Benning Elementary School FM-200330653 5/23/03 Benning Main Roof Repair or replace exhaust fan #1. MFR: Greenhouse - MOD-CEE245 Motor MFR: Marathon - HP- 1/2; V-208-230-460 RPM-1725 A; 2.0-1.0 Fr:56 Cy 60 PH-3 Belt 4L400 May 23, 2003
Rudolph Elementary School FM-200330642 5/23/03 (Rudolph) 2nd Floor/Near Room #214: Replace double door fire glass in hallway door. Please respond as soon as possible, as this is a potential fire code violation. May 23, 2003
Ferebee-Hope Elementary School FM-200330720 5/27/03 (Ferebee-Hope) 2nd Floor/Ms. York's area: Repair leaks around window frame; carpet getting mildew. May 27, 2003
Reed LC FM-200330795 5/28/03 REPAIR/REPLACE SUMP PUMP OR EJECTOR Repair inoperable sump pump. Boiler room will flood. May 28, 2003
Slowe Elementary School FM-200330860 5/29/03 Outside - Lights are out. 01/11/2007 08:49 TH - Second request was faxed in on 1-10-07 May 29, 2003
Slowe Elementary School FM-200330859 5/29/03 (Slowe) First floor All multi purpose Room (divider) need to be put back on track. Asbestos Code A - Clear for repairs on 05/30/03. Horne Engineering - Roger Kager (RG 06/02/03) May 29, 2003
Tubman Elementary School FM-200330837 5/29/03 Tubman Through - Out Building 1. Paint the entire building from the first to the third floor . Lead & Asbestos Code A - Clear for repairs on 05/29/03. Horne Engineering - Roger Kager (RG 05/30/03) May 29, 2003
Marshall Educational Center FM-200330888 0330888 5/29/03 Thurgood Marshall Pool Roof Drains First Floor Roofing Department need to repair roof drains. Drains are leaking in four locations around flanges. Tiles have been removed in area were leaks are (4 drains total) May 29, 2003
Bell High School FM-200330891 5/29/03 Bell M.C Main Roof Correct problem thats causing water to leak into room # 201a from roof. Problem occurs when cooling tower over-flow. May 29, 2003
Wilkinson ES FM-200330884 5/29/03 (Wilkinson) Through Out the Building: Fluorescent lights are operating intermittently in the following rooms: 2nd Floor, electrical room, hall corridor, boys bathroom, women restroom,. Room #180, 181,182, and 184. May 29, 2003
Stevens Elementary School FM-200330828 5/29/03 Stevens Second Floor - North side ( near science Room) 1. Plaster ceiling damaged by water leaking from wall , (plaster is falling from ceiling). Asbestos Code A - Clear for repairs on 05/29/03. Horne Engineering - Bipin Nanavaty (RG 05/30/03) May 29, 2003
Beers Elementary School FM-200330922 5/30/03 (Beers) Building #2/1st Floor: The PTA has a TV set installed in the wall; outlets are needed for connection. Asbestos Code A - Clear for repairs on 05/30/03. Horne Engineering - Troy Wilcome (RG 06/03/03) May 30, 2003
Reed LC FM-200330914 5/30/03 Reed, Marie Three male restrooms - center 1 and 3 Re-attach four petitions to walls in male restroms. Asbestos Code A - Clear for repairs on 05/30/03. Horne Engineering - Roger Kager (RG 06/02/03) May 30, 2003
Oyster Elementary School FM-200330905 5/30/03 Oyster Roof front roof drains and gutters Roof drains and gutters need cleaning out. Gutters are stopped up causing flooding inside classrooms. May 30, 2003
Patricia R Harris Ed Center FM-200330946 5/30/03 (Harris, P.R./Patterson) 3rd Floor Girls bathroom/Stairwell #6: Replace stop valves on two (2) leaking toilets. May 30, 2003
Reed LC FM-200330912 5/30/03 Reed, Marie First floor early childhood male restroom Survey and replace missing floor tile (small ceramic tile). Asbestos Code A - Clear for repairs on 06/02/03. Horne Engineering - Sharon Voss (RG 06/02/03) May 30, 2003